PowerTag Flex 160A 3P/3P+N top and bottom position - A9MEM1580
This PowerTag Energy F160 3P/3P+N is a wireless communication energy sensor.
With its Flex design, it is dedicated to 3P and 3P+N devices with 25 to 27 mm pitch between phases, rating up to 160A.
It has to be associated with a concentror or a gateway to provide circuit monitoring and diagnosis down to load level.
It is designed specifically for Energy Management, Load Monitoring and Power Availability applications.
It incorporates accurate real-time measurements of active, reactive and apparent energy, active, reactive and apparent power, current, voltage and power factor.
In case of power outage, it sends a voltage loss alarm and the current-per-phase value before being de-energized.
PowerTag Energy F160 complies with IEC 61557-12 standard.
It is a PMD-II/DD/K70/1.
The Performance category is Class 1.
The Imax maximum current is 160A.
The Ib Base current is 25A.
The Saturation current is 320A and the Ist Starting current is 100mA.
The Un Rated voltages are Phase-to-neutral 100 to 277VAC +/- 20% and Phase-to-phase 173 to 480VAC +/- 20%.
The maximum consumption is below or equal to 3VA.
It can be either mounted on the top or the bottom of the protective device.
The product color is white (RAL9003).
The weight is 100g.
The degree of protection is IP20 and IK05.
The operating temperature is between -25°C to +70°C.
The storage temperature is between -40°C to +85°C.
Attribute | Value |
---|---|
SKU | A9MEM1580 |
relative humidity | 0-95 % at 55-55 °C conforming to IEC 60721-3-3 |
ambient air temperature for storage | -50-85 °C |
overvoltage category | IV conforming to IEC 61010-1 |
pollution degree | 3 |
ambient air temperature for operation | -25-70 °C |
environmental characteristic | indoor use |
quality labels | CE |
cable cross section | 1 rigid cable 0.2-1.5 mm² without cable end, 1 stranded cable 0.2-2.5 mm² without cable end, 1 stranded cable 0.25-1.5 mm² with cable end |
product or component type | Meter & Manajemen Energi |
net weight | 80 g |
mounting mode | free mounting |
standards | IEC 61557-12, IEC 61010 |
range | PowerTag |
wire stripping length | 11 mm |
range compatibility | Compact INS, ComPact NSXm, Acti 9 iID, Acti 9 iSW, Acti 9 iSW-NA, PowerPact B, Acti 9 C120, Acti 9 NG125, TeSys GV4 |
IK degree of protection | IK05 |
product name | PowerTag F160 |
type of measurement | voltage, current, frequency, power factor, active and reactive power, active and reactive energy, apparent energy, apparent power, internal temperature |
measurement category | category IV conforming to IEC 61010-2-030 |
electrical connection | removable spring terminal block |
starting current | 100 mA |
transmission support medium | radio frequency 2.4-2.4835 GHz conforming to IEEE 802.15.4 |
saturation current | 320 A |
form factor | flex |
maximum emission power | 10 mW |
Concentrator compatibility | Acti9 PowerTag Link C, Acti9 PowerTag Link, Acti9 PowerTag Link HD, Harmony Hub |
Event management | voltage loss with measured current at voltage loss |
[Ib] basic current | 25 A |
maximum cable outer diameter | 17 mm |
network frequency | 50 Hz, 60 Hz |
height | 39 mm |
mounting support | cables |
width | 91 mm |
depth | 62 mm |
vibration resistance | 3M4 conforming to IEC 60721-3-3 |
operating altitude | 0...2000 m |
IP degree of protection | IP20 conforming to IEC 60529 |
poles description | 3P, 3P + N |
colour | white (RAL 9003) |
[Ue] rated operational voltage | 100...277 V AC, +/- 20 %, phase to neutral, 173...480 V AC, +/- 20 %, phase to phase |
product destination | switchboard |
connection pitch | 27 mm |
maximum power consumption in VA | 3 VA |
metering type | active power P, P1, P2, P3, calculated neutral current, reactive power Q, Q1, Q2, Q3, apparent power S, S1, S2, S3, active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at total per phase, active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at partial per phase, active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at 3-phase total, active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at 3-phase partial, reactive energy E -rA- IN/OUT 0...281 x 10exp(9) kVARh at total per phase, reactive energy E -rA- IN/OUT 0...281 x 10exp(9) kVARh at partial per phase, reactive energy E -rA- IN/OUT 0...281 x 10exp(9) kVARh at 3-phase total, reactive energy E -rA- IN/OUT 0...281 x 10exp(9) kVARh at 3-phase partial, apparent energy E -apA- 0...281 x 10exp(9) kVAh at total per phase, apparent energy E -apA- 0...281 x 10exp(9) kVAh at partial per phase, apparent energy E -apA- 0...281 x 10exp(9) kVAh at 3-phase total, apparent energy E -apA- 0...281 x 10exp(9) kVAh at 3-phase partial, current I1, I2, I3, voltage U12, U23, U31, voltage V1N, V2N, V3N, frequency 45...65 Hz, power factor at per phase, power factor at total |
accuracy class | class 1 active energy conforming to IEC 61557-12, class 2 reactive energy conforming to IEC 61557-12, class 2 apparent energy conforming to IEC 61557-12, class 1 active power conforming to IEC 61557-12, class 2 reactive power conforming to IEC 61557-12, class 2 apparent power conforming to IEC 61557-12, class 1 current conforming to IEC 61557-12, class 0.5 voltage conforming to IEC 61557-12, class 1 power factor conforming to IEC 61557-12, class 1 frequency conforming to IEC 61557-12 |
product specific application | energy management, overload alarm, power factor, load monitoring, circuit monitoring |
mounting location | top or bottom |
directives | 2014/53/EU - radio equipment directive |
max current | 160 A |