Schneider Electric

TeSys K contactor - 3P - AC-3 <= 440 V 9 A - 1 NC aux. - 24 V DC coil - LP1K0901BD

Out of stock
SKU
LP1K0901BD
38%
Special Price Rp 353.047 Regular Price Rp 569.430
Details

TeSys K contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3 (4kW@400V), and for non-inductive load control applications up to 20A/690V AC-1.

It provides a 24V DC coil, 1NC built-in auxiliary contact, connection by screw clamp terminals.

For operating rates until 600 cycles/hour and environments until 50°C, it procures reliability and durability to standard applications.

Very compact (45mm width), DIN-rail mounting or screw fixing.

Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).

More Information
More Information
Attribute Value
SKU LP1K0901BD
product certifications CSA, UL
ambient air temperature for storage -50-80 °C
overvoltage category III
ambient air temperature for operation -25-50 °C
range of product TeSys K
product or component type Kontaktor
net weight 0.225 kg
mechanical durability 10 Mcycles
device short name LP1K
range TeSys K
average impedance 3 mOhm - Ith 20 A 50 Hz for power circuit
[Ie] rated operational current 20 A (at <50 °C) at <= 440 V AC AC-1 for power circuit, 9 A at <= 440 V AC AC-3 for power circuit, 16 A (at <70 °C) at 690 V AC AC-1 for power circuit
[Uimp] rated impulse withstand voltage 8 kV
minimum switching current 5 mA for signalling circuit
[Ith] conventional free air thermal current 20 A (at 50 °C) for power circuit, 10 A (at 50 °C) for signalling circuit
safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
contactor application motor control, resistive load
insulation resistance > 10 MOhm for signalling circuit
rated breaking capacity 110 A at 440 V conforming to IEC 60947, 80 A at 500 V conforming to IEC 60947, 70 A at 660...690 V conforming to IEC 60947, 110 A at 415 V conforming to IEC 60947, 110 A at 220...230 V conforming to IEC 60947, 110 A at 380...400 V conforming to IEC 60947
Irms rated making capacity 110 A AC for signalling circuit conforming to IEC 60947, 110 A AC for power circuit conforming to NF C 63-110, 110 A AC for power circuit conforming to IEC 60947
pole contact composition 3 NO
auxiliary contacts type type instantaneous 1 NC
operating time 10 ms coil de-energisation and NO opening, 30...40 ms coil energisation and NO closing
height 58 mm
mounting support plate, rail
compatibility code LP1K
width 45 mm
depth 57 mm
operating altitude 2000 m without derating
poles description 3P
tightening torque 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm, 1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2
[Ue] rated operational voltage power circuit: 690 V AC 50/60 Hz, signalling circuit: <= 690 V AC 50/60 Hz
utilisation category AC-4, AC-3, AC-1
[Ui] rated insulation voltage power circuit: 690 V conforming to IEC 60947-4-1, power circuit: 600 V conforming to UL 508, signalling circuit: 690 V conforming to IEC 60947-4-1, signalling circuit: 690 V conforming to IEC 60947-5-1, signalling circuit: 600 V conforming to UL 508, power circuit: 600 V conforming to CSA C22.2 No 14, signalling circuit: 600 V conforming to CSA C22.2 No 14
auxiliary contact composition 1 NC
control circuit voltage limits operational: 0.8...1.15 Uc (at <50 °C), drop-out: 0.1...0.75 Uc (at <50 °C)
hold-in power consumption in W 3-3 W at 20 °C
associated fuse rating 25 A gG at <= 440 V for power circuit, 25 A aM for power circuit, 10 A gG for signalling circuit conforming to IEC 60947, 10 A gG for signalling circuit conforming to VDE 0660
flame retardance V1 conforming to UL 94, requirement 2 conforming to NF F 16-101, requirement 2 conforming to NF F 16-102
minimum switching voltage 17 V for signalling circuit
maximum operating rate 3600 cyc/h
inrush power in W 3-3 W (at 20 °C)