Schneider Electric

EasyPact TVS thermal overload relay 124...198 A - class 10A - LRE483

Out of stock
SKU
LRE483
38%
Special Price Rp 5.334.926 Regular Price Rp 8.604.720
Details

The LRE relay is a differential thermal overload relays for use with fuses or magnetic circuit-breakers GV2 L and GV3 L.

Its thermal setting range is 124-198A 50/60Hz and the tripping class is 10A conforming to IEC 60947-4-1.

It can be direct mounted on EasyPact TVS contactors with directly connected by connector.

It protects unbalanced loads and motors with 132 - 280kW at 400VAC.

It provides manual or automatic reset, trip auxiliary contact and flag indicator.

Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach).

More Information
More Information
Attribute Value
SKU LRE483
product certifications GOST
ambient air temperature for storage -60-80 °C
ambient air temperature for operation -20-60 °C without derating conforming to IEC 60947-4-1, -20-70 °C with derating
product or component type Relay Beban Lebih Termal
net weight 2.1 kg
standards IEC 60947-4-1, IEC 60947-5-1
device short name LRE
range EasyPact TVS
product compatibility LC1E160...630
product name EasyPact TVS
mechanical robustness shocks: 6 Gn for 11 ms conforming to IEC 60068-2-7, vibrations: 3 Gn conforming to IEC 60068-2-6
[Ith] conventional free air thermal current 5 A for signalling circuit
electromagnetic compatibility surge withstand: 6 kV conforming to IEC 60801-5
signalling function relay trip indicator
relay application motor protection
tripping threshold 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
network frequency 50...60 Hz
connections - terminals signalling circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, signalling circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible without cable end, signalling circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: solid without cable end, power circuit: lugs, power circuit: bars - busbar cross section: 3 x 20 mm
height 131 mm
mounting support plate, under contactor
width 180 mm
depth 134 mm
dielectric strength 6 kV at 50 Hz conforming to IEC 60255-5
IP degree of protection IP00 conforming to IEC 60529
network type AC
tightening torque signalling circuit: 1.7 N.m - on screw clamp terminals, power circuit: 27.5 N.m - on bars M8, power circuit: 27.5 N.m - on lugs M8
control type push-button red stop:, push-button green reset:
[Ue] rated operational voltage <= 690 V AC
local signalling trip indicator
connection pitch 40 mm
[Ui] rated insulation voltage 690 V conforming to IEC 60947-4-1
auxiliary contact composition 1 NO + 1 NC
associated fuse rating 5 A gG for signalling circuit, 250 A gG for power circuit, 200 A aM for power circuit
protective treatment TH conforming to IEC 60068
fire resistance 850 °C conforming to IEC 60068-2-1
thermal protection adjustment range 124-198 A
phase failure sensitivity tripping current 130 % of Ir on two phase, the last one at 0 conforming to IEC 60947-4-1
thermal overload class class 10A conforming to IEC 60947-4-1
temperature compensation -20-60 °C