Schneider Electric
Masterpact MT interface and automatic controller - ACP + BA - 220..240 V - 29470
Out of stock
SKU
29470
Details
It is a remote controlled source changeover system for Compact NSX, Compact NS and Masterpact devices.
It is composed of an ACP plate and of an integrated BA controller.
This ACP provides in a single unit the protection of the controller, the control and the connection to the devices.
The BA controller is used to create simple source-changeover system that switch from one source to another depending on the presence of voltage UN on the “Normal” source.
The BA controller is generally used to manage two permanent sources.
The control voltage is from 220VAC to 240VAC 50/60Hz.
More Information
Attribute | Value |
---|---|
SKU | 29470 |
range of product | ComPact NS630b...1600, Masterpact NW, Masterpact NT, NSX400...630, NSX100...250, Compact NS100...630 |
product or component type | Air Circuit Breaker |
standards | IEC 947-5-1 |
device short name | ACP + BA |
range | Aksesoris |
product compatibility | Compact NSX400...630, Compact NSX100...250, Compact NS630b...1600 |
[Ie] rated operational current | AC-12: 4 A AC 440 V, AC-13: 7 A AC 48 V, AC-14: 4 A AC 110 V, AC-14: 4 A AC 220/240 V, AC-14: 5 A AC 24 V, AC-14: 5 A AC 48 V, AC-15: 3 A AC 220/240 V, AC-15: 4 A AC 110 V, AC-15: 5 A AC 24 V, AC-15: 5 A AC 48 V, DC-12: 0.4 A DC 250 V, AC-12: 5 A AC 380/415 V, DC-12: 0.6 A DC 110 V, DC-12: 2 A DC 48 V, DC-12: 8 A DC 24 V, DC-13: 2 A 24 V, AC-12: 8 A AC 110 V, AC-12: 8 A AC 220/240 V, AC-12: 8 A AC 24 V, AC-12: 8 A AC 48 V, AC-13: 6 A AC 110 V, AC-13: 6 A AC 220/240 V, AC-13: 7 A AC 24 V |
range compatibility | ComPact NSX circuit breaker, ComPact NS circuit breaker, MasterPact NT circuit breaker, Masterpact NW circuit breaker |
IK degree of protection | front: IK07 conforming to EN 50102 |
accessory / separate part category | interlocking accessory |
[Ith] conventional free air thermal current | 8 A |
[Us] rated supply voltage | 220...240 V AC at 50/60 Hz |
output type | contacts customer: indication of operation in automatic or stop mode |
operating mode | automatic operation, forced operation on replacement source, forced operation on normal source, stop (both normal and replacement source off) |
selection modes | circuit breaker on N, circuit breaker on R |
test function | by opening the P25M circuit breaker supplying the controller |
compatibility code | ACP+BA |
IP degree of protection | IP20 connectors: conforming to EN 60529, IP40 front: conforming to EN 60529, IP30 side: conforming to EN 60529 |
local signalling | off, on, fault trip |
interlocked device | Masterpact NW, NSX400...630, NSX100...250, Masterpact NT, Compact NS630b...1600, Compact NS100...630 |
input type | contacts customer voluntary order to transfer to source R |
complementary function | additional contact: transfer to replacement source only if contact is closed, voluntary transfer to replacement source (e.g. energy management commands) |
Technical Documents