Schneider Electric

EasyPact CVS - CVS160N circuit breaker - 4P/3d - LV516467

Out of stock
SKU
LV516467
50%
Special Price Rp 2.575.200 Regular Price Rp 5.150.400
More Information
More Information
Attribute Value
SKU LV516467
product certifications IEC, GOST
ambient air temperature for storage -50-85 °C
ambient air temperature for operation -25-70 °C
upside connection front
electrical shock protection class class II
range of product Easypact CVS100...250
product or component type MCCB
mounting mode fixed
standards IEC 60947-2, EN 60947-2
earth-leakage protection without
mechanical durability 25000 cycles
device short name CVS160N
breaking capacity 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 40 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 80 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
trip unit technology thermal-magnetic
range EasyPact CVS
[Ics] rated service breaking capacity 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2, 80 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
trip unit name TM-D
trip unit rating 125-125 A at 40 °C
breaking capacity code N
downside connection front
[Uimp] rated impulse withstand voltage 8 kV conforming to EN/IEC 60947-2
product name EasyPact CVS
short-time delay adjustment type fixed
network frequency 50/60 Hz
connections - terminals screw connection
height 161 mm
mounting support backplate
compatibility code CVS160
width 140 mm
depth 86 mm
IP degree of protection IP40
[In] rated current 160 A at 40 °C
network type AC
poles description 4P
electrical durability 12000 cycles 415 V In conforming to IEC 60947-2
device application distribution
control type toggle
protection type short-circuit protection (magnetic), overload protection (thermal)
utilisation category category A
neutral protection setting no protection (3d)
connection pitch 35 mm
protected poles description 3d
neutral position left
long time pick-up adjustment range 0.7...1 x In
long time pick-up adjustment type Ir adjustable
contact position indicator yes
thermal protection adjustment range 0-125 A
instantaneous pick-up adjustment range 1250 A
long time delay adjustment type fixed
instantaneous pick-up adjustment type Ii fixed
PT. Telesindo Citra Sejahtera © 2025 All Rights Reserved.