Acti 9 iRCP phase control relay iRCP - 8 A - 400 V 50/60Hz - 1 OC - A9E21180
This Acti 9 iRCP is a Phase control relay.
The voltage measurement range is 0.15VAC to 10VAC.
It monitors phases and the presence of voltage on the 3 phases of a 3 phase circuit power supply.
It indicates also any phase loss or inversion.
It supplies 1 fail-safe change-over contact.
The parameter setting is done on the front panel by direct scale by using a screwdriver.
It could be used for example to control the power supply of a 3-phase motor.
The precision of the display is +/- 10% of the full scale.
The time delay on tripping is 0.3s.
The Uc supply voltage is 400VAC +/- 15%.
The operating frequency is 50Hz or 60Hz.
The output by changeover contact current is 8A under 250VAC with cos phi equal to 1.
On the front face green led indicates the voltage presence.
The red led indicates a fault.
The consumption is 3VA.
The dissipated power is 2W.
The width in 9mm pitches is 4.
The degree of protection is IP20.
The dimensions are (W) 36mm x (H) 88,1mm x (D) 65mm.
The operating temperature is -5°C to + 55°C.
The storage temperature is -40°C to + 80°C.
Attribute | Value |
---|---|
SKU | A9E21180 |
ambient air temperature for storage | -40-80 °C |
ambient air temperature for operation | -5-55 °C |
product or component type | Miniature Circuit Breaker |
net weight | 0.21 kg |
mounting mode | fixed |
device short name | iRCP |
range | Command Control |
[Ie] rated operational current | 8 A at 250 V AC (cos Phi = 1) |
product name | Acti 9 iRC |
[Us] rated supply voltage | 400 V AC 50/60 Hz |
tripping threshold | 5...25 % of Us phase asymmetry |
connections - terminals | tunnel type terminals (top or bottom) 6 cable(s) 1.5-1.5 mm² rigid |
height | 88.1 mm |
mounting support | 35 mm symmetrical DIN rail |
compatibility code | iRCP |
width | 36 mm |
depth | 67 mm |
IP degree of protection | IP20 |
9 mm pitches | 4 |
colour | white |
device application | phase control relay |
local signalling | red LED for fault, it reports phase loss or reversal, green LED for power on |
market segment | small commercial, residential |
signal contacts composition | 1 C/O |
time delay range | 0.3 s |
accuracy error | +/- 10 % |
type of setting | rotary knob: asymmetry, selected by wiring: measurement range |
power consumption in VA | 3 VA |
hysteresis | 5 % |