This product is part of the Modicon TM3 range, an offer of expansion I/O modules for Modicon M221, M241, M251 and M262.

The analogue output module provides 2 outputs with 11bit + sign and 12bit resolution.

It is an output module with a rated supply voltage of 24V DC and a current consumption of 70mA at 24V DC via external supply full load.

This product is capable of controlling variable speed drives or any device equipped with a current or voltage input.

There is an insulation between output and supply at 1500V AC, output and internal logic at 500V AC.

It is furnished with removable screw terminal for electrical connection with 5.08mm pitch adjustment for outputs.

It is an IP20 rated product.

Its dimensions are 23.6mm (Width) x 70mm (Depth) x 90mm (Height).

It weighs 0.115kg.

This product is certified by CE.

It meets EN/IEC 61131-2 and EN/IEC 61010-2-201 standards.

This module is compatible with Modicon M262, Modicon M241, Modicon M251 and Modicon M221 logic controller.

It supports top hat type TH35-15, top hat type TH35-7.5 rail conforming to IEC 60715 and plate or panel with fixing kit mount.

Modicon TM3 expansion modules have been designed with a simple interlocking assembly mechanism.

A bus expansion connector is used to distribute data and the power supply when assembling the Modicon TM3 modules with logic controllers.

Boost the performance of your controller with the Modicon TM3 I/O system specially designed for the Modicon M221, M241 and M251 logic controllers.

More Information
More Information
Attribute Value
SKU TM221C16R
product certifications EAC, CSA, RCM, cULus, DNV-GL, IACS E10, ABS, LR
relative humidity 10-95 %, without condensation (in operation), 10-95 %, without condensation (in storage)
ambient air temperature for storage -25-70 °C
pollution degree <= 2
ambient air temperature for operation -10-55 °C (horizontal installation), -10-35 °C (vertical installation)
environmental characteristic ordinary and hazardous location
resistance to electrostatic discharge 8 kV in air conforming to EN/IEC 61000-4-2, 4 kV on contact conforming to EN/IEC 61000-4-2
voltage state 1 guaranteed >= 15 V for input
discrete output voltage 5...125 V DC, 5...250 V AC
data backed up 256 kB built-in flash memory for backup of application and data
maximum number of I/O expansion module 4 for transistor output, 4 for relay output
permitted overload on inputs +/- 30 V DC for 5 min (maximum) for analog input, +/- 13 V DC (permanent) for analog input
range of product Modicon M221
power supply output current 0.325-0.325 A 5 V for expansion bus, 0.12-0.12 A 24 V for expansion bus
product or component type Relay & Power Supply
net weight 0.346 kg
standards EN/IEC 61010-2-201, EN/IEC 61131-2, EN/IEC 60664-1
mechanical durability 20000000 cycles for relay output
range Modicon M221
[Us] rated supply voltage 100...240 V AC
electrical connection terminal block, 3 terminal(s) for connecting the 24 V DC power supply, connector, 4 terminal(s) for analogue inputs, mini B USB 2.0 connector for a programming terminal, removable screw terminal block for inputs, removable screw terminal block for outputs
immunity to microbreaks 10 ms
discrete output type relay normally open
backup time 1 year at 25 °C (by interruption of power supply)
voltage state 0 guaranteed <= 5 V for input
insulation between input and internal logic at 500 V AC, non-insulated between analogue input and internal logic, non-insulated between analogue inputs, between output and internal logic at 2300 V AC, between Ethernet terminal and internal logic at 500 V AC, between supply and sensor power supply at 2300 V AC, between supply and ground at 1500 V AC, between sensor power supply and ground at 500 V AC, between input and ground at 500 V AC, between output and ground at 1500 V AC, between supply and internal logic at 2300 V AC, between sensor power supply and internal logic at 500 V AC
discrete output current 2 A
memory capacity 256 kB for user application and data RAM with 10000 instructions, 256 kB for internal variables RAM
conversion time 1 ms per channel + 1 controller cycle time for analogue input analog input
analogue input resolution 10 bits
maximum cable distance between devices shielded cable: <10 m for fast input, unshielded cable: <30 m for output, unshielded cable: <30 m for digital input, unshielded cable: <1 m for analog input
network frequency 50/60 Hz
height 90 mm
output voltage limits 125 V DC, 277 V AC
mounting support top hat type TH35-15 rail conforming to IEC 60715, top hat type TH35-7.5 rail conforming to IEC 60715, plate or panel with fixing kit
marking CE
width 95 mm
depth 70 mm
inrush current 40 A
vibration resistance 3.5 mm at 5-8.4 Hz on symmetrical rail, 3.5 mm at 5-8.4 Hz on panel mounting, 1 gn at 8.4-150 Hz on symmetrical rail, 1 gn at 8.4-150 Hz on panel mounting
operating altitude 0...2000 m
IP degree of protection IP20 with protective cover in place
electrical durability 100000 cycles AC-12, 240 V, 480 VA, resistive, 100000 cycles DC-12, 24 V, 48 W, resistive, 100000 cycles AC-12, 120 V, 240 VA, resistive, 100000 cycles AC-14, cos phi = 0.7 , 240 V, 240 VA, inductive, 300000 cycles AC-14, cos phi = 0.7 , 120 V, 36 VA, inductive, 300000 cycles AC-14, cos phi = 0.7 , 240 V, 72 VA, inductive, 300000 cycles DC-12, 24 V, 16 W, resistive, 100000 cycles DC-13, 24 V, 24 W, inductive (L/R = 7 ms), 300000 cycles DC-13, 24 V, 7.2 W, inductive (L/R = 7 ms), 300000 cycles AC-12, 120 V, 80 VA, resistive, 300000 cycles AC-12, 240 V, 160 VA, resistive, 100000 cycles AC-15, cos phi = 0.35 , 120 V, 60 VA, inductive, 100000 cycles AC-15, cos phi = 0.35 , 240 V, 120 VA, inductive, 300000 cycles AC-15, cos phi = 0.35 , 120 V, 18 VA, inductive, 300000 cycles AC-15, cos phi = 0.35 , 240 V, 36 VA, inductive, 100000 cycles AC-14, cos phi = 0.7 , 120 V, 120 VA, inductive
local signalling 1 LED (green) for PWR, 1 LED (green) for RUN, 1 LED (red) for module error (ERR), 1 LED (green) for SD card access (SD), 1 LED (red) for BAT, 1 LED (green) for SL1, 1 LED (green) for SL2, 1 LED per channel (green) for I/O state
response time 35 µs turn-off, I2...I5 terminal(s) for input, 5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input, 35 µs turn-on, other terminals terminal(s) for input, 5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input, 100 µs turn-off, other terminals terminal(s) for input, 10 ms turn-on for output, 10 ms turn-off for output
integrated connection type USB port with mini B USB 2.0 connector, non isolated serial link serial 1 with RJ45 connector and RS485 interface, non isolated serial link serial 2 with RJ45 connector and RS232/RS485 interface
protection type without protection at 5 A
absolute accuracy error +/- 1 % of full scale for analog input
maximum power consumption in VA 46 VA at 100...240 V with max number of I/O expansion module, 31 VA at 100...240 V without I/O expansion module
shock resistance 98 m/s² for 11 ms
reset time 1 s
minimum load 1 mA at 5 V DC for relay output
supply voltage limits 85-264 V
communication port protocol USB port: USB - SoMachine-Network, non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network
control signal type single phase, frequency meter, dual phase (quadrature), dual phase (pulse/direction)
surge withstand 2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5, 2 kV relay output common mode conforming to EN/IEC 61000-4-5, 1 kV shielded cable common mode conforming to EN/IEC 61000-4-5, 1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5, 1 kV relay output differential mode conforming to EN/IEC 61000-4-5, 1 kV I/O common mode conforming to EN/IEC 61000-4-5, 0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5, 0.5 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5
resistance to electromagnetic fields 10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3, 3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3, 1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
resistance to fast transients 2 kV (power lines) conforming to EN/IEC 61000-4-4, 2 kV (relay output) conforming to EN/IEC 61000-4-4, 1 kV (serial link) conforming to EN/IEC 61000-4-4, 1 kV (I/O) conforming to EN/IEC 61000-4-4, 1 kV (Ethernet line) conforming to EN/IEC 61000-4-4
electromagnetic emission conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10-150 kHz conforming to EN/IEC 55011, conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5-30 MHz conforming to EN/IEC 55011, radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30-230 MHz conforming to EN/IEC 55011, conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150-1500 kHz conforming to EN/IEC 55011, conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15-0.5 MHz conforming to EN/IEC 55011, conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5-300 MHz conforming to EN/IEC 55011, radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 200-1000 MHz conforming to EN/IEC 55011
discrete input voltage 24 V
discrete output number 7 relay
discrete input number 9 , discrete input conforming to IEC 61131-2 Type 1
transmission rate 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15-15 m for RS485, 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3-3 m for RS232, 480 Mbit/s for USB
discrete input logic sink or source (positive/negative)
switching frequency 20 switching operations/minute with maximum load
analogue input number 2 at 0...10 V
regulation loop adjustable PID regulator up to 14 simultaneous loops
input impedance 3.4 kOhm for discrete input, 100 kOhm for analog input, 4.9 kOhm for fast input
clock drift <= 30 s/month at 25-25 °C
discrete input current 7 mA for discrete input, 5 mA for fast input
supply (serial)serial link supply: 5 V, <200 mA
LSB value 10 mV
resistance to conducted disturbances 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6, 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL), 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
storage altitude 0-3000 m
discrete input voltage type DC
battery type BR2032 lithium non-rechargeable, battery life: 4 year(s)
discrete I/O number 16
configurable filtering time 0 ms for input, 3 ms for input, 12 ms for input
sensor power supply 24-24 V DC at 250 mA supplied by the controller
execution time for 1 KInstruction 0.3 ms for event and periodic task
realtime clock with
data storage equipment 2 GB SD card (optional)
counting input number 4 fast input (HSC mode) at 100 kHz 32 bits
resistance to magnetic fields 30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
exct time for event task 60 µs response time
maximum current per output common 7 A at COM 0, 6 A at COM 1
maximum size of object areas 8000 %MW memory words, 255 %TM timers, 512 %KW constant words, 512 %M memory bits, 255 %C counters
execution time per instruction 0.2 µs Boolean