TeSys F contactor - 3P(3 NO) - AC-3 - <= 440 V 630 A - without coil - LC1F630

Out of stock
SKU
LC1F630
75%
Special Price Rp 14.614.815 Regular Price Rp 58.459.260
Details

TeSys F contactor, 3 poles (3NO), 630A/1000V AC-3, for motor applications up to 250kW@400V.

Contactor with no coil to allow a later selection and installation (coil to be ordered separately), it provides bolt terminals for bars or cables with lugs.

For high operating rates until 1200 cycles/hour and environments until 55°C, it procures high reliability and durability.

It makes installation and maintenance easy thanks to a drawer for insertion of the selected coil and a large choice of add-on blocks and accessories (to be ordered separately).

Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

More Information
More Information
Attribute Value
SKU LC1F630
product certifications LROS (Lloyds register of shipping), BV, RINA, CSA, DNV, UL, ABS, CB, RMRoS
ambient air temperature for storage -60-80 °C
overvoltage category III
ambient air temperature for operation -5-55 °C
[Icw] rated short-time withstand current 5050 A 40 °C - 10 s, 4400 A 40 °C - 30 s, 3400 A 40 °C - 1 min, 2200 A 40 °C - 3 min, 1600 A 40 °C - 10 min
range of product TeSys F
product or component type Kontaktor
net weight 18.6 kg
standards EN 60947-4-1, IEC 60947-4-1, IEC 60947-1, JIS C8201-4-1, EN 60947-1
mechanical durability 5 Mcycles
device short name LC1F
range TeSys F
average impedance 0.12 mOhm - Ith 1000 A 50 Hz
[Ie] rated operational current 1000 A (at <40 °C) at <= 440 V AC AC-1, 630 A (at <55 °C) at <= 440 V AC AC-3
[Uc] control circuit voltage 48...1000 V AC 40...400 Hz with LX1/LX9 coil, 48...440 V DC with LX4 coil
[Uimp] rated impulse withstand voltage 8 kV
product name TeSys F
mechanical robustness vibrations contactor open: 2 Gn, 5...300 Hz, vibrations contactor closed: 4 Gn, 5...300 Hz, shocks contactor open: 6 Gn for 1/2 sine wave (11 ms), shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms)
power dissipation per pole 48 W AC-3, 120 W AC-1
[Ith] conventional free air thermal current 1000 A (at 40 °C), 1250 A
contactor application motor control, resistive load
rated breaking capacity 5040 A conforming to IEC 60947-4-1
Irms rated making capacity 6300 A AC conforming to IEC 60947-4-1
pole contact composition 3 NO
operating time 40...80 ms closing for with LX1/LX9 coil, 100...200 ms opening for with LX1/LX9 coil, 60...70 ms closing for with LX4 coil, 40...50 ms opening for with LX4 coil
hold-in power consumption in VA 20-25 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil, 6.5-12.5 VA (at 20 °C)with LX4 coil
inrush power in VA 1500-1730 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil, 1420-1920 VA (at 20 °C)with LX4 coil
permissible ambient air temperature around the device -40-70 °C
connections - terminals control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end, control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end, control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²solid without cable end, power circuit: bar 2 cable(s) - busbar cross section: 60 x 5 mm, power circuit: bolted connection, control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible with cable end, control circuit: screw clamp terminals 1 cable(s) 1-4 mm², control circuit: screw clamp terminals 2 cable(s) 1-4 mm²
height 304 mm
mounting support plate
compatibility code LC1F
width 309 mm
depth 255 mm
operating altitude 3000 m without derating
IP degree of protection IP20 front face with shrouds conforming to IEC 60529, IP20 front face with shrouds conforming to VDE 0106
poles description 3P
tightening torque control circuit: 1.2 N.m, power circuit: 58 N.m
[Ue] rated operational voltage <= 1000 V AC 50/60 Hz, <= 460 V DC
utilisation category AC-4, AC-3, AC-1
[Ui] rated insulation voltage 1000 V conforming to IEC 60947-4-1, 1500 V conforming to VDE 0110 group C
control circuit voltage limits operational: 0.85...1.1 Uc N/A 40...400 Hz with LX1/LX9 coil, drop-out: 0.25...0.5 Uc N/A 40...400 Hz with LX1/LX9 coil, operational: 0.85...1.1 Uc N/A with LX4 coil, drop-out: 0.2...0.35 Uc N/A with LX4 coil
associated fuse rating 630 A aM at <= 440 V, 1000 A gG at <= 440 V
maximum operating rate 1200 cyc/h 55 °C
protective treatment TH
motor power kW 335 kW at 380...400 V AC 50/60 Hz (AC-3), 375 kW at 415 V AC 50/60 Hz (AC-3), 400 kW at 440 V AC 50/60 Hz (AC-3), 400 kW at 500 V AC 50/60 Hz (AC-3), 450 kW at 1000 V AC 50/60 Hz (AC-3), 200 kW at 220...240 V AC 50/60 Hz (AC-3), 450 kW at 660...690 V AC 50/60 Hz (AC-3), 100 kW at 400 V AC 50/60 Hz (AC-4)
heat dissipation 20-20 W