SKU 59659
ambient air temperature for operation -25-70 °C
range of product Sepam series 80 NPP, Sepam series 80, Sepam series 60, Sepam series 40
product or component type Relay Proteksi Digital
net weight 0.4 kg
mounting mode fixed
device short name ACE850FO
range Sepam Series 40
wire stripping length supply: 8 mm
mechanical robustness earthquakes in operation (level: 2) : 1 Gn (vertical axes) conforming to IEC 60255-21-3, earthquakes in operation (level: 2) : 2 Gn (horizontal axes) conforming to IEC 60255-21-3, jolts de-energized (level: 2) : 20 Gn/16 ms conforming to IEC 60255-21-2, shocks in operation (level: 2) : 10 Gn/11 ms conforming to IEC 60255-21-2, vibrations de-energized (level: 2) : 2 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1, vibrations in operation (level: 2) : 1 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1, vibrations in operation (level: Fc) : 2 Hz...13.2 Hz, a = +/- 1 mm conforming to IEC 60068-2-6, shocks de-energized (level: 2) : 30 Gn/11 ms conforming to IEC 60255-21-2
auxiliary connection terminal protective earth: screw-type connector 1 pin(s) 1 cable(s) wire 2.5-2.5 mm² <3 m, supply: screw-type connector 2 pin(s) 1 cable(s) wire 0.2-2.5 mm², supply: screw-type connector 2 pin(s) 1 cable(s) wire 1.5-1.5 mm², supply: screw-type connector 2 pin(s) 1 cable(s) wire 2.5-2.5 mm², supply: screw-type connector 2 pin(s) 2 cable(s) wire 0.2-1 mm², supply: screw-type connector 2 pin(s) 2 cable(s) wire 1-1 mm², functional earth: ring lug 1 pin(s) 1 cable(s) 4-4 mm²
[Us] rated supply voltage 110...240 V AC tolerance: - 20...10 %, 24...250 V DC tolerance: - 20...10 %
electromagnetic compatibility fast transient bursts: (immunity tests-conducted disturbances), 4kV, 2.5 kHz, conforming to ANSI C37.90.1, fast transient bursts: (immunity tests-conducted disturbances), IV, 4kV, 2.5 kHz, conforming to IEC 61000-4-4, immunity to magnetic fields at network frequency: (immunity tests-radiated disturbances), IV, 30 A/m (continuous)-300 A/m (13 s), conforming to IEC 61000-4-8, immunity to radiated fields: (immunity tests-radiated disturbances), 10 V/m, 80 MHz...1 GHz, conforming to IEC 60255-22-3, immunity to radiated fields: (immunity tests-radiated disturbances), III, 10 V/m, 80 MHz...2 GHz, conforming to IEC 61000-4-3, conducted disturbance emission: (emission tests), conforming to IEC 60255-25, disturbing field emission: (emission tests), conforming to IEC 60255-25, disturbing field emission: (emission tests), A, conforming to EN 55022, electrostatic discharge: (immunity tests-radiated disturbances), 8 kV air, 4 kV contact, conforming to ANSI C37.90.3, electrostatic discharge: (immunity tests-radiated disturbances), 8 kV air, 6 kV contact, conforming to IEC 60255-22-2, 1 MHz damped oscillating wave: (immunity tests-conducted disturbances), 2.5 kV MC and MD, conforming to ANSI C37.90.1, fast transient bursts: (immunity tests-conducted disturbances), A or B, 4kV, 2.5 kHz/2 kV, 5 kHz, conforming to IEC 60255-22-4, immunity to conducted RF disturbances: (immunity tests-conducted disturbances), 10 V, conforming to IEC 60255-22-6, immunity to radiated fields: (immunity tests-radiated disturbances), 35 V/m, 25 MHz...1 GHz, conforming to ANSI C37.90.2 (1995), surges: (immunity tests-conducted disturbances), III, 2 kV MC, 1 kV MD, conforming to IEC 61000-4-5, voltage interruptions: (immunity tests-conducted disturbances), 100 %, 10 ms, conforming to IEC 60255-11, 1 MHz damped oscillating wave: (immunity tests-conducted disturbances), III, 2.5 kV MC, 1 kV MD, conforming to IEC 60255-22-1, 100 kHz damped oscillating wave: (immunity tests-conducted disturbances), 2.5 kV MC, 1 kV MD, conforming to IEC 61000-4-12, conducted disturbance emission: (emission tests), B, conforming to EN 55022
height 127 mm
mounting support symmetrical DIN rail
width 171 mm
depth 58 mm
local signalling green LED1 for energized (front face), red LED1 off for de-energized (front face), red LED1 remains ON for fault (front face), green LED2 for communication status ok (front face), green LED4 flashing for port 2 Ethernet sending data and receiving data (front face), green LED6 flashing for port 1 Ethernet sending data and receiving data (front face), red LED1 flashing for not set up or not base-unit connected (front face), green LED3 for port 2 Ethernet 100 Mbit/s (front face), green LED5 for port 1 Ethernet 100 Mbit/s (front face)
communication port protocol ARP network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX, FTP network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX, HTTP network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX, IEC 61850 network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX, Modbus RTU network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX, Modbus TCP/IP network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX, RSTP 801.1d 2004 network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX, SNMP network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX, SNTP network: S-LAN and E-LAN interface: 2 Ethernet ports 100BASE-FX
climatic withstand influence of corrosion/gaz test 4 (in operation) : 21 days, 75 % RH, 25 °C, 0.01 ppm H2S, 0.2 ppm S02, 0.02 ppm NO2, 0.01 ppm Cl2 conforming to IEC 60068-2-60, temperature variation with specified variation rate (in operation) : Nb: - 25 °C to 70 °C (- 13 °F to 158 °F) 5 °C/min (41 °F/min) conforming to IEC 60068-2-14, continuous exposure to damp heat (in operation) : Ca: 10 days, 93 % RH, 40 °C (104 °F) conforming to IEC 60068-2-3, continuous exposure to damp heat (in storage) : Ca: 56 days, 93 % RH, 40 °C (104 °F) conforming to IEC 60068-2-3, exposure to cold (in operation) : Ab: - 25 °C (- 13 °F) conforming to IEC 60068-2-1, exposure to cold (in storage) : Ab: - 25 °C (- 13 °F) conforming to IEC 60068-2-1, exposure to dry heat (in operation) : Bb: 70 °C (158 °F) conforming to IEC 60068-2-2, exposure to dry heat (in storage) : Bb: 70 °C (158 °F) conforming to IEC 60068-2-2, influence of corrosion/gaz test 2 (in operation) : C: 21 days, 75 % RH, 25 °C (- 13 °F), 0.5 ppm H2S, 1 ppm S02 conforming to IEC 60068-2-60, salt mist (in operation) : Kb/2 conforming to IEC 60068-2-52
optic fiber type multi mode wavelength: 1300 nm connector(s): SC
optic fiber length 2000 m diameter: 50/125 µm optical power (dBm) -14, 2000 m diameter: 62.5/125 µm optical power (dBm) -14