Acti 9 PRD135r modular surge arrester - 1 pole - 440V - with remote transfer - 16649
This Acti9 PRD135r product is a modular surge arrester protecting 1P electrical installations against direct lightning strikes.
The Imax maximum discharge current is 50kA .The In nominal discharge current is 35kA.
The Type 1 surge arrester is recommended for electrical installations in the service sector and industrial buildings protected by a lightning conductor.
It is used to conduct the direct lightning current, propagating from the earth conductor to the network conductors.
The surge arresters with "r" indication have remote transfer of the information "Cartridge to be replaced".
The Uc maximum continuous operating voltage in common mode (between neutral and earth) is 440VAC.
The Uc maximum continuous operating voltage in differential mode (between phase and neutral) is 440VAC.
The Up Voltage protection level in common mode (between phase and earth) is 2.5kV.
The Ue rated operational voltage is 400VAC to 690VAC +/- 10%.
The product colour is anthracite grey (RAL7016).The dimensions are (W) 36mm x (H) 99mm x (D) 71mm.
The weight is 401g.
The degree of protection is IP20 and IP40 in modular enclosure.
The operating temperature is -25°C to 60°C.
The storage temperature is -40°C to 85°C.
This product is compliant with EN 61643-11 and IEC 61643-11 standards.
Attribute | Value |
---|---|
SKU | 16649 |
product certifications | CE |
relative humidity | 5-95 % |
ambient air temperature for storage | -40-85 °C |
ambient air temperature for operation | -25-60 °C |
quality labels | NF |
range of product | PRD1 |
product or component type | Surge Arrester |
net weight | 401 g |
mounting mode | clip-on |
standards | IEC 61643-11:2011, EN 61643-11:2012 |
device short name | PRD1 35r |
range | Acti 9 |
surge arrester class type | type 1 |
maximum discharge current | differential mode: 50 kA L/N |
IK degree of protection | IK05 conforming to IEC 62262 |
product name | Acti 9 PRD1 |
surge arrester type | electrical distribution network |
signalling circuit voltage | 1 A/250 V AC, 1 A/30 V DC |
residual current | 0.005 mA |
connections - terminals | tunnel type terminal (top or bottom) 10-25 mm² flexible, tunnel type terminal (top or bottom) 16-35 mm² rigid |
height | 99 mm |
mounting support | DIN rail |
compatibility code | PRD1_35r |
width | 36 mm |
depth | 71 mm |
operating altitude | 2000 m |
IP degree of protection | IP40 on front face: conforming to IEC 60529, IP20 built-in: conforming to IEC 60529 |
9 mm pitches | 4 |
poles description | 1P |
colour | anthracite grey (RAL 7016) |
tightening torque | 4.5-4.5 N.m |
device application | distribution |
[Ue] rated operational voltage | 400/690 V AC TN, 400 V AC IT |
disconnector device type | associated circuit breaker NSX 160B 160 A - Icu 10 kA, associated circuit breaker NSX 160B 160 A - Icu 15 kA, associated circuit breaker NSX 160B 160 A - Icu 25 kA, associated circuit breaker NSX160F 160 A - Icu 36 kA, associated circuit breaker NSX160N 160 A - Icu 50 kA, associated fuse gG 400 A |
surge arrester technology | spark gap |
[Ut] temporary overvoltage | 580 V L/N 5 s withstand, 800 V N/PE 7200 s withstand, 1640 V L/N 0.2 s safe failure mode |
response time | <= 100 ns |
maximum [Up] voltage protection level | common mode <2.5 kV type 1 L/PE |
nominal discharge current | common mode: 35 kA (L/PE), differential mode: 35 kA (L/N) |
earthing system | TN-S, TN-C, IT |
[Uc] maximum continuous operating voltage | common mode: 440 V L/PE, differential mode: 440 V L/N |
market segment | small commercial |
signal contacts composition | 1 SD (1 C/O) |
remote signalling | with |
short-circuit withstand | 50 kA |
[If] follow current | 50 kA differential mode L/N |
[Iimp] impulse current | differential mode: 35 kA L/N, common mode: 35 kA L/PE 17.5 A.s |
impulse current | 35 kA |