Schneider Electric

TeSys GV5 Motor circuit breaker, 3P, 150A, Icu 70kA, thermal magnetic - GV5P150H

Out of stock
SKU
GV5P150H
38%
Special Price Rp 7.322.448 Regular Price Rp 11.810.400
Details

TeSys GV motor circuit breaker, 3 poles (3P), 150A/690V, for protection of 3-phase motors 55-75kW@400V.

It provides thermal magnetic protection and additional protections, breaking capacity Icu 70kA, start-stop control by rotary handle, connection for bars or cables with lugs (direct connection of cables with additional connectors).

Thermal protection adjustable by dials with a setting current Ir in range 70-150A and a selectable tripping class 5, 10 or 20, magnetic protection at 15 In.

Additional protections with fixed pick-up include short time delay protection Isd at 13 Ir, phase unbalance and loss protection.

It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX).

Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

More Information
More Information
Attribute Value
SKU GV5P150H
product certifications IECEE CB Scheme, EAC (pending)
ambient air temperature for storage -55-85 °C
overvoltage category III
pollution degree 3
ambient air temperature for operation -25-70 °C
magnetic tripping current 2250-2250 A
range of product TeSys GV5
product or component type motor circuit breaker
net weight 2.4 kg
standards EN/IEC 60947-2, EN/IEC 60947-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, EN/IEC 60947-4-1
mechanical durability 40000 cycles
device short name GV5P
breaking capacity 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2, 70 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
trip unit technology electronic
range TeSys GV
IK degree of protection IK07 conforming to IEC 62262
trip unit name Micrologic 2.2 M
trip unit rating 150-150 A
breaking capacity code H 70 kA
product name TeSys GV5
mechanical robustness vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6, vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
power dissipation per pole 9.2 W
mounting position horizontal and vertical
connections - terminals power circuit: bars - busbar cross section: 25 x 6 mm, power circuit: lugs - external diameter: 25 mm
height 161 mm
width 105 mm
depth 155 mm
operating altitude 0...2000 m without derating
IP degree of protection IP40 conforming to IEC 60529
[In] rated current 150 A at 65 °C
poles description 3P
colour anthracite (RAL 7016)
tightening torque 15 N.m screw : M8
electrical durability 20000 cycles for AC-3 at 400/415 V In
device application motor protection
control type direct rotary handle
[Ue] rated operational voltage 690 V AC 50/60 Hz
local signalling LED ready, LED 95 % Ith
fixing mode by screws
protection type short-circuit protection, overload protection, phase loss, phase unbalance, instantaneous short-circuit protection
utilisation category category A conforming to IEC 60947-2
connection pitch 35 mm without spreaders
[Ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
suitability for isolation yes conforming to EN/IEC 60947-2
maximum operating rate 25 cyc/h
protective treatment TC
fire resistance 960 °C conforming to IEC 60695-2-1
motor power kW 55-75 kW at 400/415 V AC 50/60 Hz, 75-90 kW at 500 V AC 50/60 Hz, 90-110 kW at 660/690 V AC 50/60 Hz
thermal protection adjustment range 70-150 A adjustable 9 settings
phase failure sensitivity yes conforming to IEC 60947-4-1
[Isd] short-time pick-up adjustment range 5...13 x Ir adjustable 9 settings
rated duty continuous
thermal overload class class 5 conforming to IEC 60947-4-1, class 10 conforming to IEC 60947-4-1, class 20 conforming to IEC 60947-4-1
[Ics] rated service short-circuit breaking capacity 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
PT. Telesindo Citra Sejahtera © 2025 All Rights Reserved.