Schneider Electric

Modicon M241 Controller 40 IO transistor PNP Ethernet - TM241CE40T

Out of stock
SKU
TM241CE40T
33%
Special Price Rp 8.867.573 Regular Price Rp 13.235.184
Details

This product is part of the Modicon TM3 range, an offer of expansion I/O modules for Modicon M221, M241, M251 and M262.

The analogue output module provides 2 outputs with 11bit + sign and 12bit resolution.

It is an output module with a rated supply voltage of 24V DC and a current consumption of 70mA at 24V DC via external supply full load.

This product is capable of controlling variable speed drives or any device equipped with a current or voltage input.

There is an insulation between output and supply at 1500V AC, output and internal logic at 500V AC.

It is furnished with removable screw terminal for electrical connection with 5.08mm pitch adjustment for outputs.

It is an IP20 rated product.

Its dimensions are 23.6mm (Width) x 70mm (Depth) x 90mm (Height).

It weighs 0.115kg.

This product is certified by CE.

It meets EN/IEC 61131-2 and EN/IEC 61010-2-201 standards.

This module is compatible with Modicon M262, Modicon M241, Modicon M251 and Modicon M221 logic controller.

It supports top hat type TH35-15, top hat type TH35-7.5 rail conforming to IEC 60715 and plate or panel with fixing kit mount.

Modicon TM3 expansion modules have been designed with a simple interlocking assembly mechanism.

A bus expansion connector is used to distribute data and the power supply when assembling the Modicon TM3 modules with logic controllers.

Boost the performance of your controller with the Modicon TM3 I/O system specially designed for the Modicon M221, M241 and M251 logic controllers.

More Information
More Information
Attribute Value
SKU TM241CE40T
product certifications CSA, RCM, cULus, IACS E10
relative humidity 10-95 %, without condensation (in operation), 10-95 %, without condensation (in storage)
ambient air temperature for storage -25-70 °C
pollution degree 2
ambient air temperature for operation -10-50 °C (vertical installation), -10-55 °C (horizontal installation)
resistance to electrostatic discharge 8 kV in air conforming to EN/IEC 61000-4-2, 4 kV on contact conforming to EN/IEC 61000-4-2
voltage state 1 guaranteed >= 15 V for input
cycle time 10 ms 16 Ethernet/IP, 64 ms 64 Modbus TCP
discrete output voltage 24 V DC for transistor output
data backed up 128 MB built-in flash memory for backup of user programs
maximum number of I/O expansion module 7 (local), 14 (remote)
range of product Modicon M241
product or component type Relay & Power Supply
net weight 0.62 kg
standards UL 508, ANSI/ISA 12-12-01, CSA C22.2 No 142, CSA C22.2 No 213, EN/IEC 61131-2:2007, Marine specification (LR, ABS, DNV, GL), UL 1604
range Modicon M241
[Us] rated supply voltage 24 V DC
electrical connection removable screw terminal blockfor inputs and outputs (pitch 5.08 mm), removable screw terminal blockfor connecting the 24 V DC power supply (pitch 5.08 mm)
immunity to microbreaks 10 ms
discrete output type transistor
maximum output frequency 20 kHz for fast output (PWM mode), 100 kHz for fast output (PLS mode), 1 kHz for output
backup time 2 years at 25 °C
voltage state 0 guaranteed <= 5 V for input
insulation between supply and internal logic at 500 V AC, non-insulated between supply and ground, between output and internal logic at 500 V AC, between input and internal logic at 500 V AC, between fast input and internal logic at 500 V AC, non-insulated between inputs, between output groups at 500 V AC, non-insulated between outputs, between fast output and internal logic at 500 V AC
discrete output current 0.1 A for fast output (PTO mode) (Q0...Q3), 0.5 A for transistor output (Q0...Q15)
memory capacity 8 MB for program, 64 MB for system memory RAM
maximum cable distance between devices unshielded cable: <50 m for input, shielded cable: <10 m for fast input, unshielded cable: <50 m for output, shielded cable: <3 m for fast output
port Ethernet 10BASE-T/100BASE-TX - 1 port(s) copper cable
height 90 mm
output voltage limits 30 V DC
mounting support top hat type TH35-15 rail conforming to IEC 60715, top hat type TH35-7.5 rail conforming to IEC 60715, plate or panel with fixing kit
marking CE
width 190 mm
depth 95 mm
inrush current 50 A
vibration resistance 3.5 mm at 5-8.4 Hz on symmetrical rail, 3 gn at 8.4-150 Hz on symmetrical rail, 3.5 mm at 5-8.4 Hz on panel mounting, 3 gn at 8.4-150 Hz on panel mounting
operating altitude 0...2000 m
IP degree of protection IP20 with protective cover in place
local signalling 1 LED (green) for PWR, 1 LED (green) for RUN, 1 LED (red) for module error (ERR), 1 LED (red) for I/O error (I/O), 1 LED (green) for SD card access (SD), 1 LED (red) for BAT, 1 LED (green) for SL1, 1 LED (green) for SL2, 1 LED (red) for bus fault on TM4 (TM4), 1 LED per channel (green) for I/O state, 1 LED (green) for Ethernet port activity
response time 50 µs turn-on, I0...I15 terminal(s) for input, <= 2 µs turn-on, I0...I7 terminal(s) for fast input, <= 2 µs turn-off, I0...I7 terminal(s) for fast input, <= 2 µs turn-on, Q0...Q3 terminal(s) for fast output, <= 2 µs turn-off, Q0...Q3 terminal(s) for fast output, 50 µs turn-off, I0...I15 terminal(s) for input, <= 34 µs turn-on, Q0...Q15 terminal(s) for output, <= 250 µs turn-off, Q0...Q15 terminal(s) for output
integrated connection type non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface, non isolated serial link serial 2 with removable screw terminal block connector and RS485 interface, USB port with mini B USB 2.0 connector, Ethernet with RJ45 connector
power consumption in W 32.6-40.4 W (with max number of I/O expansion module)
protection type short-circuit protection, short-circuit and overload protection with automatic reset, reverse polarity protection for fast output
shock resistance 15 gn for 11 ms
reset time 10 ms automatic reset output, 12 s automatic reset fast output
supply voltage limits 20.4-28.8 V
communication port protocol non isolated serial link: Modbus master/slave
communication service FDR, DHCP server via TM4 Ethernet switch network module, DHCP client embedded Ethernet port, SMS notifications, updating firmware, SNMP client/server, programming, NGVL, monitoring, IEC VAR ACCESS, FTP client/server, downloading, SQL client, Modbus TCP client I/O scanner, Ethernet/IP originator I/O scanner embedded Ethernet port, Ethernet/IP target, Modbus TCP server and Modbus TCP slave, send and receive email from the controller based on TCP/UDP library, web server (WebVisu & XWeb system), OPC UA server, DNS client
control signal type A/B at 100 kHz for fast input (HSC mode), pulse/direction at 200 kHz for fast input (HSC mode), single phase at 200 kHz for fast input (HSC mode)
surge withstand 1 kV shielded cable common mode conforming to EN/IEC 61000-4-5, 1 kV relay output differential mode conforming to EN/IEC 61000-4-5, 1 kV input common mode conforming to EN/IEC 61000-4-5, 1 kV transistor output common mode conforming to EN/IEC 61000-4-5, 0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5, 1 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5
resistance to electromagnetic fields 10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3, 3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3, 1 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3
resistance to fast transients 2 kV (power lines) conforming to EN/IEC 61000-4-4, 1 kV (serial link) conforming to EN/IEC 61000-4-4, 1 kV (input) conforming to EN/IEC 61000-4-4, 1 kV (transistor output) conforming to EN/IEC 61000-4-4, 1 kV (Ethernet line) conforming to EN/IEC 61000-4-4
electromagnetic emission conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10-150 kHz conforming to EN/IEC 55011, conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5-30 MHz conforming to EN/IEC 55011, conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150-1500 kHz conforming to EN/IEC 55011, radiated emissions - test level: 40 dBμV/m QP class A at 30-230 MHz conforming to EN/IEC 55011, radiated emissions - test level: 47 dBμV/m QP class A at 230-1000 MHz conforming to EN/IEC 55011
discrete input voltage 24 V
discrete output number 16 transistor 4 fast output
discrete input number 24 , discrete input 8 fast input conforming to IEC 61131-2 Type 1
transmission rate 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15-15 m for RS485, 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3-3 m for RS232, 480 Mbit/s for bus length of 3-3 m for USB, 10/100 Mbit/s for Ethernet
discrete input logic sink or source
accuracy +/- 0.1 % at 0.02-0.1 kHz for fast output, +/- 1 % at 0.1-1 kHz for fast output
input impedance 4.7 kOhm for input, 2.81 kOhm for fast input
clock drift <= 60 s/month at 25-25 °C
discrete input current 7 mA for input, 10.7 mA for fast input
maximum voltage drop <1 V
maximum leakage current 5 µA for output
supply (serial 1)serial link supply: 5 V, <200 mA
web services web server
resistance to conducted disturbances 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6, 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL), 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
discrete output logic positive logic (source)
storage altitude 0-3000 m
discrete input voltage type DC
positioning functions PTO function 4 channel(s) (positioning frequency: 100 kHz), PTO function 4 channel(s) for transistor output (positioning frequency: 1 kHz)
battery type BR2032 lithium non-rechargeable, battery life: 4 year(s)
discrete I/O number 40
application structure 4 cyclic master tasks, 3 cyclic master tasks + 1 freewheeling task, 8 external event tasks, 8 event tasks
configurable filtering time 1 µs for fast input, 0 ms for input, 12 ms for input, 12 ms for fast input, 1 ms for input, 4 ms for input
execution time for 1 KInstruction 0.3 ms for event and periodic task, 0.7 ms for other instruction
realtime clock with
data storage equipment <= 16 GB SD card (optional)
counting input number 4 fast input (HSC mode) at 200 kHz, 16 standard input at 1 kHz
maximum current per output common 2 A
maximum tungsten load <2.4 W
maximum number of connections 8 Modbus server, 8 SoMachine protocol, 10 web server, 4 FTP server, 16 Ethernet/IP target, 8 Modbus client
number of slave 64 Modbus TCP:, 16 Ethernet/IP:
PT. Telesindo Citra Sejahtera © 2021 All Rights Reserved.