Schneider Electric

EasyPact TVS contactor 3P(3 NO) - AC-3 - <= 440 V 18A - 220 V AC coil - LC1E1801M7

Out of stock
SKU
LC1E1801M7
38%
Special Price Rp 280.097 Regular Price Rp 451.770
Details

EasyPact TVS contactor 3 poles for motor applications up to 18A 9kW@440V.

It provides a 220V 50/60Hz AC coil, 1NC built-in auxiliary contacts, power and control connections by screw clamp terminals.

45mm width for standard operating rates up to 1800 cycles per hour.

It procures standard reliability and durability with 1.2 Mcycles electrical durability AC-3 and 10 Mcycles mechanical durability.

It can cover -5°C to 55°C working temperature and mounted by DIN-rail, No derating up to 3000m altitude.

Multi-standards certified (IEC, CCC, EAC) and Green Premium compliant (RoHs/Reach).

More Information
More Information
Attribute Value
SKU LC1E1801M7
product certifications EAC
ambient air temperature for storage -60-80 °C
overvoltage category III
pollution degree 3
ambient air temperature for operation -5-55 °C
non-overlap time 1.5 ms on energisation guaranteed between NC and NO contact, 1.5 ms on de-energisation guaranteed between NC and NO contact
[Icw] rated short-time withstand current 145 A 40 °C - 10 s for power circuit, 84 A 40 °C - 60 s for power circuit, 40 A 40 °C - 600 s for power circuit
product or component type Kontaktor
net weight 0.3 kg
standards IEC 60947-4-1, IEC 60947-5-1, IEC 60947-1
mechanical durability 10000000 cycles
device short name LC1E
range EasyPact TVS
average impedance 2.5 mOhm - Ith 32 A 50 Hz for power circuit
[Ie] rated operational current 18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit, 32 A (at <60 °C) at <= 415 V AC AC-1 for power circuit
[Uc] control circuit voltage 220 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 6 kV coil not connected to the power circuit conforming to IEC 60947
product name EasyPact TVS
minimum switching current 5 mA for control circuit
mechanical robustness vibrations contactor open: 1.5 Gn, 5...300 Hz, vibrations contactor closed: 3 Gn, 5...300 Hz, shocks contactor open: 7 Gn for 11 ms, shocks contactor closed: 10 Gn for 11 ms
power dissipation per pole 0.81 W AC-3, 2.6 W AC-1
control circuit type AC at 50/60 Hz
contactor application motor control, resistive load
insulation resistance > 10 MOhm for control circuit
rated breaking capacity 144 A at 440 V for power circuit conforming to IEC 60947
Irms rated making capacity 180 A at 440 V AC for power circuit conforming to IEC 60947-4-1
pole contact composition 3 NO
operating time 12...22 ms on closing, 4...19 ms on opening
hold-in power consumption in VA 8.5-8.5 VA 50 Hz cos phi 0.3 (at 20 °C), 8.5-8.5 VA 60 Hz cos phi 0.3 (at 20 °C)
inrush power in VA 95-95 VA 50 Hz cos phi 0.75 (at 20 °C), 95-95 VA 60 Hz cos phi 0.75 (at 20 °C)
permissible ambient air temperature around the device -20-70 °C at Uc
connections - terminals power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end, power circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end, power circuit: screw clamp terminals 1 1.5-6 mm² - cable stiffness: solid without cable end, power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: solid without cable end
height 74 mm
mounting support DIN rail, plate
width 45 mm
depth 80 mm
operating altitude 3000 m without derating
IP degree of protection IP2x conforming to IEC 60529
poles description 3P
colour grey (RAL 7011)
tightening torque power circuit: 1.2 N.m, control circuit: 1.2 N.m, power circuit: 1.4 N.m, control circuit: 1.4 N.m
electrical durability 300000 cycles AC-1, 1200000 cycles AC-3
[Ue] rated operational voltage power circuit: <= 690 V AC 50/60 Hz
utilisation category AC-3, AC-1
[Ui] rated insulation voltage 690 V conforming to IEC 60947-4-1
auxiliary contact composition 1 NC
control circuit voltage limits operational: 0.85...1.1 Uc at 50/60 Hz (at <55 °C), drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55 °C)
associated fuse rating 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1, 35 A gG at <= 690 V coordination type 1 for power circuit
minimum switching voltage 17 V for control circuit
maximum operating rate 1800 cyc/h 60 °C
protective treatment TH (pollution degree 3) conforming to IEC 60068
fire resistance 850 °C conforming to IEC 60695-2-1
motor power kW 4 kW at 220...230 V AC 50/60 Hz, 7.5 kW at 380...400 V, 9 kW at 415 V, 9 kW at 440 V, 10 kW at 500 V, 10 kW at 660...690 V
heat dissipation 2-3 W for control circuit