EasyPact TVS contactor 4 poles for category AC-1 applications up to 125A.

It provides a 220V 50/60Hz AC coil, 4NO built-in auxiliary contacts, power and control connections by screw clamp terminals.

95.5mm width for standard operating rates up to 1200 cycles per hour.

It procures standard reliability and durability with 0.35 Mcycles electrical durability and 3 Mcycles mechanical durability.

It can cover -5°C to 55°C working temperature and mounted by DIN-rail, No derating up to 3000m altitude.

Multi-standards certified (IEC, CCC, EAC) and Green Premium compliant (RoHs/Reach).

More Information
More Information
Attribute Value
SKU LC1E95004M7
ambient air temperature for storage -60-80 °C
overvoltage category III
pollution degree 3
ambient air temperature for operation -5-55 °C
[Icw] rated short-time withstand current 135 A 40 °C - 600 s for power circuit, 800 A 40 °C - 10 s for power circuit, 400 A 40 °C - 60 s for power circuit
product or component type Kontaktor
net weight 1.6 kg
standards IEC 60947-4-1, IEC 60947-5-1
mechanical durability 300000 cycles
device short name LC1E
range EasyPact TVS
average impedance 0.8 mOhm - Ith 125 A 50 Hz for power circuit
[Ie] rated operational current 125 A (at <60 °C) at <= 415 V AC AC-1 for power circuit
[Uc] control circuit voltage 220 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
product name EasyPact TVS
mechanical robustness vibrations contactor open: 1.5 Gn, 5...300 Hz, vibrations contactor closed: 3 Gn, 5...300 Hz, shocks contactor open: 6 Gn for 11 ms, shocks contactor closed: 7 Gn for 11 ms
power dissipation per pole 7.2 W AC-3, 12 W AC-1
[Ith] conventional free air thermal current 125 A (at 60 °C) for power circuit
control circuit type AC at 50/60 Hz
contactor application resistive load
insulation resistance > 10 MOhm for control circuit
rated breaking capacity 760 A at 440 V for power circuit conforming to IEC 60947
Irms rated making capacity 950 A at 440 V AC for power circuit conforming to IEC 60947-4-1
pole contact composition 4 NO
operating time 20...35 ms on closing, 6...30 ms on opening
hold-in power consumption in VA 22-22 VA 60 Hz cos phi 0.3 (at 20 °C), 20-20 VA 50 Hz cos phi 0.3 (at 20 °C)
inrush power in VA 200-200 VA 50 Hz cos phi 0.75 (at 20 °C), 220-220 VA 60 Hz cos phi 0.75 (at 20 °C)
permissible ambient air temperature around the device -20-70 °C at Uc
connections - terminals control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end, power circuit: screw clamp terminals 1 4-50 mm² - cable stiffness: flexible with cable end, power circuit: screw clamp terminals 2 4-16 mm² - cable stiffness: flexible with cable end, power circuit: screw clamp terminals 1 4-50 mm² - cable stiffness: solid without cable end, power circuit: screw clamp terminals 2 4-50 mm² - cable stiffness: solid without cable end
height 127 mm
mounting support DIN rail, plate
width 95 mm
depth 135 mm
operating altitude 3000 m without derating
IP degree of protection IP2x conforming to IEC 60529
poles description 4P
colour grey (RAL 7011)
tightening torque control circuit: 1.2 N.m, control circuit: 1.4 N.m, power circuit: 12 N.m, power circuit: 13.5 N.m
electrical durability 350000 cycles AC-1, 900000 cycles AC-3
[Ue] rated operational voltage power circuit: <= 690 V AC 50/60 Hz
utilisation category AC-1
[Ui] rated insulation voltage 690 V conforming to IEC 60947-4-1
control circuit voltage limits operational: 0.85...1.1 Uc at 50/60 Hz (at <55 °C), drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55 °C)
associated fuse rating 160 A gG at <= 690 V coordination type 1 for power circuit conforming to IEC 60947-5-1
maximum operating rate 1200 cyc/h 60 °C
protective treatment TH (pollution degree 3) conforming to IEC 60068
fire resistance 850 °C conforming to IEC 60695-2-1
heat dissipation 6-10 W for control circuit