Zelio Logic analogue I/O extension module - 4 I O - 24 V DC - for Zelio Logic - SR3XT43BD
This product is part of the Zelio Logic range, an offer of smart relays for simple automation systems from 10 to 40 I/Os.
The analogue I/O extension module provides 2 input/outputs.
It is an extension module with an analogue output range of 0 to 10V and a maximum load current of 10mA for analogue output.
It provides 10bit on the input range and 10bit on the output range.
The temperature probe is Pt 100, 3-wire conforming to IEC 751.
It is furnished with screw terminal for electrical connections.
It is an IP20 and IP40 rated product.
It weighs 0.11kg.
This product meets EN/IEC 61000-4-12, EN/IEC 61000-4-5, EN/IEC 61000-4-3, EN/IEC 61000-4-4 level 3, EN/IEC 61000-4-6 level 3, EN/IEC 61000-4-2 level 3, EN/IEC 60068-2-6 Fc, EN/IEC 61000-4-11 and EN/IEC 60068-2-27 Ea standards.
Simple to select, install and program, Zelio Logic is suitable for all your applications.
Flexible, it offers you the choice of 2 ranges, compact or modular, extendable and 2 programming languages (FBD or LADDER).
Easy to use, Zelio Logic provides a real alternative to solutions based on cabled logic or specific cards.
Attribute | Value |
---|---|
SKU | SR3XT43BD |
product certifications | GOST, CSA, UL, C-Tick |
relative humidity | 95-95 % without condensation or dripping water |
ambient air temperature for storage | -40-70 °C |
pollution degree | 2 conforming to EN/IEC 61131-2 |
ambient air temperature for operation | -20-55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2, -20-40 °C conforming to IEC 60068-2-1 and IEC 60068-2-2 |
environmental characteristic | EMC directive conforming to EN/IEC 61000-6-2, EMC directive conforming to EN/IEC 61000-6-3, EMC directive conforming to EN/IEC 61000-6-4, EMC directive conforming to EN/IEC 61131-2 zone B, low voltage directive conforming to EN/IEC 61131-2 |
range of product | Zelio Logic |
product or component type | Relay & Power Supply |
net weight | 0.11 kg |
standards | EN/IEC 61000-4-12, EN/IEC 61000-4-4 level 3, EN/IEC 61000-4-6 level 3, EN/IEC 61000-4-3, EN/IEC 61000-4-2 level 3, EN/IEC 61000-4-5, EN/IEC 61000-4-11, EN/IEC 60068-2-6 Fc, EN/IEC 60068-2-27 Ea |
range | Smart Relay |
analogue input type | common mode |
short-circuit protection | with analogue output |
repeat accuracy | < +/- 0.3 °C, input range: - 25...125 °C at 25 °C for analogue input circuit, <= +/- 1 %, input range: 0...10 V at 25 °C for analogue input circuit, <= +/- 1 %, input range: 0...10 V at 55 °C for analogue output, <= +/- 1 %, input range: 0...20 mA at 25 °C for analogue input circuit |
analogue output number | 2 |
analogue input range | 0...10 V, 0...20 mA, -25...125 °C |
conversion error | +/- 1 % of the full scale value, input range: 0...10 V (25 °C) for analogue output, +/- 1 % of the full scale value, input range: 0...10 V (55 °C) for analogue output, +/- 1 %, input range: 0...10 V (25 °C) for analogue input circuit, +/- 1 %, input range: 0...10 V (55 °C) for analogue input circuit, +/- 1 %, input range: 0...20 mA (25 °C) for analogue input circuit, +/- 1 %, input range: 0...20 mA (55 °C) for analogue input circuit, +/- 1.5 °C, input range: - 25...125 °C (25 °C) for analogue input circuit, +/- 1.5 °C, input range: - 25...125 °C (55 °C) for analogue input circuit |
conversion time | smart relay cycle time for analogue input circuit, smart relay cycle time for analogue output |
operating distance | 10 m with screened cable for analogue input circuit, 10 m with screened cable for analogue output |
analogue input resolution | 10 bits on the input range |
reverse polarity protection | analogue input circuit: with |
maximum load current | 10 mA for analogue output |
analogue output range | 0...10 V |
connections - terminals | screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end, screw terminals, 2 x 0.25...2 x 0.75 mm² (AWG 24...AWG 18) flexible with cable end, screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) semi-solid, screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) solid, screw terminals, 2 x 0.25...2 x 1.5 mm² (AWG 23...AWG 16) solid |
operating altitude | 2000 m |
IP degree of protection | IP20 (terminal block) conforming to IEC 60529, IP40 (front panel) conforming to IEC 60529 |
tightening torque | 0.5 N.m |
load type | resistive load for analogue output |
analogue input number | 2 |
maximum permissible voltage | 30 V for analogue input circuit |
[Imp] maximum permanent current | 30 mA for analogue input circuit |
input impedance | 18 kOhm, input range: 0...10 V for analogue input circuit, 247 Ohm, input range: 0...20 mA for analogue input circuit |
disturbance radiated/conducted | class B conforming to EN 55022-11 group 1 |
maximum altitude transport | 3048 m |
LSB value | 0.15 °C, - 25...125 °C for analogue input circuit, 20 µA, 0...20 mA for analogue input circuit, 9.8 mV, 0...10 V for analogue input circuit, 9.8 mV, 0...10 V for analogue output |
analogue output resolution | 10 bits on the output range |
temperature probe type | Pt 100, 3-wire conforming to IEC 751 |