Schneider Electric

Compact NSX <630 circuit breaker NSX100N - Micrologic 2.2 - 100 A - 3 poles 3d - LV429795

Out of stock
SKU
LV429795
55%
Special Price Rp 3.929.067 Regular Price Rp 8.731.260
Details

This Compact NSX100N is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity.

It is an optimal choice for all standard and specific applications.

The breaking capacity (Icu) is 50kA rms at 415VAC 50/60Hz.

The operational voltage is 690VAC 50/60Hz.

This product embeds an electronic Micrologic 2.2 trip unit, with 100A rating.

Micrologic 2.2 trip unit provides adjustable long time and short time protections, and a fixed instantaneous protection.

This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories.

It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications.

Compact NSX100N is part of Schneider Electric EcoStruxure Power architecture.

More Information
More Information
Attribute Value
SKU LV429795
product certifications EAC, CCC, Marine
relative humidity 0-95 %
ambient air temperature for storage -50-85 °C
overvoltage category class II
pollution degree 3 conforming to IEC 60664-1
ambient air temperature for operation -25-70 °C
upside connection front
electrical shock protection class class II
range of product ComPact NSX100...250
product or component type MCCB
net weight 2.05 kg
mounting mode fixed
standards EN/IEC 60947
earth-leakage protection without
mechanical durability 50000 cycles
device short name NSX100N
breaking capacity 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 85 kA at 240 V AC 50/60 Hz conforming to UL 508, 20 kA at 600 V AC 50/60 Hz conforming to UL 508, 50 kA at 480 V AC 50/60 Hz conforming to UL 508, 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
trip unit technology electronic
range ComPact NSX
IK degree of protection IK07 conforming to IEC 62262
[Ics] rated service breaking capacity 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2, 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2, 90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
trip unit name Micrologic 2.2
trip unit rating 100-100 A at 40 °C
breaking capacity code N 50 kA 415 V AC
downside connection front
[Uimp] rated impulse withstand voltage 8 kV
product name ComPact NSX
short-time delay adjustment type fixed
thermal memory 20 minutes before and after tripping
network frequency 50/60 Hz
height 161 mm
mounting support backplate
compatibility code NSX100
width 105 mm
depth 86 mm
operating altitude 0...2000 m without derating, 2000 m...5000 m with derating
IP degree of protection IP40 conforming to IEC 60529
[In] rated current 100 A at 40 °C
network type AC
poles description 3P
electrical durability 10000 cycles at 690 V In, 20000 cycles at 690 V In/2, 30000 cycles at 440 V In, 50000 cycles at 440 V In/2
device application distribution
control type toggle
[Ue] rated operational voltage 690 V AC 50/60 Hz
local signalling flashing LED (green) for ready to operate, LED 105 % Ir (red) for overload, LED 90 % Ir (orange) for overload
protection type L : for overload protection (long time), So : for short time short-circuit protection with fixed delay, I : for instantaneous short-circuit protection
utilisation category category A
connection pitch 35 mm
[Ui] rated insulation voltage 800 V AC 50/60 Hz
suitability for isolation yes conforming to EN/IEC 60947-2
protected poles description 3t
long time pick-up adjustment range 40...100 A
long time pick-up adjustment type Ir adjustable 9 settings
instantaneous pick-up adjustment range 1500 A
long time delay adjustment type fixed
instantaneous pick-up adjustment type Ii fixed
number of slots 5 slot(s)
[Isd] short-time pick-up adjustment range 1.5...10 x Ir
[tr] long-time delay adjustment range 16-16 s at 6 x Ir, 11-11 s at 7.2 x Ir, 400-400 s at 1.5 x Ir
trip unit protection functions LSoI
short-time pick-up adjustment type Isd adjustable 9 settings