Schneider Electric
EasyLogic DM6200H VAF PF DPM RS48 CL1.0 - METSEDM6200HCL10RS
Out of stock
SKU
METSEDM6200HCL10RS
Details
This digital panel meter is part of the EasyLogic Digital Panel Meter Series.
The device is able to analyse the load and indicate current burden with a tricolor bar.
Providing Class 1 active energy accuracy per IEC 62053-21 standard, the meter will measure voltage, current and power factor.
Communication protocol is Modbus with RS485 port support.
The meter has a 4 digits, eight segments, 15 mm height and bright red LED display.
Mechanical dimensions are 96 mm in width, 96 mm in height and 80 mm in depth, for a product weight of 400 g.
More Information
Attribute | Value |
---|---|
SKU | METSEDM6200HCL10RS |
product certifications | CE conforming to IEC 61010-1, cULus conforming to UL 61010-1, cULus conforming to CSA C22.2 No 61010-1, C-Tick |
relative humidity | 5-95 % at 50-50 °C |
ambient air temperature for storage | -20-70 °C |
overvoltage category | III |
pollution degree | 2 |
ambient air temperature for operation | -10-60 °C |
display digits | 12 digit(s) - 14.2 mm in height |
product or component type | Meter & Manajemen Energi |
net weight | 300 g |
mounting mode | flush-mounted |
standards | IEC 61010-1:ed. 3, UL 61010-1:ed. 3 |
device short name | DM6200H |
range | Digital Meter |
wire stripping length | current circuit: 3.68 mm, voltage circuit: 7 mm, control circuit: 7 mm, communication: 7 mm |
product name | EasyLogic DM6X00H RS |
[Us] rated supply voltage | 48...277 V AC 45...65 Hz, 48...277 V DC |
electromagnetic compatibility | electrostatic discharge conforming to IEC 61000-4-2, electrical fast transient/burst immunity test conforming to IEC 61000-4-4, surge immunity test conforming to IEC 61000-4-5, conducted RF disturbances conforming to IEC 61000-4-6, magnetic field at power frequency conforming to IEC 61000-4-8, voltage dips and interruptions immunity test conforming to IEC 61000-4-11, radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3, emission tests conforming to FCC part 15 class A, emission tests conforming to FCC part 15 subpart C, emission tests conforming to FCC part 15 subpart E |
type of measurement | voltage, current, frequency, RPM |
analogue input type | current 0.005...10 A (impedance 0.3 MOhm)6 x |
measurement category | category III 480-480 V |
service life | 7 year(s) |
refresh time | 1 s |
network frequency | 50 Hz, 60 Hz |
connections - terminals | current circuit: screw clamp terminals (bottom) 2.08-3.31 mm² cable(s), voltage circuit: screw clamp terminals (top) 0.82-3.31 mm² cable(s), control circuit: screw clamp terminals (top) 0.82-3.31 mm² cable(s), communication: screw clamp terminals (bottom) 0.33-3.31 mm² cable(s) |
height | 96 mm |
mounting support | framework |
width | 96 mm |
depth | 13 mm outside:, 49 mm panel: |
operating altitude | <= 2000 m |
IP degree of protection | IP30 body: conforming to IEC 60529, IP51 front: conforming to IEC 60529 |
[In] rated current | 1 A, 5 A |
poles description | 1P + N, 3P, 3P + N, 2P, 2P + N |
tightening torque | current circuit: 0.9-1 N.m Philips No 2 screwdriver, voltage circuit: 0.9-1 N.m Philips No 2 screwdriver, control circuit: 0.9-1 N.m Philips No 2 screwdriver, communication: 0.5-0.6 N.m Philips no 1 screwdriver |
device application | remote monitoring |
local signalling | red LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh), green LED: activity |
material | polycarbonate |
flame retardance | V-0 conforming to UL 94 |
measurement voltage | 46-277 V AC 50...60 Hz between phase and neutral, 80-480 V AC 50...60 Hz between phases, 277-999000 V AC 50...60 Hz with external VT |
display type | 8 segments LED |
type of installation | indoor installation |
maximum power consumption in VA | 4 VA at 240 V between phase and neutral |
electrical insulation class | class II |
measurement current | 5-6000 mA |
frequency measurement range | 45-65 Hz |
communication port support | screw terminal block: RS485 |
sampling rate | 32 samples/cycle |
maximum power consumption in W | 2 W at 240 V |
communication port protocol | Modbus at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2-wire, insulation 2500 V |
number of inputs | 2 |
tamperproof of settings | protected by access code |
messages display capacity | 3 fields of 4 characters |
measurement accuracy | power factor +/- 0.01, frequency +/- 0.05 %, current +/- 1 %, voltage +/- 1 % |
display colour | red |
metering type | calculated neutral current, unbalance current, rotation speed, average current Iavg, average voltage Vavg, unbalance voltage, phase currents, frequency, voltage U21, U32, U13, V1, V2, V3 |
accuracy class | class 1 |
targeted country | all |
counter functions | ON hour counting, power interruption |
communication of data | instantaneous and demand values, revolution speed, all counters, reading of measurements |
installation category | III |
Technical Documents