Schneider Electric
OsiSense XM pressure sensor XMLG - 0..400 bar - G 1/4A (male) - 24 V - 4..20 mA - XMLG400D21
Out of stock
SKU
XMLG400D21
Details
The XMLG range is an offer of electronic pressure transmitters, with an analogue or solid-state output.
The XMLG transmitters feature a stainless steel AISI 303 body and a ceramic cell combined with a viton gasket.
Therefore, they are compatible with industrial fluids such as air, fresh water and hydraulic oils.
From 0bar to 400bar or 0psi to 5800psi.
Analogue output: 4mA to 20mA.
Fluid connection: G 1/4 A (male).
Electrical connection: M12.
More Information
Attribute | Value |
---|---|
SKU | XMLG400D21 |
pressure sensor size | 400 bar |
product certifications | EAC, CSA C22.2 No 14, UL 508 |
ambient air temperature for storage | -40-85 °C |
ambient air temperature for operation | -15-85 °C |
resistance to electrostatic discharge | 15 kV in air conforming to EN/IEC 61000-4-2, 8 kV on contact conforming to EN/IEC 61000-4-2 |
range of product | OsiSense XM |
operating position | any position |
product or component type | Detektor / Sensor |
current consumption | < 20 mA |
net weight | 0.095 kg |
standards | CE, EN/IEC 61326-2-3 |
mechanical durability | 10000000 cycles |
range | Pressure Switch |
[Uimp] rated impulse withstand voltage | 0.5 kV |
[Us] rated supply voltage | 12 V DC (voltage limits: 8-33 V), 24 V DC (voltage limits: 8-33 V) |
electrical connection | 1 male connector M12, 3 pins |
repeat accuracy | +/- 0.1 % of the measuring range |
scale type | fixed differential |
pressure sensor name | XMLG |
response time on output | < 2 ms |
height | 58.1 mm |
vibration resistance | 20 gn (f= 9-2000 Hz) conforming to EN/IEC 60028-2-6 |
IP degree of protection | IP66 conforming to EN/IEC 60529, IP67 conforming to EN/IEC 60529 |
Quantity per set | set of 1 |
type of packing | individual |
protection type | reverse polarity, load short-circuit |
protective treatment | TC |
shock resistance | 25 gn for 11 ms conforming to EN/IEC 60068-2-27 |
NEMA degree of protection | NEMA 4 |
measurement accuracy | +/- 0.3 % of the measuring range |
length | 48.5 mm |
surge withstand | 1 kV 42 Ohm conforming to EN/IEC 61000-4-5, 500 kV 12 Ohm conforming to EN/IEC 61000-4-5 |
resistance to electromagnetic fields | 200 V/m 80-1000 Hz conforming to EN/IEC 61000-4-3 |
resistance to fast transients | 4 kV conforming to EN/IEC 61000-4-4 |
diameter | 22.8 mm |
local display | without |
pressure sensor type | pressure transmitter |
controlled fluid | air (-15-125 °C), corrosive fluid (-15-125 °C), hydraulic oil (-15-125 °C), fresh water (0-125 °C), air,hydraulic oil,corrosive fluid,fresh water |
electrical circuit type | control circuit |
maximum permissible accidental pressure | 800 bar |
materials in contact with fluid | stainless steel type AISI 303, ceramic, FPM (Viton), PPS |
temperature of controlled fluid | -15-125 °C |
destruction pressure | 900 bar |
fluid connection type | G 1/4A (male) conforming to DIN 3852-E |
type of output signal | analogue |
resistance to conducted disturbances | 30 V (0.15-80 Hz) conforming to EN/IEC 61000-4-6 |
resistance to magnetic fields | 30 A/m 50 Hz conforming to EN/IEC 61000-4-8 |
analogue output function | 4...20 mA, 2 wires |
drift of the zero point | +/- 0.015 % of measuring range/°C |
drift of the sensitivity | +/- 0.015 % of measuring range/°C |
pressure setting range | 0-400 bar |
Technical Documents