PowerTag Flex 63A 3P+N top and bottom position - A9MEM1570
This PowerTag Energy F63 1P+N 110V is a wireless communication energy sensor.
With its Flex design, it is dedicated to 3P+N devices, rating less than or equal 63A.
It has to be associated with a concentror or a gateway to provide circuit monitoring and diagnosis down to load level.
It is designed specifically for Energy Management, Load Monitoring and Power Availability applications.
It incorporates accurate real-time measurements of active energy, active power, current, voltage and power factor.
In case of power outage, it sends a voltage loss alarm and the current-per-phase value before being de-energized.
PowerTag Energy 63A complies with IEC 61557-12 standard.
It is a PMD-I/DD/K55/1.
The Performance category is Class 1.
The Imax Maximum current is 63A.
The Ib Base current is 10A.
The Saturation current is 130A.
The Ist Starting current is 40mA.
The Un rated voltage are Phase-to-neutral 220VAC to 240VAC +/- 20% and Phase-to-phase 380VAC to 415VAC +/- 20%.
The maximum consumption is below or equal to 2VA.
It can be either mounted on the top or the bottom of the protective device.
The product color is white (RAL9003).
The weight is 40g.
The degree of protection is IP20 and IK05 The operating temperature is between -25°C to +60°C.
The Storage temperature is between -40°C to +85°C.
Attribute | Value |
---|---|
SKU | A9MEM1570 |
relative humidity | 0-95 % at 45-45 °C conforming to IEC 60721-3-3 |
ambient air temperature for storage | -40-85 °C |
overvoltage category | III conforming to IEC 61010-1 |
pollution degree | 3 |
ambient air temperature for operation | -25-60 °C |
environmental characteristic | indoor use, dustproof class 3S3 conforming to IEC 60721-3-3, salt mist class 3C2 conforming to IEC 60721-3-3 |
quality labels | CE |
Cable length | 0.25 m |
cable cross section | 1 rigid cable 1.5-16 mm², 2 stranded cable 1.5-2.5 mm², 2 rigid cable 1.5-2.5 mm², 1 stranded cable 1.5-16 mm² |
product or component type | Meter & Manajemen Energi |
net weight | 40 g |
mounting mode | by screws (terminals) |
standards | IEC 61557-12, IEC 61010-1, IEC 61010-2-030, IEC 61326-1, ETSI EN 300 328 |
range | PowerTag |
range compatibility | Vigi DT40, Vigi iC40, Vigi iDT40, Vigi N40, Vigi C40, Vigi iC60, Acti 9 iDD40, Acti 9 iDD40 XA, Acti 9 iCV40 XA, Vigi iDPN, Acti 9 iCV40, Vigi iTG40, Vigi iCG40 |
IK degree of protection | IK05 |
product name | PowerTag A9 F63 |
type of measurement | voltage, current, power factor, active energy, active power |
measurement category | category III conforming to IEC 61010-2-030 |
electrical connection | wires with cable end |
starting current | 40 mA |
transmission support medium | radio frequency 2.4-2.4835 GHz conforming to IEEE 802.15.4 |
saturation current | 130 A |
form factor | flex |
maximum emission power | 10 mW |
Concentrator compatibility | Acti9 PowerTag Link C, Acti9 PowerTag Link, Acti9 PowerTag Link HD, Harmony Hub, Acti9 Smartlink SI B, Acti9 Smartlink SI D |
Event management | voltage loss with measured current at voltage loss |
[Ib] basic current | 10 A |
network frequency | 50 Hz, 60 Hz |
height | sensor element: 20 mm |
mounting support | on circuit breaker |
compatibility code | PowerTag A9 P63 |
width | sensor element: 54 mm |
depth | sensor element: 46.6 mm |
vibration resistance | 3M4 conforming to IEC 60721-3-3 |
operating altitude | 0...2000 m |
IP degree of protection | IP20 conforming to IEC 60529 |
poles description | 3P + N |
colour | white (RAL 9003) |
[Ue] rated operational voltage | 220...240 V AC, +/- 20 %, between phase and neutral, 380...415 V AC, +/- 20 %, between phases |
product destination | switchboard |
market segment | buildings: breaker voltage monitoring, buildings: cost allocation, buildings: overload alarm |
maximum power consumption in VA | 2 VA |
accuracy class | class 1 active energy conforming to IEC 61557-12, class 1 active power conforming to IEC 61557-12, class 1 current conforming to IEC 61557-12, class 0.5 voltage conforming to IEC 61557-12, class 1 power factor conforming to IEC 61557-12 |
product specific application | energy management, overload alarm, load monitoring, circuit monitoring, cost allocation |
mounting location | top or bottom |
directives | 2014/53/EU - radio equipment directive |
max current | 63 A |