Schneider Electric        
    
    
        
            
    
Zelio Logic compact smart relay - “discovery†pack - 12 I O - 24 V DC - SR2PACKBD
            Out of stock
        
    
            SKU
        
SR2PACKBD
                        More Information
                    
                        | Attribute | Value | 
|---|---|
| SKU | SR2PACKBD | 
| product certifications | GL, GOST, CSA, UL, C-Tick | 
| relative humidity | 95-95 % without condensation or dripping water | 
| ambient air temperature for storage | -40-70 °C | 
| overvoltage category | III conforming to EN/IEC 60664-1 | 
| pollution degree | 2 conforming to EN/IEC 61131-2 | 
| ambient air temperature for operation | -20-40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2, -20-55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2 | 
| environmental characteristic | EMC directive conforming to EN/IEC 61000-6-2, EMC directive conforming to EN/IEC 61000-6-3, EMC directive conforming to EN/IEC 61000-6-4, EMC directive conforming to EN/IEC 61131-2 zone B, low voltage directive conforming to EN/IEC 61131-2 | 
| current state 1 guaranteed | >= 1.2 mA (IB...IG used as discrete input circuit), >= 2.2 mA (I1...IA and IH...IR discrete input circuit) | 
| voltage state 1 guaranteed | >= 15 V for I1...IA and IH...IR discrete input circuit, >= 15 V for IB...IG used as discrete input circuit | 
| cycle time | 6-90 ms | 
| range of product | Zelio Logic | 
| product or component type | Relay & Power Supply | 
| net weight | 0.7 kg | 
| standards | EN/IEC 61000-4-12, EN/IEC 61000-4-4 level 3, EN/IEC 61000-4-6 level 3, EN/IEC 61000-4-3, EN/IEC 61000-4-2 level 3, EN/IEC 61000-4-5, EN/IEC 61000-4-11, EN/IEC 60068-2-6 Fc, EN/IEC 60068-2-27 Ea | 
| mechanical durability | 10000000 cycles for relay output | 
| range | Smart Relay | 
| [Uimp] rated impulse withstand voltage | 4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1 | 
| [Us] rated supply voltage | 24 V | 
| analogue input type | common mode | 
| immunity to microbreaks | 1 ms | 
| repeat accuracy | +/- 2 % at 55 °C for analogue input circuit | 
| input compatibility | 3-wire proximity sensors PNP for discrete input | 
| backup time | 10 years at 25 °C | 
| voltage state 0 guaranteed | <= 5 V for I1...IA and IH...IR discrete input circuit, <= 5 V for IB...IG used as discrete input circuit | 
| analogue input range | 0...10 V, 0...24 V | 
| conversion error | +/- 5 % at 25 °C for analogue input circuit, +/- 6.2 % at 55 °C for analogue input circuit | 
| conversion time | smart relay cycle time for analogue input circuit | 
| operating distance | 10 m between stations, with screened cable (sensor not isolated) for analogue input circuit | 
| analogue input resolution | 8 bits | 
| reverse polarity protection | with | 
| input/output number | 12 | 
| connections - terminals | screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) semi-solid, screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) solid, screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end, screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) solid, screw terminals, 2 x 0.25...2 x 0.75 mm² (AWG 24...AWG 18) flexible with cable end | 
| power dissipation in W | 3 W without extension | 
| output voltage limits | 5...30 V DC (relay output), 24...250 V AC (relay output) | 
| operating altitude | 2000 m | 
| IP degree of protection | IP20 (terminal block) conforming to IEC 60529, IP40 (front panel) conforming to IEC 60529 | 
| tightening torque | 0.5 N.m | 
| electrical durability | AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1, AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to EN/IEC 60947-5-1, DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1, DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to EN/IEC 60947-5-1 | 
| response time | 10 ms (from state 0 to state 1) for relay output, 5 ms (from state 1 to state 0) for relay output | 
| contacts type and composition | NO for relay output | 
| kit composition | Zelio Soft 2 programming software CD-ROM, cable PC SR2USB01 for connection to PC, SR2B121BD | 
| supply voltage limits | 19.2-30 V | 
| number of outputs | 4 relay | 
| discrete input voltage | 24 V DC | 
| discrete input type | resistive | 
| discrete input number | 8 conforming to EN/IEC 61131-2 type 1 | 
| analogue input number | 4 | 
| maximum permissible voltage | 30 V for analogue input circuit | 
| input impedance | 12 kOhm for IB...IG used as analogue input circuit, 12 kOhm for IB...IG used as discrete input circuit, 7.4 kOhm for I1...IA and IH...IR discrete input circuit | 
| disturbance radiated/conducted | class B conforming to EN 55022-11 group 1 | 
| output thermal current | 8 A for all 4 outputs for relay output | 
| number or control scheme lines | 120-120 with ladder programming, 0-200 with FBD programming | 
| clock drift | 12 min/year at 0-55 °C, 6 s/month at 25-25 °C | 
| discrete input current | 4 mA | 
| clock | with | 
| local display | with | 
| current state 0 guaranteed | <= 0.5 mA (IB...IG used as discrete input circuit), <= 0.75 mA (I1...IA and IH...IR discrete input circuit) | 
| maximum supply current | 100 mA (without extension) | 
| switching capacity in mA | >= 10 mA at 12 V (relay output) | 
| operating rate in Hz | 0.1 Hz (at Ie) for relay output, 10 Hz (no load) for relay output | 
| maximum altitude transport | 3048 m | 
| checks | program memory on each power up | 
| LSB value | 39 mV for analogue input circuit | 
| counting frequency | 1 kHz for discrete input | 
                        Technical Documents
                    
                    
    
                