Schneider Electric        
    
    
        
            
    
OsiSense XM pressure sensor XMLK - 0..150psi - 1/4NPT - 4..20mA - M12 - set of 1 - XMLK150P2D23
            Out of stock
        
    
            SKU
        
XMLK150P2D23
                        More Information
                    
                        | Attribute | Value | 
|---|---|
| SKU | XMLK150P2D23 | 
| pressure sensor size | 150-150 psi | 
| product certifications | EAC, RCM, CSA C22.2 No 14, UL 508 | 
| ambient air temperature for storage | -25-80 °C | 
| ambient air temperature for operation | 0-80 °C | 
| range of product | OsiSense XM | 
| operating position | any position | 
| product or component type | Detektor / Sensor | 
| current consumption | < 20 mA | 
| net weight | 0.11 kg | 
| standards | CE, EN/IEC 61326-2-3 | 
| mechanical durability | 10000000 cycles | 
| range | Pressure Switch | 
| [Uimp] rated impulse withstand voltage | 0.5 kV | 
| [Us] rated supply voltage | 24 V DC SELV (voltage limits: 8-33 V) | 
| electromagnetic compatibility | electrostatic discharge immunity test conforming to EN/IEC 61000-4-2 8 kV air, 6 kV contact, susceptibility to electromagnetic fields conforming to EN/IEC 61000-4-3 10 V/m 80...1000 MHz, electrical fast transient/burst immunity test conforming to EN/IEC 61000-4-4 2 kV, 1.2/50 µs shock waves immunity test conforming to EN/IEC 61000-4-5 500 V 12 Ohm, 1 kV 42 Ohm, radiated RF fields conforming to EN/IEC 61000-4-6 10 V 0.15...80 MHz, immunity to magnetic fields conforming to EN/IEC 61000-4-8 30 A/m 50 Hz | 
| electrical connection | 1 male connector M12 4 pins | 
| repeat accuracy | +/- 1 % of the measuring range | 
| scale type | fixed differential | 
| pressure sensor name | XMLK | 
| response time on output | < 5 ms | 
| vibration resistance | 20 gn (f = 9-2000 Hz) conforming to EN/IEC 60068-2-6 | 
| IP degree of protection | IP65 conforming to EN/IEC 60529 | 
| Quantity per set | set of 1 | 
| type of packing | individual | 
| protection type | reverse polarity, load short-circuit | 
| protective treatment | TC | 
| shock resistance | 25 gn for 11 ms conforming to EN/IEC 60068-2-27 | 
| NEMA degree of protection | NEMA 4 | 
| measurement accuracy | +/- 1 % of the measuring range | 
| length | 65.5 mm | 
| accuracy | 0.1 % of the measuring range | 
| diameter | 36 mm | 
| local display | without | 
| pressure sensor type | pressure transmitter | 
| controlled fluid | air (0-80 °C), fresh water (0-80 °C), air,fresh water | 
| electrical circuit type | control circuit | 
| maximum permissible accidental pressure | 300 psi | 
| materials in contact with fluid | stainless steel type AISI 303, nitrile (NBR), ceramic | 
| temperature of controlled fluid | 80-80 °C | 
| destruction pressure | 450 psi | 
| fluid connection type | 1/4" - 18 NPT (male) | 
| type of output signal | analogue | 
| analogue output function | 4...20 mA, 2-wire | 
| drift of the zero point | +/- 0.03 % of measuring range/°K | 
| drift of the sensitivity | +/- 0.04 % of measuring range/°K | 
| pressure setting range | 0-150 psi | 
                        Technical Documents
                    
                    
    
                