EasyPact CVS - CVS400F ETS 2.3 circuit breaker - 400 A - 4P/4d - LV540506
EasyPact CVS400F is a 4 poles 4d fixed circuit breaker with a high level of performance and cost-saving functionality.
It is an optimal choice for small and medium-sized buildings protection applications.
The breaking capacity (Icu) is 36kA rms at 415VAC 50/60Hz.
The operational voltage is 440VAC 50/60Hz.
This product embeds an electronic ETS 2.3 trip unit, with 400A rating.
ETS 2.3 trip unit provides adjustable long time and short time protections, and a fixed instantaneous protection.
This 4 poles version (185mm x 255mm x 110mm) comes with a variety of optional functions and accessories.
EasyPact CVS400F is compliant with international standards (IEC 60947, CCC, EAC).
It can be installed in class II insulation switchboards as it is a class II front face device (IEC 60664-1).
Attribute | Value |
---|---|
SKU | LV540506 |
product certifications | IEC, GOST |
ambient air temperature for storage | -50-85 °C |
pollution degree | 3 conforming to IEC 60664-1 |
ambient air temperature for operation | -25-70 °C |
upside connection | front |
electrical shock protection class | class II |
range of product | Easypact CVS400...630 |
product or component type | MCCB |
net weight | 6.3 kg |
mounting mode | fixed |
standards | IEC 60947-2, EN 60947-2 |
earth-leakage protection | without |
mechanical durability | 15000 cycles |
device short name | CVS400F |
breaking capacity | 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
trip unit technology | electronic |
range | EasyPact CVS |
[Ics] rated service breaking capacity | 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 23 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
trip unit name | ETS 2.3 |
trip unit rating | 400-400 A at 40 °C |
breaking capacity code | F |
downside connection | front |
[Uimp] rated impulse withstand voltage | 8 kV conforming to EN/IEC 60947-2 |
product name | EasyPact CVS |
short-time delay adjustment type | fixed |
thermal memory | yes |
network frequency | 50/60 Hz |
connections - terminals | screw connection |
height | 255 mm |
mounting support | backplate |
compatibility code | CVS400 |
width | 185 mm |
depth | 110 mm |
IP degree of protection | IP40 |
[In] rated current | 400 A at 40 °C |
network type | AC |
poles description | 4P |
electrical durability | 6000 cycles 415 V In conforming to IEC 60947-2 |
device application | distribution |
control type | toggle |
protection type | short time short-circuit protection, instantaneous short-circuit protection, overload protection (long time) |
utilisation category | category A |
neutral protection setting | 1 x Ir (4d), 0.5 x Ir (3d + N/2) |
connection pitch | 45 mm |
protected poles description | 3d, 3d + N/2, 4d |
neutral position | left |
long time pick-up adjustment range | 160…400 A |
long time pick-up adjustment type Ir | adjustable 9 settings |
contact position indicator | yes |
instantaneous pick-up adjustment range | 11 x In |
long time delay adjustment type | fixed |
instantaneous pick-up adjustment type Ii | fixed |
[Isd] short-time pick-up adjustment range | 1.5...10 x Ir |
[tr] long-time delay adjustment range | 5.5-5.5 s at 7.2 x Ir, 8-8 s at 6 x Ir, 200-200 s at 1.5 x Ir |
trip unit protection functions | LSoI |
short-time pick-up adjustment type Isd | adjustable 9 settings |