Schneider Electric
TeSys GV2 - Circuit breaker - magnetic - 10 A - screw clamp terminals - GV2L14
Out of stock
SKU
GV2L14
Details
TeSys GV motor circuit breaker, 3 poles (3P), 10A/690V, for 3-phase motor applications 3-4kW@400V.
It provides a magnetic protection with a tripping level at 13xIn, high breaking capacity Icu 100kA@400V.
Connection by screw clamp terminals.
Start-stop control by rotary handle guaranteed for 100 000 cycles AC-3.
To complete motor protection, use in association with a thermal overload relay LRD14 (to be ordered separately).
Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
More Information
Attribute | Value |
---|---|
SKU | GV2L14 |
product certifications | EAC, CCC, LROS (Lloyds register of shipping), BV, RINA, CSA, UL, IECEE CB Scheme, DNV-GL |
ambient air temperature for storage | -40-80 °C |
ambient air temperature for operation | -20-60 °C |
magnetic tripping current | 138-138 A |
range of product | TeSys GV2 |
operating position | any position |
product or component type | motor circuit breaker |
net weight | 0.33 kg |
standards | EN/IEC 60947-2, UL 60947-4-1, CSA C22.2 No 60947-4-1, EN/IEC 60947-4-1 |
mechanical durability | 100000 cycles |
device short name | GV2L |
breaking capacity | 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2, 4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
trip unit technology | magnetic |
range | TeSys GV |
IK degree of protection | IK04 |
product name | TeSys GV2 |
mechanical robustness | shocks: 30 Gn conforming to IEC 60068-2-27, vibrations: 5 Gn, 5...150 Hz conforming to IEC 60068-2-6 |
power dissipation per pole | 1.8 W |
direct connector | without |
network frequency | 50/60 Hz conforming to IEC 60947-2 |
connections - terminals | screw clamp terminals 2 cable(s) 1-6 mm² solid, screw clamp terminals 2 cable(s) 1.5-6 mm² flexible without cable end, screw clamp terminals 2 cable(s) 1-4 mm² flexible with cable end |
height | 89 mm |
compatibility code | GV2L |
width | 45 mm |
depth | 97 mm |
operating altitude | 0...2000 m |
IP degree of protection | IP20 conforming to IEC 60529 |
[In] rated current | 10 A |
network type | AC |
poles description | 3P |
tightening torque | 1.7 N.m on screw clamp terminals |
electrical durability | 100000 cycles for AC-3 at 415 V |
device application | motor |
control type | rotary knob |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
fixing mode | 35 mm symmetrical DIN rail: clipped, panel: screwed (with 2 x M4 screws) |
utilisation category | category A conforming to IEC 60947-2, AC-3 conforming to IEC 60947-4-1 |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
suitability for isolation | yes conforming to IEC 60947-1 |
maximum operating rate | 40 cyc/h |
protective treatment | TH |
fire resistance | 960 °C conforming to IEC 60695-2-1 |
motor power kW | 4-4 kW at 500 V AC 50/60 Hz, 3-3 kW at 400/415 V AC 50/60 Hz, 4-4 kW at 400/415 V AC 50/60 Hz, 5.5-5.5 kW at 690 V AC 50/60 Hz, 7.5-7.5 kW at 690 V AC 50/60 Hz |
rated duty | continuous conforming to IEC 60947-4-1 |
[Ics] rated service short-circuit breaking capacity | 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2, 75 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Technical Documents