Acti9 Smartlink SI D Acti9 PowerTag Link - Wireless to Modbus TCP/IP Concentrator - A9XMWD20
This Acti 9 PowerTag Link is a Wireless to Modbus TCP/IP Concentrator smart communication module.
It has to be associated with a PowerTag wireless-communication energy sensor to provide circuit monitoring and diagnosis down to load level.
The number of HW-interfaces industrial Ethernet is 1.
Number of HW-interfaces Wireless is 1.
The voltage power supply is 110VAC to 230VAC.
The operating frequency is 50Hz or 60Hz.
It is a screw connection.
The degree of protection is IP20 or IP40 for modular enclosure.
The pollution degree is 2.
It complies with RoHS directive.
The dimensions are (W) 54mm x (H) 85mm x (D) 67.5mm.
The operating temperature is -25°C to + 60°C.
The storage temperature is -40°C to + 85°C.
This product complies with IEC/EN 61131-2 standard.
Attribute | Value |
---|---|
SKU | A9XMWD20 |
relative humidity | 93-93 % at 40-40 °C |
ambient air temperature for storage | -40-85 °C |
overvoltage category | III |
pollution degree | 2 |
ambient air temperature for operation | -25-60 °C |
reset | factory reset on front face |
product or component type | Meter & Manajemen Energi |
net weight | 133 g |
tropicalisation | 2 |
device short name | PowerTag Link |
range | PowerTag |
range compatibility | PowerTag wireless energy sensor |
product name | Acti9 PowerTag Link |
[Us] rated supply voltage | 110...230 V AC +/- 15 % |
mounting position | horizontal/vertical on DIN rail |
immunity to microbreaks | 10 ms |
transmission support medium | radio frequency 2.4-2.4835 GHz PowerTag 20 |
connectivity to devices | wireless energy sensor |
location of connection | upstream |
connected auxiliaries | up to 20 wireless devices |
height | 85 mm |
compatibility code | Acti9 PowerTag Link |
width | 54 mm |
depth | 67.5 mm |
operating altitude | 0...2000 m |
IP degree of protection | IP20 conforming to IEC 60529, IP40 (modular enclosure) conforming to IEC 60529 |
9 mm pitches | 6 useful |
colour | white (RAL 9003) |
device application | basic energy metering E, improved load monitoring E, U, I, P, Pf, load alarming |
local signalling | product status: 1 LED (green, orange and red), Ethernet status (LAN ST): 1 LED (green, orange and red) |
communication service | Ethernet Modbus TCP/IP server, web server |
power consumption in VA | 5 VA |
maximum supply current | 2 A |
web services | web page |
commissioning interface | web page, ECOREACH |
application specific I/O | pulse totalising counter |
web server | embedded web page, BMS controller compatible |