Schneider Electric

Compact NSX <630 circuit breaker NSX100F - TMD - 50 A - 4 poles 3d - LV429643

In stock
SKU
LV429643
55%
Special Price Rp 1.650.348 Regular Price Rp 3.667.440
Details

This Compact NSX100F is a complete 4P 3d fixed circuit breaker designed to optimize space and breaking capacity.

It is an optimal choice for all standard and specific applications.

The breaking capacity (Icu) is 36kA rms at 415VAC 50/60Hz.

The operational voltage is 690VAC 50/60Hz.

This product embeds a 50A rating thermal-magnetic trip unit (TMD).

TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection.

This 4 poles version (140mm x 161mm x 86mm) comes with a variety of optional functions and accessories.

It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications.

Compact NSX100F is part of Schneider Electric EcoStruxure Power architecture.

More Information
More Information
Attribute Value
SKU LV429643
product certifications EAC, CCC, Marine
relative humidity 0-95 %
ambient air temperature for storage -50-85 °C
overvoltage category class II
pollution degree 3 conforming to IEC 60664-1
ambient air temperature for operation -25-70 °C
upside connection front
electrical shock protection class class II
range of product ComPact NSX100...250
product or component type MCCB
net weight 2.4 kg
mounting mode fixed
standards EN/IEC 60947
earth-leakage protection without
mechanical durability 50000 cycles
device short name NSX100F
breaking capacity 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2, 85 kA at 240 V AC 50/60 Hz conforming to UL 508, 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2, 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 10 kA at 600 V AC 50/60 Hz conforming to UL 508, 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 25 kA at 480 V AC 50/60 Hz conforming to UL 508, 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
trip unit technology thermal-magnetic
range ComPact NSX
IK degree of protection IK07 conforming to IEC 62262
[Ics] rated service breaking capacity 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2, 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2, 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2, 12.5 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
trip unit name TM-D
trip unit rating 50-50 A at 40 °C
breaking capacity code F 36 kA 415 V AC
downside connection front
[Uimp] rated impulse withstand voltage 8 kV
product name ComPact NSX
short-time delay adjustment type fixed
network frequency 50/60 Hz
height 161 mm
mounting support backplate
compatibility code NSX100
width 140 mm
depth 86 mm
operating altitude 0...2000 m without derating, 2000 m...5000 m with derating
IP degree of protection IP40 conforming to IEC 60529
[In] rated current 50 A at 40 °C
network type AC
poles description 4P
electrical durability 10000 cycles at 690 V In, 20000 cycles at 690 V In/2, 30000 cycles at 440 V In, 50000 cycles at 440 V In/2
device application distribution
control type toggle
[Ue] rated operational voltage 690 V AC 50/60 Hz
protection type L : for overload protection (thermal), I : for short-circuit protection (magnetic)
utilisation category category A
neutral protection setting no protection (3t)
connection pitch 35 mm
[Ui] rated insulation voltage 800 V AC 50/60 Hz
suitability for isolation yes conforming to EN/IEC 60947-2
protected poles description 3t
neutral position left
long time pick-up adjustment range 0.7...1 x In
long time pick-up adjustment type Ir adjustable
long time delay adjustment type fixed
number of slots 5 slot(s)
[Isd] short-time pick-up adjustment range 500 A
[tr] long-time delay adjustment range 120-400 s at 1.5 x In, 15-15 s at 6 x Ir
trip unit protection functions LI
short-time pick-up adjustment type Isd fixed