Schneider Electric

TeSys D control relay - 3 NO + 2 NC - <= 690 V - 24 V DC standard coil - CAD32BD

Out of stock
SKU
CAD32BD
38%
Special Price Rp 549.872 Regular Price Rp 886.890
Details

TeSys D control relay, 5 contacts (3NO + 2NC), 10A/690V, for control of electromagnetic loads AC-15/DC-13.

It provides a 24V DC control circuit with no inrush consumption and equipped with a surge suppression device, connection by screw clamp terminals.

For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability.

Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw.

Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium product (RoHS/REACh).

More Information
More Information
Attribute Value
SKU CAD32BD
product certifications CSA, UL
ambient air temperature for storage -60-80 °C
ambient air temperature for operation -40-60 °C, 60-70 °C with derating
non-overlap time 1.5 ms on de-energisation between NC and NO contact, 1.5 ms on energisation between NC and NO contact
[Icw] rated short-time withstand current 100 A - 1 s, 120 A - 500 ms, 140 A - 100 ms
range of product TeSys D control relay
product or component type Relay Kontrol
net weight 0.58 kg
standards IEC 60947-5-1, NF C 63-140, VDE 0660, EN 60947-5, BS 4794
mechanical durability 30 Mcycles
device short name CAD
range TeSys D
[Uc] control circuit voltage 24 V DC
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
product name TeSys CAD
minimum switching current 5 mA
mechanical robustness shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27, shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27, vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6, vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
[Ith] conventional free air thermal current 10 A (at 60 °C)
control circuit type DC standard
contactor application control circuit
insulation resistance > 10 MOhm
Irms rated making capacity 140 A AC conforming to IEC 60947-5-1, 250 A DC conforming to IEC 60947-5-1
pole contact composition 3 NO + 2 NC
time constant 28 ms
operating time 15...25 ms coil de-energisation and NC closing, 53...72 ms coil energisation and NO closing, 16...24 ms coil de-energisation and NO opening, 47...63 ms coil energisation and NC opening
connections - terminals screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end, screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end, screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end, screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end, screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end, screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
height 77 mm
mounting support plate, rail
compatibility code CAD
width 45 mm
depth 93 mm
operating altitude 0...3000 m
IP degree of protection IP2x front face conforming to VDE 0106
tightening torque 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2, 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
[Ue] rated operational voltage <= 690 V AC 25...400 Hz
utilisation category AC-15, DC-13, AC-14
[Ui] rated insulation voltage 690 V conforming to IEC 60947-5-1, 600 V UL certified, 600 V CSA certified
control circuit voltage limits 0.1...0.25 Uc (-40-70 °C):drop-out DC, 0.7...1.25 Uc (-40-60 °C):operational DC, 1...1.25 Uc (60-70 °C):operational DC
hold-in power consumption in W 5.4-5.4 W at 20 °C
associated fuse rating 10 A gG conforming to IEC 60947-5-1
minimum switching voltage 17 V
maximum operating rate 180 cyc/mn
protective treatment TH conforming to IEC 60068
inrush power in W 5.4-5.4 W (at 20 °C)
PT. Telesindo Citra Sejahtera © 2025 All Rights Reserved.