Schneider Electric
Acti 9 iRCi current control relay iRCI - 8 A - 230 V 50/60Hz - 1 OC - A9E21181
Out of stock
SKU
A9E21181
More Information
| Attribute | Value |
|---|---|
| SKU | A9E21181 |
| ambient air temperature for storage | -40-80 °C |
| ambient air temperature for operation | -5-55 °C |
| product or component type | Miniature Circuit Breaker |
| net weight | 215 g |
| mounting mode | fixed |
| device short name | iRCI |
| range | Command Control |
| [Ie] rated operational current | 8 A at 250 V AC (cos Phi = 1) |
| product name | Acti 9 iRC |
| [Us] rated supply voltage | 230 V AC at 50/60 Hz |
| analogue input range | 1...10 A DC, 0.15...1.5 A DC, 1...10 A AC, 0.15...1.5 A AC |
| tripping threshold | 10...100 % |
| connections - terminals | tunnel type terminals6 cable(s) 1.5-1.5 mm² rigid |
| height | 88.1 mm |
| power dissipation in W | 2 W |
| mounting support | 35 mm symmetrical DIN rail |
| compatibility code | iRCI |
| width | 36 mm |
| depth | 67 mm |
| IP degree of protection | IP20 |
| 9 mm pitches | 4 |
| colour | white |
| device application | current control relay |
| local signalling | red LED for fault, green LED for power on, reports when the preset threshold is reached |
| market segment | small commercial, residential |
| signal contacts composition | 1 C/O |
| time delay range | 0.1...10 s |
| accuracy error | +/- 10 % |
| type of setting | selected by wiring: measurement range, switch: overcurrent, switch: undercurrent |
| power consumption in VA | 3 VA |
| hysteresis | 5-50 % |