Schneider Electric

TeSys D contactor - 4P(4 NO) - AC-1 - <= 440 V 125 A - 220 V AC 50/60 Hz coil - LC1D80004M7

Out of stock
SKU
LC1D80004M7
38%
Special Price Rp 3.988.119 Regular Price Rp 6.432.450
Details

TeSys D contactor, 4-pole (4NO), for non-inductive load applications up to 125A/1000V AC-1.

It provides a 220V 50/60Hz AC coil, power connection by screw terminals, control connection by screw clamp terminals.

For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability.

Compact (96mm width), DIN-rail mounting or screw fixing.

Without build-in auxiliary contacts, side and front mounting auxiliary contact blocks available (to be ordered separately).

Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

More Information
More Information
Attribute Value
SKU LC1D80004M7
product certifications CCC, LROS (Lloyds register of shipping), BV, GL, RINA, GOST, CSA, DNV, UL
ambient air temperature for storage -60-80 °C
overvoltage category III
pollution degree 3
ambient air temperature for operation -40-60 °C, 60-70 °C with derating
[Icw] rated short-time withstand current 640 A 40 °C - 10 s for power circuit, 990 A 40 °C - 1 s for power circuit, 135 A 40 °C - 10 min for power circuit, 320 A 40 °C - 1 min for power circuit
range of product TeSys D
product or component type Kontaktor
net weight 1.76 kg
standards CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
mechanical durability 4 Mcycles
device short name LC1D
range TeSys D
average impedance 0.8 mOhm - Ith 125 A 50 Hz for power circuit
[Ie] rated operational current 125 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage 220 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947
product name TeSys D
mechanical robustness vibrations contactor open: 2 Gn, 5...300 Hz, shocks contactor open: 8 Gn for 11 ms, vibrations contactor closed: 3 Gn, 5...300 Hz, shocks contactor closed: 10 Gn for 11 ms
power dissipation per pole 12.5 W AC-1
[Ith] conventional free air thermal current 125 A (at 60 °C) for power circuit
control circuit type AC at 50/60 Hz
safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
contactor application resistive load
rated breaking capacity 1100 A at 440 V for power circuit conforming to IEC 60947
Irms rated making capacity 1100 A at 440 V for power circuit conforming to IEC 60947
pole contact composition 4 NO
operating time 6...20 ms opening, 20...35 ms closing
protective cover without
hold-in power consumption in VA 26-26 VA 60 Hz cos phi 0.3 (at 20 °C), 26-26 VA 50 Hz cos phi 0.3 (at 20 °C)
inrush power in VA 245-245 VA 60 Hz cos phi 0.75 (at 20 °C), 245-245 VA 50 Hz cos phi 0.75 (at 20 °C)
connections - terminals control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end, control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end, control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end, control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end, control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end, control circuit: screw clamp terminals 1 cable(s) 1-2.5 mm²flexible with cable end, power circuit: connector 1 cable(s) 4-50 mm²flexible without cable end, power circuit: connector 2 cable(s) 4-25 mm²flexible without cable end, power circuit: connector 1 cable(s) 4-50 mm²flexible with cable end, power circuit: connector 2 cable(s) 4-16 mm²flexible with cable end, power circuit: connector 1 cable(s) 4-50 mm²solid without cable end, power circuit: connector 2 cable(s) 4-25 mm²solid without cable end
height 127 mm
mounting support plate, rail
compatibility code LC1D
width 96 mm
depth 125 mm
operating altitude 0...3000 m
IP degree of protection IP20 front face conforming to IEC 60529
poles description 4P
tightening torque control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm, control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2, power circuit: 12 N.m - on connector hexagonal screw head 4 mm, power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm
electrical durability 0.8 Mcycles 125 A AC-1 at Ue <= 440 V
[Ue] rated operational voltage power circuit: <= 300 V DC 25...400 Hz, power circuit: <= 690 V AC
utilisation category AC-1
[Ui] rated insulation voltage power circuit: 600 V CSA certified, power circuit: 600 V UL certified, power circuit: 1000 V conforming to IEC 60947-4-1
control circuit voltage limits 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz, 0.85...1.1 Uc (-40-55 °C):operational AC 60 Hz, 0.8...1.1 Uc (-40-55 °C):operational AC 50 Hz, 1...1.1 Uc (55-70 °C):operational AC 50/60 Hz
contact compatibility M1
associated fuse rating 200 A gG at <= 690 V coordination type 1 for power circuit, 160 A gG at <= 690 V coordination type 2 for power circuit
coil technology without built-in suppressor module
flame retardance V1 conforming to UL 94
maximum operating rate 3600 cyc/h 60 °C
protective treatment TH conforming to IEC 60068-2-30
fire resistance 850 °C conforming to IEC 60695-2-1
heat dissipation 6-10 W at 50/60 Hz
PT. Telesindo Citra Sejahtera © 2025 All Rights Reserved.