Acti 9 iPRD20 modular surge arrester - 3P + N - 350V - A9L20600
This Acti9 iPRD20 surge arrester protects 3P+N installations.
It allows quick replacement of damaged cartridges.
This Type 2 device is recommended for medium risk level and incoming panel board.
It can be turned over to allow the phase/neutral/earth cables to enter through either the top or the bottom.
The associated circuit breaker Isc breaking capacity can go up to 50kA.
This Acti9 iPRD20 is compatible with TT and TN-S earthing system.
The Imax rated discharge current is 20kA.
The In nominal discharge current is 5kA.
The Uc maximum continuous operating voltage in common mode is 260VAC between neutral and earth, and 350VAC between phase and earth.
The Up Voltage protection level in differential mode (between phase and neutral) is 1.1kV.
The Up Voltage protection level in common mode (between neutral and earth) is 1.4kV.
The Ue operating voltage is 230VAC or 400VAC +/- 10%.
The operating frequency is 50Hz or 60Hz.
The dimensions are (W) 72mm x (H) 85mm x (D) 69mm.
The width in 9mm pitches is 8.
The weight is 450g.
The degree of protection is IP20 and IP40 in modular enclosure.
The operating temperature is -25°C to 60°C.
The storage temperature is -40°C to 85°C.
This product is compliant with EN 61643-11 and IEC 61643-11 standards.
Attribute | Value |
---|---|
SKU | A9L20600 |
product certifications | CE |
relative humidity | 5-95 % |
ambient air temperature for storage | -40-85 °C |
ambient air temperature for operation | -25-60 °C |
quality labels | NF, KEMA-KEUR |
range of product | iPRD |
product or component type | Surge Arrester |
net weight | 0.414 kg |
mounting mode | clip-on |
standards | IEC 61643-11:2011, EN 61643-11:2012 |
device short name | iPRD20 |
range | Acti 9 |
surge arrester class type | type 2 |
maximum discharge current | common mode: 20 kA L/PE, common mode: 20 kA N/PE, differential mode: 20 kA L/N |
IK degree of protection | IK03 conforming to IEC 62262 |
product name | Acti 9 iPRD |
surge arrester type | electrical distribution network |
residual current | 0.003 mA, 0.6 mA |
connections - terminals | tunnel type terminal (downside) 2.5-35 mm², tunnel type terminal (upside) 2.5-35 mm² |
height | 85 mm |
mounting support | DIN rail |
compatibility code | iPRD20 |
width | 72 mm |
depth | 69 mm |
operating altitude | 2000 m |
IP degree of protection | IP40 on front face: conforming to IEC 60529, IP20 built-in: conforming to IEC 60529 |
9 mm pitches | 8 |
poles description | 3P + N |
colour | white (RAL 9003) |
tightening torque | 2.5-2.5 N.m |
device application | distribution |
[Ue] rated operational voltage | 230/400 V AC (+/- 10 %) at 50/60 Hz |
disconnector device type | associated circuit breaker NG125H 63 A curve C - Icu 36 kA, associated circuit breaker NG125L 63 A curve C - Icu 50 kA, associated fuse gG 80 A - Icu 50 kA, associated circuit breaker iC60N 20 A curve C - Icu 10 kA, associated circuit breaker iC60H 20 A curve C - Icu 15 kA, associated circuit breaker iC60L 20 A curve C - Icu 25 kA, associated fuse gG 40 A - Icu 15 kA |
surge arrester technology | MOV + GDT |
[Ut] temporary overvoltage | 337 V L/N 5 s withstand, 442 V L/PE 5 s withstand, 1200 V N/PE 200 ms safe failure mode, 1453 V L/PE 200 ms safe failure mode |
response time | <= 25 ns |
maximum [Up] voltage protection level | common mode <1.4 kV type 2 N/PE, differential mode <1.1 kV type 2 L/N |
nominal discharge current | common mode: 5 kA (L/PE), common mode: 5 kA (N/PE), differential mode: 5 kA (L/N) |
earthing system | TT, TN-S |
[Uc] maximum continuous operating voltage | common mode: 260 V N/PE, common mode: 350 V L/PE, differential mode: 350 V L/N |
remote signalling | without |
short-circuit withstand | 50 kA |