Schneider Electric
EasyPact TVS contactor 3P(3 NO) - AC-3 - <= 440 V 18A - 220 V AC coil - LC1E1810M7
Out of stock
SKU
LC1E1810M7
Details
EasyPact TVS contactor 3 poles for motor applications up to 18A 9kW@440V.
It provides a 220V 50/60Hz AC coil, 1NO built-in auxiliary contacts, power and control connections by screw clamp terminals.
45mm width for standard operating rates up to 1800 cycles per hour.
It procures standard reliability and durability with 1.2 Mcycles electrical durability AC-3 and 10 Mcycles mechanical durability.
It can cover -5°C to 55°C working temperature and mounted by DIN-rail, No derating up to 3000m altitude.
Multi-standards certified (IEC, CCC, EAC) and Green Premium compliant (RoHs/Reach).
More Information
Attribute | Value |
---|---|
SKU | LC1E1810M7 |
product certifications | EAC |
ambient air temperature for storage | -60-80 °C |
overvoltage category | III |
pollution degree | 3 |
ambient air temperature for operation | -5-55 °C |
non-overlap time | 1.5 ms on energisation guaranteed between NC and NO contact, 1.5 ms on de-energisation guaranteed between NC and NO contact |
[Icw] rated short-time withstand current | 145 A 40 °C - 10 s for power circuit, 84 A 40 °C - 60 s for power circuit, 40 A 40 °C - 600 s for power circuit |
product or component type | Kontaktor |
net weight | 0.3 kg |
standards | IEC 60947-4-1, IEC 60947-5-1, IEC 60947-1 |
mechanical durability | 10000000 cycles |
device short name | LC1E |
range | EasyPact TVS |
average impedance | 2.5 mOhm - Ith 32 A 50 Hz for power circuit |
[Ie] rated operational current | 18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit, 32 A (at <60 °C) at <= 415 V AC AC-1 for power circuit |
[Uc] control circuit voltage | 220 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage | 6 kV coil not connected to the power circuit conforming to IEC 60947 |
product name | EasyPact TVS |
minimum switching current | 5 mA for control circuit |
mechanical robustness | vibrations contactor open: 1.5 Gn, 5...300 Hz, vibrations contactor closed: 3 Gn, 5...300 Hz, shocks contactor open: 7 Gn for 11 ms, shocks contactor closed: 10 Gn for 11 ms |
power dissipation per pole | 0.81 W AC-3, 2.6 W AC-1 |
control circuit type | AC at 50/60 Hz |
contactor application | motor control, resistive load |
insulation resistance | > 10 MOhm for control circuit |
rated breaking capacity | 144 A at 440 V for power circuit conforming to IEC 60947 |
Irms rated making capacity | 180 A at 440 V AC for power circuit conforming to IEC 60947-4-1 |
pole contact composition | 3 NO |
operating time | 12...22 ms on closing, 4...19 ms on opening |
hold-in power consumption in VA | 8.5-8.5 VA 50 Hz cos phi 0.3 (at 20 °C), 8.5-8.5 VA 60 Hz cos phi 0.3 (at 20 °C) |
inrush power in VA | 95-95 VA 50 Hz cos phi 0.75 (at 20 °C), 95-95 VA 60 Hz cos phi 0.75 (at 20 °C) |
permissible ambient air temperature around the device | -20-70 °C at Uc |
connections - terminals | power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end, power circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end, power circuit: screw clamp terminals 1 1.5-6 mm² - cable stiffness: solid without cable end, power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: solid without cable end |
height | 74 mm |
mounting support | DIN rail, plate |
width | 45 mm |
depth | 80 mm |
operating altitude | 3000 m without derating |
IP degree of protection | IP2x conforming to IEC 60529 |
poles description | 3P |
colour | grey (RAL 7011) |
tightening torque | power circuit: 1.2 N.m, control circuit: 1.2 N.m, power circuit: 1.4 N.m, control circuit: 1.4 N.m |
electrical durability | 300000 cycles AC-1, 1200000 cycles AC-3 |
[Ue] rated operational voltage | power circuit: <= 690 V AC 50/60 Hz |
utilisation category | AC-3, AC-1 |
[Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1 |
auxiliary contact composition | 1 NO |
control circuit voltage limits | operational: 0.85...1.1 Uc at 50/60 Hz (at <55 °C), drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55 °C) |
associated fuse rating | 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1, 35 A gG at <= 690 V coordination type 1 for power circuit |
minimum switching voltage | 17 V for control circuit |
maximum operating rate | 1800 cyc/h 60 °C |
protective treatment | TH (pollution degree 3) conforming to IEC 60068 |
fire resistance | 850 °C conforming to IEC 60695-2-1 |
motor power kW | 4 kW at 220...230 V AC 50/60 Hz, 7.5 kW at 380...400 V, 9 kW at 415 V, 9 kW at 440 V, 10 kW at 500 V, 10 kW at 660...690 V |
heat dissipation | 2-3 W for control circuit |
Technical Documents