EasyPact CVS circuit breaker CVS100BS, 25 kA at 415 VAC, 100 A rating thermal magnetic TM-D trip unit, 4P 3d - LV510958
EasyPact CVS100BS is a 4 poles 3d fixed circuit breaker with a high level of performance and cost-saving functionality.
It is an optimal choice for small and medium-sized buildings protection applications.
The breaking capacity (Icu) is 25kA rms at 415VAC 50/60Hz.
The operational voltage is 440VAC 50/60Hz.
EasyPact CVS100BS current-limiting technology greatly reduces damage to installation caused by short-circuit current.
This product embeds a 100A rating thermal-magnetic trip unit (TMD).
TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection.
This 4 poles version (100mm x 130mm x 60mm) comes with a variety of optional functions and accessories.
EasyPact CVS100BS is compliant with international standards (IEC 60947, CCC, EAC).
| Attribute | Value | 
|---|---|
| SKU | LV510958 | 
| product certifications | CCC, GOST, CCS | 
| ambient air temperature for storage | -50-85 °C | 
| pollution degree | 3 conforming to IEC 60664-1 | 
| ambient air temperature for operation | -25-70 °C | 
| upside connection | front | 
| electrical shock protection class | class II | 
| range of product | Easypact CVS100...160 | 
| product or component type | MCCB | 
| net weight | 1 kg | 
| mounting mode | fixed | 
| standards | IEC 60947-2 | 
| earth-leakage protection | without | 
| mechanical durability | 13000 cycles | 
| device short name | CVS100BS | 
| breaking capacity | 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 25 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 200/240 V AC 50/60 Hz conforming to IEC 60947-2, 25 kA Icu at 380/400 V AC 50/60 Hz conforming to IEC 60947-2 | 
| trip unit technology | thermal-magnetic | 
| range | EasyPact CVS | 
| [Ics] rated service breaking capacity | 25 kA at 200/240 V AC 50/60 Hz conforming to IEC 60947-2, 17 kA at 380/400 V AC 50/60 Hz conforming to IEC 60947-2 | 
| trip unit name | TM-D | 
| trip unit rating | 100-100 A at 40 °C | 
| breaking capacity code | BS | 
| downside connection | front | 
| [Uimp] rated impulse withstand voltage | 8 kV conforming to EN/IEC 60947-2 | 
| product name | EasyPact CVS | 
| network frequency | 50/60 Hz | 
| connections - terminals | screw connection | 
| height | 130 mm | 
| mounting support | backplate | 
| compatibility code | CVS100 | 
| width | 100 mm | 
| depth | 60 mm | 
| IP degree of protection | IP40 | 
| [In] rated current | 100 A at 40 °C | 
| network type | AC | 
| poles description | 4P | 
| electrical durability | 4000 cycles 415 V In conforming to IEC 60947-2 | 
| device application | distribution | 
| control type | toggle | 
| protection type | instantaneous short-circuit protection, overload protection (long time) | 
| utilisation category | category A | 
| neutral protection setting | no protection (3d) | 
| connection pitch | 35 mm | 
| suitability for isolation | yes | 
| protected poles description | 3d | 
| neutral position | left | 
| long time pick-up adjustment range | 0.7...1 x In | 
| long time pick-up adjustment type Ir | adjustable | 
| contact position indicator | yes | 
| thermal protection adjustment range | 70-100 A | 
| instantaneous pick-up adjustment range | 800 A | 
| long time delay adjustment type | fixed | 
| instantaneous pick-up adjustment type Ii | fixed | 