Schneider Electric

EasyPact TVS contactor 3P(3 NO) - AC-3 - <= 440 V 32A - 220 V AC coil - LC1E3210M7

Out of stock
SKU
LC1E3210M7
38%
Special Price Rp 505.827 Regular Price Rp 815.850
Details

EasyPact TVS contactor 3 poles for motor applications up to 32A 15kW@440V.

It provides a 220V 50/60Hz AC coil, 1NO built-in auxiliary contacts, power and control connections by screw clamp terminals.

56mm width for standard operating rates up to 1800 cycles per hour.

It procures standard reliability and durability with 1 Mcycles electrical durability AC-3 and 8 Mcycles mechanical durability.

It can cover -5°C to 55°C working temperature and mounted by DIN-rail, No derating up to 3000m altitude.

Multi-standards certified (IEC, CCC, EAC) and Green Premium compliant (RoHs/Reach).

More Information
More Information
Attribute Value
SKU LC1E3210M7
product certifications EAC
ambient air temperature for storage -60-80 °C
overvoltage category III
pollution degree 3
ambient air temperature for operation -5-55 °C
non-overlap time 1.5 ms on energisation guaranteed between NC and NO contact, 1.5 ms on de-energisation guaranteed between NC and NO contact
[Icw] rated short-time withstand current 260 A 40 °C - 10 s for power circuit, 138 A 40 °C - 60 s for power circuit, 60 A 40 °C - 600 s for power circuit
product or component type Kontaktor
net weight 0.45 kg
standards IEC 60947-4-1, IEC 60947-5-1, IEC 60947-1
mechanical durability 8000000 cycles
device short name LC1E
range EasyPact TVS
average impedance 2.5 mOhm - Ith 50 A 50 Hz for power circuit
[Ie] rated operational current 50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit, 32 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
[Uc] control circuit voltage 220 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 6 kV coil not connected to the power circuit conforming to IEC 60947
product name EasyPact TVS
minimum switching current 5 mA for control circuit
mechanical robustness vibrations contactor open: 1.5 Gn, 5...300 Hz, vibrations contactor closed: 3 Gn, 5...300 Hz, shocks contactor closed: 10 Gn for 11 ms, shocks contactor open: 6 Gn for 11 ms
power dissipation per pole 5 W AC-1, 2 W AC-3
control circuit type AC at 50/60 Hz
contactor application motor control, resistive load
insulation resistance > 10 MOhm for control circuit
rated breaking capacity 256 A at 440 V for power circuit conforming to IEC 60947
Irms rated making capacity 320 A at 440 V AC for power circuit conforming to IEC 60947-4-1
pole contact composition 3 NO
operating time 12...22 ms on closing, 4...19 ms on opening
hold-in power consumption in VA 8.5-8.5 VA 50 Hz cos phi 0.3 (at 20 °C), 8.5-8.5 VA 60 Hz cos phi 0.3 (at 20 °C)
inrush power in VA 95-95 VA 50 Hz cos phi 0.75 (at 20 °C), 95-95 VA 60 Hz cos phi 0.75 (at 20 °C)
permissible ambient air temperature around the device -20-70 °C at Uc
connections - terminals control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end, power circuit: screw clamp terminals 1 1.5-6 mm² - cable stiffness: solid without cable end, power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: solid without cable end, power circuit: screw clamp terminals 1 1-6 mm² - cable stiffness: flexible with cable end, power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible with cable end
height 84 mm
mounting support DIN rail, plate
width 56 mm
depth 86 mm
operating altitude 3000 m without derating
IP degree of protection IP2x conforming to IEC 60529
poles description 3P
colour grey (RAL 7011)
tightening torque control circuit: 1.2 N.m, control circuit: 1.4 N.m, power circuit: 2.1 N.m, power circuit: 2.3 N.m
electrical durability 350000 cycles AC-1, 1000000 cycles AC-3
[Ue] rated operational voltage power circuit: <= 690 V AC 50/60 Hz
utilisation category AC-3, AC-1
[Ui] rated insulation voltage 690 V conforming to IEC 60947-4-1
auxiliary contact composition 1 NO
control circuit voltage limits operational: 0.85...1.1 Uc at 50/60 Hz (at <55 °C), drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55 °C)
associated fuse rating 63 A gG at <= 690 V coordination type 1 for power circuit, 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1
minimum switching voltage 17 V for control circuit
maximum operating rate 1800 cyc/h 60 °C
protective treatment TH (pollution degree 3) conforming to IEC 60068
fire resistance 850 °C conforming to IEC 60695-2-1
motor power kW 7.5 kW at 220...230 V AC 50/60 Hz, 15 kW at 380...400 V, 15 kW at 415 V, 15 kW at 440 V, 18.5 kW at 500 V, 18.5 kW at 660...690 V
heat dissipation 2-3 W for control circuit
PT. Telesindo Citra Sejahtera © 2025 All Rights Reserved.