Schneider Electric

Zelio Logic compact smart relay - 20 I O - 12 VDC - clock - display - SR2B201JD

Out of stock
SKU
SR2B201JD
45%
Special Price Rp 2.398.655 Regular Price Rp 4.361.190
More Information
More Information
Attribute Value
SKU SR2B201JD
product certifications GL, GOST, CSA, UL, C-Tick
relative humidity 95-95 % without condensation or dripping water
ambient air temperature for storage -40-70 °C
overvoltage category III conforming to EN/IEC 60664-1
pollution degree 2 conforming to EN/IEC 61131-2
ambient air temperature for operation -20-40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2, -20-55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2
environmental characteristic EMC directive conforming to EN/IEC 61000-6-2, EMC directive conforming to EN/IEC 61000-6-3, EMC directive conforming to EN/IEC 61000-6-4, EMC directive conforming to EN/IEC 61131-2 zone B, low voltage directive conforming to EN/IEC 61131-2
current state 1 guaranteed >= 2 mA (I1...IA and IH...IR discrete input circuit), >= 0.5 mA (IB...IG used as discrete input circuit)
voltage state 1 guaranteed >= 7 V for IB...IG used as discrete input circuit, >= 5.6 V for I1...IA and IH...IR discrete input circuit
cycle time 6-90 ms
range of product Zelio Logic
product or component type Relay & Power Supply
net weight 0.38 kg
standards EN/IEC 61000-4-12, EN/IEC 61000-4-4 level 3, EN/IEC 61000-4-6 level 3, EN/IEC 61000-4-3, EN/IEC 61000-4-2 level 3, EN/IEC 61000-4-5, EN/IEC 61000-4-11, EN/IEC 60068-2-6 Fc, EN/IEC 60068-2-27 Ea
mechanical durability 10000000 cycles for relay output
range Smart Relay
[Us] rated supply voltage 12 V DC
analogue input type common mode
immunity to microbreaks 10 ms repeated 20 times
repeat accuracy +/- 2 % at 55 °C for analogue input circuit
input compatibility 3-wire proximity sensors PNP for discrete input
backup time 10 years at 25 °C
voltage state 0 guaranteed <= 3 V for IB...IG used as discrete input circuit, <= 2.4 V for I1...IA and IH...IR discrete input circuit
analogue input range 0...10 V, 0...12 V
conversion error +/- 5 % at 25 °C for analogue input circuit, +/- 6.2 % at 55 °C for analogue input circuit
conversion time smart relay cycle time for analogue input circuit
operating distance 10 m between stations, with screened cable (sensor not isolated) for analogue input circuit
analogue input resolution 8 bits at maximum voltage
reverse polarity protection with
connections - terminals screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) semi-solid, screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) solid, screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end, screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) solid, screw terminals, 2 x 0.25...2 x 0.75 mm² (AWG 24...AWG 18) flexible with cable end
power dissipation in W 2.5 W without extension
output voltage limits 5...30 V DC (relay output), 24...250 V AC (relay output)
operating altitude 2000 m
IP degree of protection IP20 (terminal block) conforming to IEC 60529, IP40 (front panel) conforming to IEC 60529
tightening torque 0.5 N.m
electrical durability AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1, AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to EN/IEC 60947-5-1, DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1, DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to EN/IEC 60947-5-1
response time 10 ms (from state 0 to state 1) for relay output, 5 ms (from state 1 to state 0) for relay output
contacts type and composition NO for relay output
supply voltage limits 10.4-14.4 V
number of outputs 8 relay
discrete input voltage 12 V DC
discrete input type resistive
discrete input number 12 conforming to EN/IEC 61131-2 type 1
analogue input number 6
maximum permissible voltage 14.4 V for analogue input circuit
input impedance 14 kOhm for IB...IG used as analogue input circuit, 14 kOhm for IB...IG used as discrete input circuit, 2.7 kOhm for I1...IA and IH...IR discrete input circuit
disturbance radiated/conducted class B conforming to EN 55022-11 group 1
output thermal current 8 A for all 8 outputs for relay output
number or control scheme lines 0-500 with FBD programming, 0-240 with ladder programming
clock drift 12 min/year at 0-55 °C, 6 s/month at 25-25 °C
discrete input current 4 mA
clock with
local display with
current state 0 guaranteed <= 0.9 mA (I1...IA and IH...IR discrete input circuit), <= 0.9 mA (IB...IG used as discrete input circuit)
maximum supply current 200 mA (without extension)
switching capacity in mA >= 10 mA at 12 V (relay output)
operating rate in Hz 0.1 Hz (at Ie) for relay output, 10 Hz (no load) for relay output
maximum altitude transport 3048 m
checks program memory on each power up
LSB value 39 mV for analogue input circuit
counting frequency 1 kHz for discrete input
PT. Telesindo Citra Sejahtera © 2025 All Rights Reserved.