Schneider Electric
TeSys F contactor - 3P(3 NO) - AC-3 - <= 440 V 630 A - without coil - LC1F630
Out of stock
SKU
LC1F630
Details
TeSys F contactor, 3 poles (3NO), 630A/1000V AC-3, for motor applications up to 250kW@400V.
Contactor with no coil to allow a later selection and installation (coil to be ordered separately), it provides bolt terminals for bars or cables with lugs.
For high operating rates until 1200 cycles/hour and environments until 55°C, it procures high reliability and durability.
It makes installation and maintenance easy thanks to a drawer for insertion of the selected coil and a large choice of add-on blocks and accessories (to be ordered separately).
Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
More Information
Attribute | Value |
---|---|
SKU | LC1F630 |
product certifications | LROS (Lloyds register of shipping), BV, RINA, CSA, DNV, UL, ABS, CB, RMRoS |
ambient air temperature for storage | -60-80 °C |
overvoltage category | III |
ambient air temperature for operation | -5-55 °C |
[Icw] rated short-time withstand current | 5050 A 40 °C - 10 s, 4400 A 40 °C - 30 s, 3400 A 40 °C - 1 min, 2200 A 40 °C - 3 min, 1600 A 40 °C - 10 min |
range of product | TeSys F |
product or component type | Kontaktor |
net weight | 18.6 kg |
standards | EN 60947-4-1, IEC 60947-4-1, IEC 60947-1, JIS C8201-4-1, EN 60947-1 |
mechanical durability | 5 Mcycles |
device short name | LC1F |
range | TeSys F |
average impedance | 0.12 mOhm - Ith 1000 A 50 Hz |
[Ie] rated operational current | 1000 A (at <40 °C) at <= 440 V AC AC-1, 630 A (at <55 °C) at <= 440 V AC AC-3 |
[Uc] control circuit voltage | 48...1000 V AC 40...400 Hz with LX1/LX9 coil, 48...440 V DC with LX4 coil |
[Uimp] rated impulse withstand voltage | 8 kV |
product name | TeSys F |
mechanical robustness | vibrations contactor open: 2 Gn, 5...300 Hz, vibrations contactor closed: 4 Gn, 5...300 Hz, shocks contactor open: 6 Gn for 1/2 sine wave (11 ms), shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms) |
power dissipation per pole | 48 W AC-3, 120 W AC-1 |
[Ith] conventional free air thermal current | 1000 A (at 40 °C), 1250 A |
contactor application | motor control, resistive load |
rated breaking capacity | 5040 A conforming to IEC 60947-4-1 |
Irms rated making capacity | 6300 A AC conforming to IEC 60947-4-1 |
pole contact composition | 3 NO |
operating time | 40...80 ms closing for with LX1/LX9 coil, 100...200 ms opening for with LX1/LX9 coil, 60...70 ms closing for with LX4 coil, 40...50 ms opening for with LX4 coil |
hold-in power consumption in VA | 20-25 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil, 6.5-12.5 VA (at 20 °C)with LX4 coil |
inrush power in VA | 1500-1730 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil, 1420-1920 VA (at 20 °C)with LX4 coil |
permissible ambient air temperature around the device | -40-70 °C |
connections - terminals | control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end, control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end, control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²solid without cable end, power circuit: bar 2 cable(s) - busbar cross section: 60 x 5 mm, power circuit: bolted connection, control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible with cable end, control circuit: screw clamp terminals 1 cable(s) 1-4 mm², control circuit: screw clamp terminals 2 cable(s) 1-4 mm² |
height | 304 mm |
mounting support | plate |
compatibility code | LC1F |
width | 309 mm |
depth | 255 mm |
operating altitude | 3000 m without derating |
IP degree of protection | IP20 front face with shrouds conforming to IEC 60529, IP20 front face with shrouds conforming to VDE 0106 |
poles description | 3P |
tightening torque | control circuit: 1.2 N.m, power circuit: 58 N.m |
[Ue] rated operational voltage | <= 1000 V AC 50/60 Hz, <= 460 V DC |
utilisation category | AC-4, AC-3, AC-1 |
[Ui] rated insulation voltage | 1000 V conforming to IEC 60947-4-1, 1500 V conforming to VDE 0110 group C |
control circuit voltage limits | operational: 0.85...1.1 Uc N/A 40...400 Hz with LX1/LX9 coil, drop-out: 0.25...0.5 Uc N/A 40...400 Hz with LX1/LX9 coil, operational: 0.85...1.1 Uc N/A with LX4 coil, drop-out: 0.2...0.35 Uc N/A with LX4 coil |
associated fuse rating | 630 A aM at <= 440 V, 1000 A gG at <= 440 V |
maximum operating rate | 1200 cyc/h 55 °C |
protective treatment | TH |
motor power kW | 335 kW at 380...400 V AC 50/60 Hz (AC-3), 375 kW at 415 V AC 50/60 Hz (AC-3), 400 kW at 440 V AC 50/60 Hz (AC-3), 400 kW at 500 V AC 50/60 Hz (AC-3), 450 kW at 1000 V AC 50/60 Hz (AC-3), 200 kW at 220...240 V AC 50/60 Hz (AC-3), 450 kW at 660...690 V AC 50/60 Hz (AC-3), 100 kW at 400 V AC 50/60 Hz (AC-4) |
heat dissipation | 20-20 W |
Technical Documents