TeSys U power base - 12 A - 24 V DC screw clamps control - LU2B12BL
TeSys U standard reversing power base, 3 poles (3NO), rated 12A/690V, to be completed with a control unit LUC to form a TeSys U reversing starter controller, for 3-phase motor applications up to 5.5kW@400V.
Base composed of power contacts, control coil, rotary handle, with a modular design for additional modules to form a "all in one" reversing starter controller with basic or advanced protection and control functions.
It is equipped with a reverser module LU2MB0BL to be supplied with 24V DC, auxiliary signaling contacts (1NO+1NC), a control terminal block, blanking shutters covering the empty cavities.
It provides a high breaking capacity Icu 50kA@400V, start-stop control guaranteed for 3600 cycles/hour.
Very compact (45mm width), DIN-rail mounting and screw fixing, with a padlockable rotary handle.
Certified when used in conjunction with a LUC control unit (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Attribute | Value |
---|---|
SKU | LU2B12BL |
product certifications | EAC, CCC, CSA, UL, CE, ATEX, ASEFA, Marine |
ambient air temperature for storage | -40-85 °C |
ambient air temperature for operation | -25-60 °C with LUCM, -25-70 °C with LUCA, LUCB, LUCC, LUCD |
resistance to electrostatic discharge | 8 kV level 3 in open air conforming to IEC 61000-4-2, 8 kV level 4 on contact conforming to IEC 61000-4-2 |
range of product | TeSys U |
product or component type | Motor Starter |
net weight | 1.27 kg |
standards | EN 60947-6-2, IEC 60947-6-2, UL 60947-4-1, with phase barrier, CSA C22.2 No 60947-4-1, with phase barrier |
mechanical durability | 15 Mcycles |
device short name | LU2B |
range | TeSys Ultra |
product compatibility | control unit LUC.X6BL, control unit LUC.1XBL, control unit LUC.05BL, control unit LUC.12BL |
[Ie] rated operational current | 12 A at <= 440 V, 12 A at 500 V, 9 A at 690 V |
[Uc] control circuit voltage | 24 V DC |
[Ics] rated service breaking capacity | 50 kA at 230 V, 50 kA at 440 V, 10 kA at 500 V, 4 kA at 690 V |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-6-2 |
product name | TeSys U |
[Ith] conventional free air thermal current | 12 A |
safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
auxiliary contacts type | type linked contacts (1 NO + 1 NC) conforming to IEC 60947-4-1, type mirror contact (1 NC) conforming to IEC 60947-1 |
operating time | 150 ms with change of direction for power circuit, 75 ms without change of direction for power circuit, 35 ms opening with LUCA, LUCB, LUCC, LUCD, LUCM for control circuit, 75 ms closing with LUCM for control circuit, 70 ms closing with LUCA, LUCB, LUCC, LUCD for control circuit |
immunity to microbreaks | 3 ms for control circuit |
resistance to radiated fields | 10 V/m 3 conforming to IEC 61000-4-3 |
typical current consumption | 120 mA at 24 V DC I maximum while closing, 120 mA at 24 V DC I rms sealed |
safe separation of circuit | 400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1 appendix N, 400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1 appendix N |
network frequency | 40...60 Hz |
connections - terminals | power circuit: screw clamp terminals 1 cable(s) 1-6 mm² flexible with cable end, control circuit: screw clamp terminals 1 cable(s) 0.34-1.5 mm² flexible with cable end, control circuit: screw clamp terminals 1 cable(s) 0.75-1.5 mm² flexible without cable end, control circuit: screw clamp terminals 1 cable(s) 0.75-1.5 mm² rigid, control circuit: screw clamp terminals 2 cable(s) 0.34-1.5 mm² flexible with cable end, control circuit: screw clamp terminals 2 cable(s) 0.75-1.5 mm² flexible without cable end, control circuit: screw clamp terminals 2 cable(s) 0.75-1.5 mm² rigid, power circuit: screw clamp terminals 1 cable(s) 1-10 mm² rigid, power circuit: screw clamp terminals 1 cable(s) 2.5-10 mm² flexible without cable end, power circuit: screw clamp terminals 2 cable(s) 1-6 mm² flexible with cable end, power circuit: screw clamp terminals 2 cable(s) 1-6 mm² rigid, power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm² flexible without cable end |
height | 224 mm |
compatibility code | LU2B |
width | 45 mm |
depth | 126 mm |
vibration resistance | 2 gn (f= 5-300 Hz) power poles open conforming to IEC 60068-2-27, 4 gn (f= 5-300 Hz) power poles closed conforming to IEC 60068-2-27 |
operating altitude | 2000 m |
IP degree of protection | IP20 conforming to IEC 60947-1 (front panel and wired terminals), IP20 conforming to IEC 60947-1 (other faces), IP40 conforming to IEC 60947-1 (front panel outside connection zone) |
poles description | 3P |
tightening torque | control circuit: 0.8-1.2 N.m flat screwdriver 5 mm, control circuit: 0.8-1.2 N.m Philips no 1 screwdriver 5 mm, power circuit: 1.9-2.5 N.m flat screwdriver 6 mm, power circuit: 1.9-2.5 N.m Philips No 2 screwdriver 6 mm |
device application | motor protection, motor control |
[Ue] rated operational voltage | 690 V AC for power circuit |
fixing mode | clipped (DIN rail), screw-fixed (plate) |
utilisation category | AC-43, AC-44, AC-41 |
[Ui] rated insulation voltage | 600 V conforming to UL 60947-4-1, 600 V conforming to CSA C22.2 No 60947-4-1, 690 V conforming to IEC 60947-6-2 (pollution degree 3) |
suitability for isolation | yes |
auxiliary contact composition | 1 NO + 1 NC |
control circuit voltage limits | 14.5 V DC drop-out, 20...27 V DC in operation |
maximum operating rate | 3600 cyc/h |
protective treatment | TH conforming to IEC 60068 |
fire resistance | 960 °C parts supporting live components conforming to IEC 60695-2-12, 650 °C conforming to IEC 60695-2-12 |
heat dissipation | 2-2 W for control circuit with LUCA, LUCB, LUCC, LUCD, 1.7-1.7 W for control circuit with LUCM |
shock resistance | 10 gn power poles open conforming to IEC 60068-2-27, 15 gn power poles closed conforming to IEC 60068-2-27 |
resistance to fast transients | 2 kV class 3 serial link conforming to IEC 61000-4-4, 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4 |
immunity to voltage dips | 70 % / 500 ms conforming to IEC 61000-4-11 |
immunity to radioelectric fields | 10 V conforming to IEC 61000-4-6 |
inrush restraint duration | 15 ms DC |