TeSys LRD thermal overload relays - 95...120 A - class 10A - LRD4367
TeSys LRD thermal overload relay, 120A/1000V, thermal setting range 95-120A, tripping class 10A, for protection of 3-phase motors 55kW@400V.
Differential device with phase failure and load unbalance detection.
It provides a thermal adjustement dial, a manual-automatic reset selector acting also as reset button, a trip test button for simulation of a tripping, a stop button, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling.
Settings are protected by a transparent cover lockable by sealing.
Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D115-D150.
Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LA7D3064 (to be ordered separately).
Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine), Green Premium compliant (RoHs/Reach).
Attribute | Value |
---|---|
SKU | LRD4367 |
product certifications | EAC, CCC, IEC, CSA, UL, ATEX INERIS |
ambient air temperature for storage | -60-70 °C |
ambient air temperature for operation | -20-60 °C without derating conforming to IEC 60947-4-1 |
product or component type | Relay Beban Lebih Termal |
net weight | 0.9 kg |
standards | EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, EN/IEC 60947-4-1, UL 60947-5-1, CSA C22.2 No 60947-5-1, GB/T 14048.4, GB/T 14048.5, EN 50495 |
device short name | LRD |
range | TeSys LR |
product compatibility | LC1D115, LC1D150 |
product name | TeSys LRD |
mechanical robustness | vibrations: 6 Gn conforming to IEC 60068-2-6, shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7 |
[Ith] conventional free air thermal current | 5 A for signalling circuit |
relay application | motor protection |
permissible current | 0.06 A at 440 V DC-13 for signalling circuit, 0.12 A at 600 V AC-15 for signalling circuit |
tripping threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
network frequency | 0...400 Hz |
connections - terminals | control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² flexible without cable end, control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² flexible with cable end, control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² solid without cable end, power circuit: screw clamp terminals 1 cable(s) 4-35 mm² flexible with cable end, power circuit: screw clamp terminals 1 cable(s) 4-50 mm² flexible without cable end, power circuit: screw clamp terminals 1 cable(s) 4-50 mm² solid without cable end |
mounting support | plate, with specific accessories, rail, with specific accessories, under contactor |
compatibility code | LRD |
depth | 132 mm |
dielectric strength | 2.2 kV at 50 Hz conforming to IEC 60947-1 |
IP degree of protection | IP20 conforming to IEC 60529 |
network type | AC, DC |
tightening torque | control circuit: 1.7 N.m - on screw clamp terminals, power circuit: 9 N.m - on screw clamp terminals |
control type | red push-button: stop, blue push-button: reset |
[Ue] rated operational voltage | 1000 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 |
[Ui] rated insulation voltage | power circuit: 1000 V conforming to IEC 60947-4-1, power circuit: 600 V conforming to CSA, power circuit: 600 V conforming to UL |
auxiliary contact composition | 1 NO + 1 NC |
associated fuse rating | 4 A gG for signalling circuit, 4 A BS for signalling circuit |
flame retardance | V1 conforming to UL 94 |
protective treatment | TH conforming to IEC 60068 |
thermal protection adjustment range | 95-120 A |
phase failure sensitivity | tripping current 130 % of Ir on two phase, the last one at 0 |
thermal overload class | class 10A conforming to IEC 60947-4-1 |
temperature compensation | -20-60 °C |