Schneider Electric
EasyPact TVS contactor 3P(3 NO) - AC-3 - <= 440 V 400A - 220 V AC coil - LC1E400M7
Out of stock
SKU
LC1E400M7
Details
EasyPact TVS contactor 3 poles for motor applications up to 400A 250kW@440V.
It provides a 220V 50/60Hz AC coil, without built-in auxiliary contacts, power and control connections by screw clamp terminals.
213mm width for standard operating rates up to 2400 cycles per hour.
It procures standard reliability and durability with 0.6 Mcycles electrical durability AC-3 and 4 Mcycles mechanical durability.
It can cover -5°C to 55°C working temperature and mounted by DIN-rail, No derating up to 3000m altitude.
Multi-standards certified (IEC, CCC, EAC) and Green Premium compliant (RoHs/Reach).
More Information
Attribute | Value |
---|---|
SKU | LC1E400M7 |
product certifications | EAC |
ambient air temperature for storage | -60-80 °C |
overvoltage category | III |
pollution degree | 3 |
ambient air temperature for operation | -5-55 °C |
non-overlap time | 1.5 ms on energisation guaranteed between NC and NO contact, 1.5 ms on de-energisation guaranteed between NC and NO contact |
[Icw] rated short-time withstand current | 3600 A 40 °C - 10 s for power circuit |
product or component type | Kontaktor |
net weight | 9.1 kg |
standards | IEC 60947-4-1, IEC 60947-5-1, IEC 60947-1 |
mechanical durability | 4000000 cycles |
device short name | LC1E |
range | EasyPact TVS |
average impedance | 0.26 mOhm - Ith 500 A 50 Hz for power circuit |
[Ie] rated operational current | 400 A (at <55 °C) at <= 440 V AC AC-3 for power circuit, 500 A (at <40 °C) at <= 440 V AC AC-1 for power circuit |
[Uc] control circuit voltage | 220 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage | 8 kV coil not connected to the power circuit conforming to IEC 60947 |
product name | EasyPact TVS |
minimum switching current | 5 mA for control circuit |
mechanical robustness | shocks contactor closed: 15 Gn for 11 ms, vibrations contactor open: 1.5 Gn, 5...300 Hz, shocks contactor open: 6 Gn for 11 ms, vibrations contactor closed: 5 Gn, 5...300 Hz |
power dissipation per pole | 42 W AC-3, 65 W AC-1 |
[Ith] conventional free air thermal current | 500 A (at 40 °C) for power circuit |
control circuit type | AC at 50/60 Hz |
contactor application | motor control, resistive load |
insulation resistance | > 10 MOhm for control circuit |
rated breaking capacity | 3200 A at 440 V for power circuit conforming to IEC 60947 |
Irms rated making capacity | 4000 A at 440 V AC for power circuit conforming to IEC 60947-4-1 |
pole contact composition | 3 NO |
operating time | 100...170 ms on opening, 40...75 ms on closing |
hold-in power consumption in VA | 15-15 VA 50 Hz cos phi 0.9 (at 20 °C), 15-15 VA 60 Hz cos phi 0.9 (at 20 °C) |
inrush power in VA | 1075-1075 VA 50 Hz cos phi 0.9 (at 20 °C), 1075-1075 VA 60 Hz cos phi 0.9 (at 20 °C) |
permissible ambient air temperature around the device | -20-70 °C at Uc |
connections - terminals | control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end, power circuit: cable with lug 2 - external diameter: 150 mm, power circuit: bars 2 - busbar cross section: 30 x 5 mm |
height | 375 mm |
mounting support | plate |
width | 213 mm |
depth | 219 mm |
operating altitude | 3000 m without derating |
IP degree of protection | IP2x conforming to IEC 60529 |
poles description | 3P |
tightening torque | control circuit: 1.2 N.m, control circuit: 1.4 N.m, power circuit: 35 N.m, power circuit: 37 N.m |
electrical durability | 250000 cycles AC-1, 600000 cycles AC-3 |
[Ue] rated operational voltage | power circuit: <= 690 V AC 50/60 Hz |
utilisation category | AC-3, AC-1 |
[Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1 |
control circuit voltage limits | operational: 0.85...1.1 Uc at 50/60 Hz (at <55 °C), drop-out: 0.35...0.5 Uc at 50/60 Hz (at <55 °C) |
associated fuse rating | 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1, 630 A gG at <= 690 V coordination type 1 for power circuit |
minimum switching voltage | 17 V for control circuit |
maximum operating rate | 2400 cyc/h 55 °C |
protective treatment | TH (pollution degree 3) conforming to IEC 60068 |
fire resistance | 850 °C conforming to IEC 60695-2-1 |
motor power kW | 110 kW at 220...230 V AC 50/60 Hz, 200 kW at 380...400 V, 220 kW at 415 V, 250 kW at 440 V, 257 kW at 500 V, 280 kW at 660...690 V |
heat dissipation | 14-14 W for control circuit |
Technical Documents