Schneider Electric

EasyPact TVS contactor 3P(3 NO) - AC-3 - <= 440 V 500A - 220 V AC coil - LC1E500M7

Out of stock
SKU
LC1E500M7
38%
Special Price Rp 22.391.275 Regular Price Rp 36.114.960
Details

EasyPact TVS contactor 3 poles for motor applications up to 500A 295kW@440V.

It provides a 220V 50/60Hz AC coil, without built-in auxiliary contacts, power and control connections by screw clamp terminals.

233mm width for standard operating rates up to 2400 cycles per hour.

It procures standard reliability and durability with 0.6 Mcycles electrical durability AC-3 and 4 Mcycles mechanical durability.

It can cover -5°C to 55°C working temperature and mounted by DIN-rail, No derating up to 3000m altitude.

Multi-standards certified (IEC, CCC, EAC) and Green Premium compliant (RoHs/Reach).

More Information
More Information
Attribute Value
SKU LC1E500M7
product certifications EAC
ambient air temperature for storage -60-80 °C
overvoltage category III
pollution degree 3
ambient air temperature for operation -5-55 °C
non-overlap time 1.5 ms on energisation guaranteed between NC and NO contact, 1.5 ms on de-energisation guaranteed between NC and NO contact
[Icw] rated short-time withstand current 4200 A 40 °C - 10 s for power circuit
product or component type Kontaktor
net weight 11.35 kg
standards IEC 60947-4-1, IEC 60947-5-1, IEC 60947-1
mechanical durability 4000000 cycles
device short name LC1E
range EasyPact TVS
average impedance 0.18 mOhm - Ith 700 A 50 Hz for power circuit
[Ie] rated operational current 500 A (at <55 °C) at <= 440 V AC AC-3 for power circuit, 700 A (at <55 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage 220 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV coil not connected to the power circuit conforming to IEC 60947
product name EasyPact TVS
minimum switching current 5 mA for control circuit
mechanical robustness vibrations contactor open: 2 Gn, 5...300 Hz, vibrations contactor closed: 4 Gn, 5...300 Hz, shocks contactor closed: 15 Gn for 11 ms, shocks contactor open: 9 Gn for 11 ms
power dissipation per pole 45 W AC-3, 88 W AC-1
[Ith] conventional free air thermal current 700 A (at 40 °C) for power circuit
control circuit type AC at 50/60 Hz
contactor application motor control, resistive load
insulation resistance > 10 MOhm for control circuit
rated breaking capacity 4000 A at 440 V for power circuit conforming to IEC 60947
Irms rated making capacity 5000 A at 440 V AC for power circuit conforming to IEC 60947-4-1
pole contact composition 3 NO
operating time 100...170 ms on opening, 40...75 ms on closing
hold-in power consumption in VA 18-18 VA 50 Hz cos phi 0.9 (at 20 °C), 18-18 VA 60 Hz cos phi 0.9 (at 20 °C)
inrush power in VA 1100-1100 VA 50 Hz cos phi 0.9 (at 20 °C), 1100-1100 VA 60 Hz cos phi 0.9 (at 20 °C)
permissible ambient air temperature around the device -20-70 °C at Uc
connections - terminals control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end, power circuit: cable with lug 2 - external diameter: 240 mm, power circuit: bars 2 - busbar cross section: 40 x 5 mm
height 400 mm
mounting support plate
width 233 mm
depth 232 mm
operating altitude 3000 m without derating
IP degree of protection IP2x conforming to IEC 60529
poles description 3P
tightening torque control circuit: 1.2 N.m, control circuit: 1.4 N.m, power circuit: 35 N.m, power circuit: 37 N.m
electrical durability 250000 cycles AC-1, 600000 cycles AC-3
[Ue] rated operational voltage power circuit: <= 690 V AC 50/60 Hz
utilisation category AC-3, AC-1
[Ui] rated insulation voltage 690 V conforming to IEC 60947-4-1
control circuit voltage limits operational: 0.85...1.1 Uc at 50/60 Hz (at <55 °C), drop-out: 0.35...0.5 Uc at 50/60 Hz (at <55 °C)
associated fuse rating 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1, 800 A gG at <= 690 V coordination type 1 for power circuit
minimum switching voltage 17 V for control circuit
maximum operating rate 2400 cyc/h 55 °C
protective treatment TH (pollution degree 3) conforming to IEC 60068
fire resistance 850 °C conforming to IEC 60695-2-1
motor power kW 147 kW at 220...230 V AC 50/60 Hz, 250 kW at 380...400 V, 280 kW at 415 V, 295 kW at 440 V, 335 kW at 500 V, 355 kW at 660...690 V
heat dissipation 18-18 W for control circuit, 18-18 W