TeSys D control relay, 5 contacts (5NO), 10A/690V, for control of electromagnetic loads AC-15/DC-13.
It provides a 24V DC control circuit with no inrush consumption and equipped with a surge suppression device, connection by screw clamp terminals.
For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability.
Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw.
Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium product (RoHS/REACh).
More Information
Attribute | Value |
---|---|
SKU | CAD50BD |
product certifications | CSA, UL |
ambient air temperature for storage | -60-80 °C |
ambient air temperature for operation | -40-60 °C, 60-70 °C with derating |
non-overlap time | 1.5 ms on de-energisation between NC and NO contact, 1.5 ms on energisation between NC and NO contact |
[Icw] rated short-time withstand current | 100 A - 1 s, 120 A - 500 ms, 140 A - 100 ms |
range of product | TeSys D control relay |
product or component type | Relay Kontrol |
net weight | 0.58 kg |
standards | IEC 60947-5-1, NF C 63-140, VDE 0660, EN 60947-5, BS 4794 |
mechanical durability | 30 Mcycles |
device short name | CAD |
range | TeSys D |
[Uc] control circuit voltage | 24 V DC |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
product name | TeSys CAD |
minimum switching current | 5 mA |
mechanical robustness | shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27, shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27, vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6, vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
[Ith] conventional free air thermal current | 10 A (at 60 °C) |
control circuit type | DC standard |
contactor application | control circuit |
insulation resistance | > 10 MOhm |
Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1, 250 A DC conforming to IEC 60947-5-1 |
pole contact composition | 5 NO |
time constant | 28 ms |
operating time | 53...72 ms coil energisation and NO closing, 16...24 ms coil de-energisation and NO opening |
connections - terminals | screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end, screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end, screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end, screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end, screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end, screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end |
height | 77 mm |
mounting support | plate, rail |
compatibility code | CAD |
width | 45 mm |
depth | 93 mm |
operating altitude | 0...3000 m |
IP degree of protection | IP2x front face conforming to VDE 0106 |
tightening torque | 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2, 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm |
[Ue] rated operational voltage | <= 690 V AC 25...400 Hz |
utilisation category | AC-15, DC-13, AC-14 |
[Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1, 600 V UL certified, 600 V CSA certified |
control circuit voltage limits | 0.1...0.25 Uc (-40-70 °C):drop-out DC, 0.7...1.25 Uc (-40-60 °C):operational DC, 1...1.25 Uc (60-70 °C):operational DC |
hold-in power consumption in W | 5.4-5.4 W at 20 °C |
associated fuse rating | 10 A gG conforming to IEC 60947-5-1 |
minimum switching voltage | 17 V |
maximum operating rate | 180 cyc/mn |
protective treatment | TH conforming to IEC 60068 |
inrush power in W | 5.4-5.4 W (at 20 °C) |