Acti 9 iPRD65r modular surge arrester - 1P - 350V - with remote transfert - A9L65101
This Acti9 iPRD65r surge arrester protects 1P installations.
It allows quick replacement of damaged cartridges.
This Type 2 device is recommended for very high risk level and incoming panel board.
It offers remote reporting of the "cartridge must be changed" message.
It can be turned over to allow the phase/neutral/earth cables to enter through either the top or the bottom.
The associated circuit breaker Isc breaking capacity can go up to 50kA.
It is compatible with TT and TN-S earthing system.
The Uc maximum continuous operating voltage in common mode (L/PE or N/PE) is 350VAC.
The Up Voltage protection level in common mode (between phase and earth) is 1.5kV.
The Ue rated operational voltage is 230VAC +/- 10%.
The product colour is white (RAL9003).The dimensions are (W) 18mm x (H) 85mm x (D) 69mm.
The weight is 136g.
The degree of protection is IP20 and IP40 in modular enclosure.
The operating temperature is -25°C to 60°C.
The storage temperature is -40°C to 85°C.
This product is compliant with EN 61643-11 and IEC 61643-11 standards.
Attribute | Value |
---|---|
SKU | A9L65101 |
product certifications | CE |
relative humidity | 5-95 % |
ambient air temperature for storage | -40-85 °C |
ambient air temperature for operation | -25-60 °C |
quality labels | NF, KEMA-KEUR |
range of product | iPRD |
product or component type | Surge Arrester |
net weight | 0.136 kg |
mounting mode | clip-on |
standards | IEC 61643-11:2011, EN 61643-11:2012 |
device short name | iPRD65r |
range | Acti 9 |
surge arrester class type | type 2 |
maximum discharge current | common mode: 65 kA L/PE |
IK degree of protection | IK03 conforming to IEC 62262 |
product name | Acti 9 iPRD |
surge arrester type | electrical distribution network |
signalling circuit voltage | 0.25 A/250 V AC 50/60 Hz |
residual current | 0.003 mA, 0.6 mA |
connections - terminals | tunnel type terminal (downside) 2.5-35 mm², tunnel type terminal (upside) 2.5-35 mm² |
height | 85 mm |
mounting support | DIN rail |
compatibility code | iPRD65r |
width | 18 mm |
depth | 69 mm |
operating altitude | 2000 m |
IP degree of protection | IP40 on front face: conforming to IEC 60529, IP20 built-in: conforming to IEC 60529 |
9 mm pitches | 2 |
poles description | 1P |
colour | white (RAL 9003) |
tightening torque | 2.5-2.5 N.m |
device application | distribution |
[Ue] rated operational voltage | 230/400 V AC (+/- 10 %) at 50/60 Hz |
disconnector device type | associated circuit breaker iC60H 50 A curve C - Icu 15 kA, associated fuse gG 80 A - Icu 50 kA, associated circuit breaker iC60N 50 A curve C - Icu 10 kA, associated circuit breaker NG125N 50 A curve C - Icu 25 kA, associated circuit breaker NG125H 100 A curve C - Icu 36 kA, associated circuit breaker NG125L 100 A curve C - Icu 50 kA |
surge arrester technology | MOV |
[Ut] temporary overvoltage | 337 V L/N 5 s withstand, 1200 V N/PE 200 ms safe failure mode |
response time | <= 25 ns |
maximum [Up] voltage protection level | common mode <1.5 kV type 2 L/PE |
nominal discharge current | common mode: 20 kA (L/PE), common mode: 20 kA (N/PE) |
earthing system | TN-C, IT 230 |
[Uc] maximum continuous operating voltage | common mode: 350 V L/PE, common mode: 350 V N/PE |
signal contacts composition | 1 SD (1 C/O) |
remote signalling | with |
short-circuit withstand | 50 kA |