Acti 9 iPRD8r modular surge arrester - 1P + N - 350V - with remote transfert - A9L08501
This Acti9 iPRD8r surge arrester protects 1P+N installations.
It allows quick replacement of damaged cartridges.
The Imax maximum discharge current is 8kA .The In nominal discharge current is 2.5kA.
The iPRD8r ensures secondary protection of loads to be protected and is placed in cascade with the incoming surge arresters.
This surge arrester is required when the loads to be protected are at a distance of more than 10 m from the incoming surge arrester.
The surge arresters with "r" indication have remote transfer of the information "Cartridge to be replaced".
The Uc maximum continuous operating voltage in common mode is 260VAC between neutral and earth, and is 350VAC between phase and earth.
The Uc maximum continuous operating voltage in differential mode (between phase and neutral) is 350VAC.
The Up Voltage protection level in common mode is 1.4kV between neutral and earth in type 2, and 1.1kV between neutral and earth in type 3.
The Up Voltage protection level in differential mode (between phase and neutral) is 1kV in type 2, and 1.1kV in type 3.
The Ue rated operational voltage is 230VAC +/- 10%.
The product colour is white (RAL9003).The dimensions are (W) 36mm x (H) 85mm x (D) 69mm.
The weight is 215g.
The degree of protection is IP20 and IP40 in modular enclosure.
The operating temperature is -25°C to 60°C.
The storage temperature is -40°C to 85°C.
This product is compliant with EN 61643-11 and IEC 61643-11 standards.
Attribute | Value |
---|---|
SKU | A9L08501 |
product certifications | CE |
relative humidity | 5-95 % |
ambient air temperature for storage | -40-85 °C |
ambient air temperature for operation | -25-60 °C |
quality labels | NF, KEMA-KEUR |
range of product | iPRD |
product or component type | Surge Arrester |
net weight | 0.215 kg |
mounting mode | clip-on |
standards | IEC 61643-11:2011, EN 61643-11:2012 |
device short name | iPRD8r |
range | Acti 9 |
surge arrester class type | type 2 + 3 |
maximum discharge current | common mode: 8 kA L/PE, common mode: 8 kA N/PE, differential mode: 8 kA L/N |
IK degree of protection | IK03 conforming to IEC 62262 |
product name | Acti 9 iPRD |
surge arrester type | electrical distribution network |
signalling circuit voltage | 0.25 A/250 V AC 50/60 Hz |
residual current | 0.003 mA, 0.6 mA |
[Uoc] open circuit voltage | 10 kV type 3 common mode N/PE, 10 kV type 3 differential mode L/N |
connections - terminals | tunnel type terminal (downside) 2.5-35 mm², tunnel type terminal (upside) 2.5-35 mm² |
height | 85 mm |
mounting support | DIN rail |
compatibility code | iPRD8r |
width | 36 mm |
depth | 69 mm |
operating altitude | 2000 m |
IP degree of protection | IP40 on front face: conforming to IEC 60529, IP20 built-in: conforming to IEC 60529 |
9 mm pitches | 4 |
poles description | 1P + N |
colour | white (RAL 9003) |
tightening torque | 2.5-2.5 N.m |
device application | distribution |
[Ue] rated operational voltage | 230/400 V AC (+/- 10 %) at 50/60 Hz |
disconnector device type | associated fuse gG 80 A - Icu 50 kA, associated circuit breaker iC60L 10 A curve C - Icu 25 kA, associated circuit breaker iC60N 10 A curve C - Icu 10 kA, associated circuit breaker iC60H 10 A curve C - Icu 15 kA, associated fuse gG 25 A - Icu 15 kA |
surge arrester technology | MOV + GDT |
[Ut] temporary overvoltage | 337 V L/N 5 s withstand, 442 V L/PE 5 s withstand, 1200 V N/PE 200 ms safe failure mode |
response time | <= 25 ns |
maximum [Up] voltage protection level | common mode <1.4 kV type 2 N/PE, common mode <1.1 kV type 3 N/PE, differential mode <1 kV type 2 L/N, differential mode <1.1 kV type 3 L/N |
nominal discharge current | common mode: 2.5 kA (L/PE), common mode: 2.5 kA (N/PE), differential mode: 2.5 kA (L/N) |
earthing system | TT, TN-S |
[Uc] maximum continuous operating voltage | common mode: 260 V N/PE, common mode: 350 V L/PE, differential mode: 350 V L/N |
signal contacts composition | 1 SD (1 C/O) |
remote signalling | with |
short-circuit withstand | 50 kA |