Schneider Electric
TeSys F contactor - 4P(4 NO) - AC-1 - <= 440 V 250 A - without coil - LC1F1504
Out of stock
SKU
LC1F1504
Details
TeSys F contactor, 4 poles (4NO), 250A/690V AC-1, for non-inductive load applications.
Contactor with no coil to allow a later selection and installation (coil to be ordered separately), it provides bolt terminals for bars or cables with lugs.
For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability.
It makes installation and maintenance easy thanks to a drawer for insertion of the selected coil and a large choice of add-on blocks and accessories (to be ordered separately).
Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
More Information
Attribute | Value |
---|---|
SKU | LC1F1504 |
product certifications | LROS (Lloyds register of shipping), BV, RINA, CSA, DNV, UL, ABS, CB, RMRoS |
ambient air temperature for storage | -60-80 °C |
overvoltage category | III |
ambient air temperature for operation | -40-60 °C |
[Icw] rated short-time withstand current | 1200 A 40 °C - 10 s, 700 A 40 °C - 30 s, 600 A 40 °C - 1 min, 450 A 40 °C - 3 min, 350 A 40 °C - 10 min |
range of product | TeSys F |
product or component type | Kontaktor |
net weight | 3.83 kg |
standards | EN 60947-4-1, IEC 60947-4-1, IEC 60947-1, JIS C8201-4-1, EN 60947-1 |
mechanical durability | 10 Mcycles |
device short name | LC1F |
range | TeSys F |
average impedance | 0.35 mOhm - Ith 250 A 50 Hz |
[Ie] rated operational current | 250 A (at <40 °C) at <= 440 V AC-1 |
[Uc] control circuit voltage | 24...460 V DC with LX4 coil, 100...250 V AC 50/60 Hz with LXE coil, 100...380 V DC with LXE coil, 24...575 V AC 40...400 Hz with LX1/LX9 coil |
[Uimp] rated impulse withstand voltage | 8 kV |
product name | TeSys F |
mechanical robustness | vibrations contactor open: 2 Gn, 5...300 Hz, shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms), vibrations contactor closed: 6 Gn, 5...300 Hz, shocks contactor open: 9 Gn for 1/2 sine wave (11 ms) |
power dissipation per pole | 22 W AC-1 |
[Ith] conventional free air thermal current | 250 A (at 40 °C) |
contactor application | resistive load |
rated breaking capacity | 1200 A conforming to IEC 60947-4-1 |
Irms rated making capacity | 1500 A conforming to IEC 60947-4-1 |
pole contact composition | 4 NO |
operating time | 40...80 ms closing for with LXE coil, 6...54 ms opening for with LXE coil, 35 ms closing for with LX1/LX9 coil, 130 ms opening for with LX1/LX9 coil, 30...40 ms closing for with LX4 coil, 30...50 ms opening for with LX4 coil |
hold-in power consumption in VA | 4.5-7.0 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil, 2.5-4.0 VA (at 20 °C)with LXE coil, 6.6-8.1 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil, 3.94-4.83 VA (at 20 °C)with LX4 coil |
inrush power in VA | 690-855 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil, 543-665 VA (at 20 °C)with LX4 coil, 280-310 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil, 270-320 VA (at 20 °C)with LXE coil |
permissible ambient air temperature around the device | 60-70 °C at Uc |
connections - terminals | control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end, control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end, control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²solid without cable end, power circuit: bolted connection, control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible with cable end, control circuit: screw clamp terminals 1 cable(s) 1-4 mm², control circuit: screw clamp terminals 2 cable(s) 1-4 mm², control circuit: screw clamp terminals 1.0 cable(s) 0.2-2.5 mm²flexible without cable end, control circuit: screw clamp terminals 1.0 cable(s) 0.25-2.5 mm²flexible with cable end, control circuit: screw clamp terminals 1.0 cable(s) 0.2-2.5 mm²solid without cable end, power circuit: lugs-ring terminals 1 cable(s) 120-120 mm² - busbar cross section: 25 x 3 mm, power circuit: connector 1 cable(s) 120-120 mm², power circuit: bar 2 cable(s) |
height | 170 mm |
mounting support | plate |
compatibility code | LC1F |
width | 200.5 mm |
depth | 171 mm |
operating altitude | 3000 m without derating |
IP degree of protection | IP2x front face with shrouds conforming to IEC 60529, IP2x front face with shrouds conforming to VDE 0106 |
poles description | 4P |
tightening torque | control circuit: 1.2 N.m, power circuit: 18 N.m, control circuit: 0.6 N.m |
[Ue] rated operational voltage | <= 690 V AC 50/60 Hz |
utilisation category | AC-1 |
[Ui] rated insulation voltage | 1000 V conforming to IEC 60947-4-1, 1500 V conforming to VDE 0110 group C |
control circuit voltage limits | operational: 0.85...1.1 Uc N/A 40...400 Hz with LX1/LX9 coil, operational: 0.85...1.1 Uc N/A with LX4 coil, drop-out: 0.15...0.2 Uc N/A with LX4 coil, operational: 85...275 V N/A 50/60 Hz with LXE coil, drop-out: 0...60 V N/A 50/60 Hz with LXE coil, operational: 85...418 V N/A with LXE coil, drop-out: 0...45 V N/A with LXE coil, drop-out: 0.2...0.55 Uc N/A 40...400 Hz with LX1/LX9 coil |
associated fuse rating | 250 A gG at <= 440 V |
maximum operating rate | 2400 cyc/h 55 °C |
protective treatment | TH |
heat dissipation | 2.2-2.5 W, 5.9-7.2 W |
Technical Documents