Schneider Electric
Zelio Logic modular smart relay Zelio Logic - 26 I O - 24 V DC - clock - display - SR3B262BD
Out of stock
SKU
SR3B262BD
Details
This Zelio Logic SR3 compact smart relay / programmable controller uses a supply voltage of 24V direct current.
It has 26 inputs / outputs with screw-clamp terminals.
It has compact design, allowing installation on DIN rail.
It also offers simple programming, display and diagnosing of malfunctions display and navigation buttons.
Its simple ladder programming makes it adapted for non-specialists.
More Information
Attribute | Value |
---|---|
SKU | SR3B262BD |
product certifications | GL, GOST, CSA, UL, C-Tick |
relative humidity | 95-95 % without condensation or dripping water |
ambient air temperature for storage | -40-70 °C |
overvoltage category | III conforming to EN/IEC 60664-1 |
pollution degree | 2 conforming to EN/IEC 61131-2 |
ambient air temperature for operation | -20-40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2, -20-55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2 |
environmental characteristic | EMC directive conforming to EN/IEC 61000-6-2, EMC directive conforming to EN/IEC 61000-6-3, EMC directive conforming to EN/IEC 61000-6-4, EMC directive conforming to EN/IEC 61131-2 zone B, low voltage directive conforming to EN/IEC 61131-2 |
current state 1 guaranteed | >= 1.2 mA (IB...IG used as discrete input circuit), >= 2.2 mA (I1...IA and IH...IR discrete input circuit) |
voltage state 1 guaranteed | >= 15 V for I1...IA and IH...IR discrete input circuit, >= 15 V for IB...IG used as discrete input circuit |
cycle time | 6-90 ms |
output voltage | 24 V transistor output |
range of product | Zelio Logic |
product or component type | Relay & Power Supply |
net weight | 0.3 kg |
standards | EN/IEC 61000-4-12, EN/IEC 61000-4-4 level 3, EN/IEC 61000-4-6 level 3, EN/IEC 61000-4-3, EN/IEC 61000-4-2 level 3, EN/IEC 61000-4-5, EN/IEC 61000-4-11, EN/IEC 60068-2-6 Fc, EN/IEC 60068-2-27 Ea |
range | Smart Relay |
[Us] rated supply voltage | 24 V |
analogue input type | common mode |
short-circuit protection | with transistor output |
immunity to microbreaks | 1 ms |
repeat accuracy | +/- 2 % at 55 °C for analogue input circuit |
input compatibility | 3-wire proximity sensors PNP for discrete input |
backup time | 10 years at 25 °C |
voltage state 0 guaranteed | <= 5 V for I1...IA and IH...IR discrete input circuit, <= 5 V for IB...IG used as discrete input circuit |
analogue input range | 0...10 V, 0...24 V |
conversion error | +/- 5 % at 25 °C for analogue input circuit, +/- 6.2 % at 55 °C for analogue input circuit |
conversion time | smart relay cycle time for analogue input circuit |
operating distance | 10 m between stations, with screened cable (sensor not isolated) for analogue input circuit |
analogue input resolution | 8 bits |
reverse polarity protection | with |
[Ures] residual voltage | 2 V at state 1 transistor output |
connections - terminals | screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) semi-solid, screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) solid, screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end, screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) solid, screw terminals, 2 x 0.25...2 x 0.75 mm² (AWG 24...AWG 18) flexible with cable end |
power dissipation in W | 10 W with extensions, 5 W without extension |
output voltage limits | 19.2...30 V DC (transistor output) |
operating altitude | 2000 m |
IP degree of protection | IP20 (terminal block) conforming to IEC 60529, IP40 (front panel) conforming to IEC 60529 |
tightening torque | 0.5 N.m |
response time | <= 1 ms (from state 0 to state 1) for transistor output, <= 1 ms (from state 1 to state 0) for transistor output |
load current | 0.5-0.625 A transistor output |
supply voltage limits | 19.2-30 V |
number of outputs | 10 transistor |
discrete input voltage | 24 V DC |
discrete input type | resistive |
discrete input number | 16 conforming to EN/IEC 61131-2 type 1 |
analogue input number | 6 |
maximum permissible voltage | 30 V for analogue input circuit |
input impedance | 12 kOhm for IB...IG used as analogue input circuit, 12 kOhm for IB...IG used as discrete input circuit, 7.4 kOhm for I1...IA and IH...IR discrete input circuit |
disturbance radiated/conducted | class B conforming to EN 55022-11 group 1 |
number or control scheme lines | 0-500 with FBD programming, 0-240 with ladder programming |
clock drift | 12 min/year at 0-55 °C, 6 s/month at 25-25 °C |
discrete input current | 4 mA |
clock | with |
local display | with |
current state 0 guaranteed | <= 0.5 mA (IB...IG used as discrete input circuit), <= 0.75 mA (I1...IA and IH...IR discrete input circuit) |
maximum supply current | 180 mA (with extensions), 70 mA (without extension) |
maximum altitude transport | 3048 m |
checks | program memory on each power up |
LSB value | 39 mV for analogue input circuit |
counting frequency | 1 kHz for discrete input |
overload protection | with overload protection for transistor output |
Technical Documents