Schneider Electric
EasyPact EZC circuit breaker EZC250F - TMD - 225 A - 3 poles 3d - EZC250F3225
In stock
SKU
EZC250F3225
Details
EasyPact EZC250F is a 3 poles fixed circuit breaker designed for the protection of low voltage electrical installations.
It is used for standard applications in industries and buildings, offering good performance at competitive price The breaking capacity (Icu) is 18kA rms at 415VAC 50/60Hz.
The operational voltage is 550VAC 50/60Hz or 250VDC.
The rating of the thermal-magnetic trip unit is 225A.
The trip unit provides fixed overload and instantaneous protections.
This 3 poles version (105mm x 165mm x 60mm) comes with a variety of optional functions and accessories.
Easypact EZC250F is compliant with international standards (IEC 60947, UL 508) and marine certifications.
More Information
Attribute | Value |
---|---|
SKU | EZC250F3225 |
range | EasyPact EZC |
product or component type | MCCB |
[In] rated current | 250 A at 40 °C |
trip unit technology | thermal-magnetic |
breaking capacity | 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2, 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2, 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2, 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2, 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2, 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2, 18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 |
ambient air temperature for operation | -25-70 °C |
ambient air temperature for storage | -35-85 °C |
control type | toggle |
mounting mode | fixed |
mechanical durability | 10000 cycles |
IK degree of protection | IK07 conforming to IEC 62262 |
network frequency | 50/60 Hz |
trip unit rating | 225-225 A at 50 °C |
earth-leakage protection | without |
breaking capacity code | F |
downside connection | front |
upside connection | front |
[Ue] rated operational voltage | 550 V AC 50/60 Hz conforming to IEC 60947-2, 250 V DC conforming to IEC 60947-2 |
product name | EasyPact EZC |
poles description | 3P |
protection type | short-circuit protection, overload protection |
standards | JIS C8201-2-2, EN/IEC 60947-2, EN/IEC 60947-1, GB/T 14048.2 |
device application | distribution |
[Ics] rated service breaking capacity | 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2, 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2, 2.5 kA at 125 V DC conforming to IEC 60947-2, 2.5 kA at 250 V DC conforming to IEC 60947-2, 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2, 9 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2, 9 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 7.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
electrical durability | category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2 |
connection pitch | 35 mm |
device short name | Easypact EZC250F |
network type | AC, DC |
pollution degree | 3 conforming to IEC 60664-1, 3 conforming to IEC 947-1 |
protected poles description | 3t |
trip unit name | TM-D |
local signalling | positive contact indication |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
height | 165 mm |
depth | 60 mm |
width | 105 mm |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
compatibility code | EZC250 |
IP degree of protection | IP20 conforming to IEC 60529 |
utilisation category | category A |
suitability for isolation | yes conforming to IEC 60947-2 |
Technical Documents