TeSys GV motor circuit breaker, 3 poles (3P), 18A/690V, for 3-phase motor applications 7.5kW@400V.

It provides a thermal-magnetic protection with a thermal setting range 13-18A, magnetic tripping at 13xIn, high breaking capacity Icu 50kA@400V.

Connection by screw clamp terminals.

Start-stop control by rotary knob guaranteed for 100 000 cycles AC-3.

Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).

More Information
More Information
Attribute Value
SKU GV2P20
product certifications EAC, CCC, LROS (Lloyds register of shipping), BV, RINA, CSA, UL, ATEX, IECEE CB Scheme, DNV-GL
ambient air temperature for storage -40-80 °C
ambient air temperature for operation -20-60 °C
magnetic tripping current 223-223 A
range of product TeSys GV2
operating position any position
product or component type motor circuit breaker
standards EN/IEC 60947-2, UL 60947-4-1, CSA C22.2 No 60947-4-1, EN/IEC 60947-4-1
mechanical durability 100000 cycles
device short name GV2P
breaking capacity 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2, 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2, 4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
trip unit technology thermal-magnetic
range TeSys GV
IK degree of protection IK04
trip unit rating 13-18 A
product name TeSys GV2
power dissipation per pole 2.5 W
[Ith] conventional free air thermal current 18 A conforming to IEC 60947-4-1
direct connector without
network frequency 50/60 Hz conforming to IEC 60947-4-1
height 89 mm
compatibility code GV2P
width 45 mm
depth 97 mm
operating altitude 2000 m
IP degree of protection IP20 conforming to IEC 60529
[In] rated current 18 A
network type AC
poles description 3P
tightening torque 1.7 N.m on screw clamp terminals
electrical durability 100000 cycles for AC-3 at 440 V
device application motor
control type rotary knob
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
fixing mode 35 mm symmetrical DIN rail: clipped, panel: screwed (with 2 x M4 screws)
utilisation category category A conforming to IEC 60947-2, AC-3 conforming to IEC 60947-4-1
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
suitability for isolation yes conforming to IEC 60947-1
maximum operating rate 25 cyc/h
protective treatment TH
fire resistance 960 °C conforming to IEC 60695-2-1
motor power kW 9-9 kW at 500 V AC 50/60 Hz, 7.5-7.5 kW at 400/415 V AC 50/60 Hz, 15-15 kW at 690 V AC 50/60 Hz
phase failure sensitivity yes conforming to IEC 60947-4-1
rated duty continuous conforming to IEC 60947-4-1
[Ics] rated service short-circuit breaking capacity 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2, 75 % at 440 V AC 50/60 Hz conforming to IEC 60947-2, 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2, 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2