Schneider Electric

TeSys T Operator control unit for LTM R controller - LTMCU

Out of stock
SKU
LTMCU
38%
Special Price Rp 4.577.906 Regular Price Rp 7.383.720
Details

TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor.

It manages most critical processes while reducing downtime and increasing productivity as well as predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range.

This motor management system is also a flexible system that supports six communication protocols which are Modbus™, CANopen, DeviceNet™, Profibus™, Ethernet/IP, and Modbus/TCP.

TeSys T motor management system consist of several components which include the LTMR controller, the expansion module, HMI and software along with several accessories.

The LTMR controller is the main component of the system that manages the basic functions.

This includes the measurement of the ground current, motor temperature, three phase current of the motor, the controller also includes logic inputs and outputs which is used in fault management.

The expansion module is directly connected to the controller and provides additional inputs as well as measure the voltage between the phases which allow the controller the monitor additional functions.

TeSys T is highly reliable and has a very long product life thanks to a state-of-the-art component selection, to the all in one design and to the advanced electronic protection.

TeSys T can be integrated in many different types of harsh environment such as dusty atmospheres, marine applications, high vibration applications and corrosive atmospheres and is used in Metal/Mining/Mineral, Oil & Gas, Water Wastewater.

This is a TeSys operactor control unit that is used in conjuction with LTMR controller to configure the parameters, display the information about the controller, display detected faults and control the motor locally.

This operator unit has LCD screen to display the information along with 5 control keys and 4 LED indicators and has 2 ports for RJ45 connectors that are used to connect to the PC and controller.

The dimensions of this device are 70 mm (H) X 117 mm (W) X 50 mm (D) and it weighs 0.4 kg.

More Information
More Information
Attribute Value
SKU LTMCU
product certifications EAC, CSA, UL, CE, C-Tick, NOM
relative humidity 15-95 %
ambient air temperature for storage -40-80 °C
ambient air temperature for operation -20-60 °C
product or component type Kontaktor
net weight 0.4 kg
mounting mode flush-mounted
standards CSA C22.2 No 60947-4-1, EN/IEC 61131-2, UL 60947-4-1A
device short name LTMCU
range TeSys T
range compatibility LTMR motor controller
mechanical robustness shocks: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27, vibrations: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6
electromagnetic compatibility electrostatic discharge, level 3, 8 kV air, 4 kV contact, conforming to EN/IEC 61000-4-2, radiated RF fields, level 3, 10 V/m, conforming to EN/IEC 61000-4-3, conducted RF disturbances, level 3, 10 V, conforming to EN/IEC 61000-4-6, surges (shielded access), level 3, 2 kV, conforming to EN/IEC 61000-4-5, fast transient bursts (shielded access), level 3, 2 kV, conforming to EN/IEC 61000-4-4
device connection connection to a LTM R controller, RJ45 connector on rear, connection to a PC, RJ45 connector on front
control button type 10 push-button
height 70 mm
compatibility code LTMCU
width 117 mm
depth 50 mm
IP degree of protection IP54 (front) conforming to EN/IEC 60947-4-1, IP20 (rear) conforming to EN/IEC 60947-4-1
local signalling 4 LEDs
flame retardance V2 conforming to UL 94
protective treatment TC 12 humidity cycles at 55 °C conforming to EN/IEC 60068-2-30
fire resistance 650 °C conforming to EN/IEC 60947-1
display type backlit LCD
maximum supply current 140 mA
supply via the controller
power dissipation 1 W
PT. Telesindo Citra Sejahtera © 2025 All Rights Reserved.