Schneider Electric

EasyPact EZC circuit breaker EZC100H - TMD - 20 A - 1 pole 1d - EZC100H1020

Out of stock
SKU
EZC100H1020
50%
Special Price Rp 440.115 Regular Price Rp 880.230
Details

EasyPact EZC100H is a 1 pole fixed circuit breaker designed for the protection of low voltage electrical installations.

It is used for standard applications in industries and buildings, offering good performance at competitive price The breaking capacity (Icu) is 25kA rms at 240VAC 50/60Hz.

The operational voltage is 415VAC 50/60Hz or 125VDC.

The rating of the thermal-magnetic trip unit is 20A.

The trip unit provides fixed overload and instantaneous protections.

The dimensions for this 1 pole version are 25mm (W) x 130mm (H) x 60mm (D).

Easypact EZC100H is compliant with international standards (IEC 60947, UL 508) and marine certifications.

More Information
More Information
Attribute Value
SKU EZC100H1020
range EasyPact EZC
product or component type MCCB
[In] rated current 100 A at 40 °C
trip unit technology thermal-magnetic
breaking capacity 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2, 10 kA Icu at 125 V DC 1P conforming to IEC 60947-2, 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2, 5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2, 5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
ambient air temperature for operation -25-70 °C
ambient air temperature for storage -35-85 °C
control type toggle
mounting mode fixed
mechanical durability 8500 cycles
IK degree of protection IK07 conforming to IEC 62262
network frequency 50/60 Hz
trip unit rating 20-20 A at 50 °C
earth-leakage protection without
breaking capacity code H
downside connection front
upside connection front
[Ue] rated operational voltage 125 V DC conforming to IEC 60947-2, 415 V AC 50/60 Hz conforming to IEC 60947-2
product name EasyPact EZC
poles description 1P
protection type short-circuit protection, overload protection
standards JIS C8201-2-2, EN/IEC 60947-2, EN/IEC 60947-1, GB/T 14048.2
device application distribution
[Ics] rated service breaking capacity 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2, 5 kA at 125 V DC conforming to IEC 60947-2, 25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2, 2.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2, 2.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
electrical durability category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
connection pitch 25 mm
device short name Easypact EZC100H
network type AC, DC
pollution degree 3 conforming to IEC 60664-1, 3 conforming to IEC 947-1
protected poles description 1t
trip unit name TM-D
local signalling positive contact indication
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
height 130 mm
depth 60 mm
width 25 mm
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
compatibility code EZC100
IP degree of protection IP20 conforming to IEC 60529
utilisation category category A
suitability for isolation yes conforming to IEC 60947-2