EasyPact CVS - CVS630F ETS 2.3 circuit breaker - 630 A - 3P/3d - LV563505
This device is a rated current 630A circuit breaker from EasyPact CVS630F.
The rated breaking capacity(Ics) is 36kA at 415VAC,and complete range with Ics=100%Icu.
The version of breaker is 3poles frame with detection on 3poles, also accompanied ETS 2.3 trip unit for electronic protection.
It is conformed to standard IEC60947-2 for circuit breakers part.
This device is certified for operation in pollution degree III environment as defined IEC60947-1& IEC60664-1, and respected for RoHs requirement as european environment directive EC/2002/95.
It can be mounted by blackplate or Din rail,also through the door of class II switchboard without downgrading switchboard insulation.
The front of toggle offers IP40 protection, but when it is equiped extended rotary handle inside the switchboard, additional IP54 protection degree for extended rotary handle.
This series have slots for electrical auxiliaries(MN/MX/OF/SD),depending on the type of trip unit if rotary handle installed.
The fixed dimension is 140mm width.255mm height,110mm depth,
Attribute | Value |
---|---|
SKU | LV563505 |
product certifications | IEC, GOST |
ambient air temperature for storage | -50-85 °C |
pollution degree | 3 conforming to IEC 60664-1 |
ambient air temperature for operation | -25-70 °C |
upside connection | front |
electrical shock protection class | class II |
range of product | Easypact CVS400...630 |
product or component type | MCCB |
net weight | 5.2 kg |
mounting mode | fixed |
standards | IEC 60947-2, EN 60947-2 |
earth-leakage protection | without |
mechanical durability | 15000 cycles |
device short name | CVS630F |
breaking capacity | 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
trip unit technology | electronic |
range | EasyPact CVS |
[Ics] rated service breaking capacity | 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 23 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
trip unit name | ETS 2.3 |
trip unit rating | 630-630 A at 40 °C |
breaking capacity code | F |
downside connection | front |
[Uimp] rated impulse withstand voltage | 8 kV conforming to EN/IEC 60947-2 |
product name | EasyPact CVS |
short-time delay adjustment type | fixed |
thermal memory | yes |
network frequency | 50/60 Hz |
connections - terminals | screw connection |
height | 255 mm |
mounting support | backplate |
compatibility code | CVS630 |
width | 140 mm |
depth | 110 mm |
IP degree of protection | IP40 |
[In] rated current | 630 A at 40 °C |
network type | AC |
poles description | 3P |
electrical durability | 4000 cycles 415 V In conforming to IEC 60947-2 |
device application | distribution |
control type | toggle |
protection type | short time short-circuit protection, instantaneous short-circuit protection, overload protection (long time) |
utilisation category | category A |
connection pitch | 45 mm |
protected poles description | 3d |
long time pick-up adjustment range | 250...630 A |
long time pick-up adjustment type Ir | adjustable 9 settings |
contact position indicator | yes |
instantaneous pick-up adjustment range | 11 x In |
long time delay adjustment type | fixed |
instantaneous pick-up adjustment type Ii | fixed |
[Isd] short-time pick-up adjustment range | 1.5...10 x Ir |
[tr] long-time delay adjustment range | 5.5-5.5 s at 7.2 x Ir, 8-8 s at 6 x Ir, 200-200 s at 1.5 x Ir |
trip unit protection functions | LSoI |
short-time pick-up adjustment type Isd | adjustable 9 settings |