Schneider Electric        
    
    
        
            
    
TeSys D contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 32 A - 220 V AC coil - LC1D188M7
            Out of stock
        
    
            SKU
        
LC1D188M7
                        Details
                    
                    
TeSys D contactor, 4 poles (2NO+2NC), for non-inductive load applications up to 32A/690V AC-1.
It provides a 220V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals.
For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability.
Compact (45mm width), DIN-rail mounting or screw fixing.
Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
                        More Information
                    
                        | Attribute | Value | 
|---|---|
| SKU | LC1D188M7 | 
| product certifications | CCC, LROS (Lloyds register of shipping), BV, GL, RINA, GOST, CSA, DNV, UL | 
| ambient air temperature for storage | -60-80 °C | 
| overvoltage category | III | 
| pollution degree | 3 | 
| ambient air temperature for operation | -40-60 °C, 60-70 °C with derating | 
| non-overlap time | 1.5 ms on de-energisation between NC and NO contact, 1.5 ms on energisation between NC and NO contact | 
| [Icw] rated short-time withstand current | 100 A - 1 s for signalling circuit, 120 A - 500 ms for signalling circuit, 140 A - 100 ms for signalling circuit, 145 A 40 °C - 10 s for power circuit, 240 A 40 °C - 1 s for power circuit, 40 A 40 °C - 10 min for power circuit, 84 A 40 °C - 1 min for power circuit | 
| range of product | TeSys D | 
| product or component type | Kontaktor | 
| net weight | 0.425 kg | 
| standards | CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508 | 
| mechanical durability | 15 Mcycles | 
| device short name | LC1D | 
| range | TeSys D | 
| average impedance | 2.5 mOhm - Ith 32 A 50 Hz for power circuit | 
| [Ie] rated operational current | 32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit | 
| [Uc] control circuit voltage | 220 V AC 50/60 Hz | 
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 | 
| product name | TeSys D | 
| minimum switching current | 5 mA for signalling circuit | 
| mechanical robustness | vibrations contactor open: 2 Gn, 5...300 Hz, vibrations contactor closed: 4 Gn, 5...300 Hz, shocks contactor closed: 15 Gn for 11 ms, shocks contactor open: 10 Gn for 11 ms | 
| power dissipation per pole | 2.5 W AC-1 | 
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit, 32 A (at 60 °C) for power circuit | 
| control circuit type | AC at 50/60 Hz | 
| safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 | 
| contactor application | resistive load | 
| insulation resistance | > 10 MOhm for signalling circuit | 
| rated breaking capacity | 300 A at 440 V for power circuit conforming to IEC 60947 | 
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1, 250 A DC for signalling circuit conforming to IEC 60947-5-1, 300 A at 440 V for power circuit conforming to IEC 60947 | 
| pole contact composition | 2 NO + 2 NC | 
| auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1, type mirror contact 1 NC conforming to IEC 60947-4-1 | 
| operating time | 12...22 ms closing, 4...19 ms opening | 
| protective cover | with | 
| hold-in power consumption in VA | 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C), 7-7 VA 50 Hz cos phi 0.3 (at 20 °C) | 
| inrush power in VA | 70-70 VA 60 Hz cos phi 0.75 (at 20 °C), 70-70 VA 50 Hz cos phi 0.75 (at 20 °C) | 
| connections - terminals | control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end, control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end, control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end, control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end, control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end, control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end, power circuit: connector 1 cable(s) 2.5-10 mm²flexible without cable end, power circuit: connector 2 cable(s) 2.5-10 mm²flexible without cable end, power circuit: connector 1 cable(s) 2.5-10 mm²flexible with cable end, power circuit: connector 2 cable(s) 2.5-10 mm²flexible with cable end, power circuit: connector 1 cable(s) 2.5-16 mm²solid without cable end, power circuit: connector 2 cable(s) 2.5-16 mm²solid without cable end | 
| height | 105 mm | 
| mounting support | plate, rail | 
| compatibility code | LC1D | 
| width | 45 mm | 
| depth | 99 mm | 
| operating altitude | 0...3000 m | 
| IP degree of protection | IP20 front face conforming to IEC 60529 | 
| poles description | 4P | 
| tightening torque | control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm, control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2, power circuit: 1.7 N.m - on connector - with screwdriver flat Ø 6 mm, power circuit: 1.7 N.m - on connector - with screwdriver Philips No 2 | 
| electrical durability | 1 Mcycles 32 A AC-1 at Ue <= 440 V | 
| [Ue] rated operational voltage | power circuit: <= 690 V AC 25...400 Hz, power circuit: <= 300 V DC | 
| utilisation category | AC-1 | 
| [Ui] rated insulation voltage | power circuit: 690 V conforming to IEC 60947-4-1, power circuit: 600 V CSA certified, power circuit: 600 V UL certified, signalling circuit: 690 V conforming to IEC 60947-1, signalling circuit: 600 V CSA certified, signalling circuit: 600 V UL certified | 
| auxiliary contact composition | 1 NO + 1 NC | 
| control circuit voltage limits | 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz, 0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz, 0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz, 1...1.1 Uc (60-70 °C):operational AC 50/60 Hz | 
| contact compatibility | M6 | 
| associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1, 50 A gG at <= 690 V coordination type 1 for power circuit, 35 A gG at <= 690 V coordination type 2 for power circuit | 
| coil technology | without built-in suppressor module | 
| flame retardance | V1 conforming to UL 94 | 
| minimum switching voltage | 17 V for signalling circuit | 
| maximum operating rate | 3600 cyc/h 60 °C | 
| signalling circuit frequency | 25...400 Hz | 
| protective treatment | TH conforming to IEC 60068-2-30 | 
| fire resistance | 850 °C conforming to IEC 60695-2-1 | 
| heat dissipation | 2-3 W at 50/60 Hz | 
                        Technical Documents
                    
                    
    
                