TeSys LT47 electronic over current relays - manual - 5...60 A - 100...120 V AC - LT4760F7S
TeSys LR47 electronic overcurrent relay, 60A/690V, with manual reset, to be supplied with 100-120V AC, for protection of motors with a rated current 5-50A.
It provides 3 dials to adjust the protection, LOAD (5-60A) for the overcurrent level, O-TIME (0.3-10sec) for the acceptable duration of the overcurrent, D-TIME (0.5-30sec) for the starting duration.
In addition, the device trips when there is a missing phase during more than O-TIME.
The device has a reset button, a test/stop button, 2 LED indicators (Run/Trip), 2 auxiliary contacts 1NO+1NC for fault signalling.
Settings can be locked by sealing the transparent cover.
DIN rail mounting, without power terminals (currents monitored by 2 current transformers crossed by the motor cables).
Multi standards certified (IEC, UL, CSA, CCC, EAC), it conforms to RoHS/REACh regulation.
Attribute | Value |
---|---|
SKU | LT4760F7S |
product certifications | CSA, UL |
ambient air temperature for storage | -30-80 °C |
ambient air temperature for operation | -25-60 °C without derating conforming to IEC 60947-4-1 |
time range | 0.5..30 s - control type D-time, 0.3...10 s - control type O-time |
range of product | TeSys LT electronic over current relays |
product or component type | Electronic Over Current Relay |
net weight | 0.192 kg |
standards | IEC 60947, IEC 60255-6 |
device short name | LT47 |
range | TeSys LT |
product name | TeSys LT |
mechanical robustness | shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7, vibrations: 4 gn conforming to IEC 60068-2-6 |
[Ith] conventional free air thermal current | 3 A for signalling circuit |
[Us] rated supply voltage | 100...120 V AC |
electromagnetic compatibility | resistance to electrostatic discharge: 8 kV in open air conforming to IEC 61000-4-2, resistance to electrostatic discharge: 6 kV in direct mode conforming to IEC 61000-4-2, conducted emission: class A conforming to EN 55011, immunity to electromagnetic interference: 10 V/m conforming to IEC 61000-4-3, immunity to fast transients: 2 kV conforming to IEC 61000-4-4, surge withstand: 6 kV conforming to IEC 61000-4-5, conducted HF disturbances: 10 V conforming to IEC 61000-4-6 |
relay application | sensitivity to phase failure, locked rotor, mechanical jamming I > 3 x Isetting, overload Imax > Isetting |
tripping threshold | 5...50 A |
network frequency | 50...60 Hz |
connections - terminals | signalling circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end, signalling circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible without cable end, signalling circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, signalling circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible without cable end |
height | 70.3 mm |
mounting support | rail |
compatibility code | LT47 |
width | 71 mm |
depth | 77.2 mm |
operating altitude | 2000 m |
dielectric strength | 2 kV at 50 Hz conforming to IEC 60255-5 |
IP degree of protection | IP20 conforming to IEC 60529, IP20 conforming to VDE 0106 |
tightening torque | signalling circuit: 1.7 N.m M3.5 |
device application | protection |
control type | push-button: reset, electrical: reset |
local signalling | 1 LED (green), 1 LED (red) |
[Ui] rated insulation voltage | power circuit: 600 V AC conforming to CSA, power circuit: 600 V AC conforming to UL, power circuit: 690 V AC conforming to IEC 60947-4-1 |
auxiliary contact composition | 1 NO + 1 NC |
associated fuse rating | 3 A gG for signalling circuit, 3 A BS for signalling circuit |
protective treatment | TH conforming to IEC 60068 |
thermal protection adjustment range | 5-60 A |