Schneider Electric
Zelio RXM - Relay Miniature Plug-in relay 3 C/O 24 V DC 10 A - RXM3AB1BD
Out of stock
SKU
RXM3AB1BD
Details
This Zelio RXM miniature plug-in relay has a coil control voltage of 24V DC and has 3 changeover contacts 3PDT (triple pole double throw) with a rating of 10A.
It has large choice of number of contacts for high rated current use with space-saving design.
It also offers one-step loackable test button and mechanical indicator for contact status.
It helps to reduce the size of enclosures and increase machine reliability: you can mount nearly everywhere.
The product is IP40 and has a transparent cover allowing operator to visually inspect the status of contacts.
Workablity for hard-wired logic automated systems to complement the functions of industrial progammable logic controllers (PLCs).
More Information
| Attribute | Value |
|---|---|
| SKU | RXM3AB1BD |
| product certifications | GOST, CSA, UL, CE, Lloyd's |
| ambient air temperature for storage | -40-85 °C |
| pollution degree | 2 |
| ambient air temperature for operation | -40-55 °C |
| safety reliability data | B10d = 100000 |
| average coil consumption | 0.9 W |
| test levels | level A group mounting |
| range of product | Harmony Relay |
| operating position | any position |
| product or component type | Relay & Power Supply |
| net weight | 0.037 kg |
| standards | CSA C22.2 No 14, UL 508, EN/IEC 61810-1 |
| mechanical durability | 10000000 cycles |
| device short name | RXM |
| range | Plug In Relay |
| [Ie] rated operational current | 10 A at 28 V (DC) NO conforming to IEC, 10 A at 250 V (AC) NO conforming to IEC, 5 A at 28 V (DC) NC conforming to IEC, 5 A at 250 V (AC) NC conforming to IEC, 10 A at 30 V (DC) conforming to UL, 10 A at 277 V (AC) conforming to UL |
| [Uc] control circuit voltage | 24 V DC |
| [Uimp] rated impulse withstand voltage | 4 kV during 1.2/50 µs |
| contacts material | AgNi |
| operating time | 20 ms |
| status LED | without |
| compatibility code | RXM |
| vibration resistance | 3 gn, amplitude = +/- 1 mm (f = 10-150 Hz)5 cycles in operation, 5 gn, amplitude = +/- 1 mm (f = 10-150 Hz)5 cycles not operating |
| dielectric strength | 1300 V AC between contacts with micro disconnection, 2000 V AC between coil and contact, 2000 V AC between poles |
| IP degree of protection | IP40 conforming to EN/IEC 60529 |
| electrical durability | 100000 cycles for resistive load |
| control type | lockable test button |
| device presentation | complete product |
| [Ui] rated insulation voltage | 250 V conforming to IEC, 300 V conforming to CSA, 300 V conforming to UL |
| contacts type and composition | 3 C/O |
| shock resistance | 10 gn for in operation, 30 gn for not operating |
| utilisation coefficient | 20 % |
| maximum switching capacity | 2500 VA/280 W |
| series name | Miniature |
| rated operational voltage limits | 19.2...26.4 V DC |
| operating rate | <= 1200 cycles/hour under load, <= 18000 cycles/hour no-load |
| protection category | RT I |
| reset time | 20 ms |
| shape of pin | flat |
| load current | 10 A at 250 V AC, 10 A at 28 V DC |
| drop-out voltage threshold | >= 0.1 Uc |
| minimum switching capacity | 170 mW at 10 mA, 17 V |
| [Ithe] conventional enclosed thermal current | 10 A at -40-55 °C |
| maximum switching voltage | 250 V conforming to IEC |
| average resistance | 650 Ohm at 20 °C +/- 10 % |
| CAD overall depth | 80.35 mm |
| CAD overall height | 82.8 mm |
Technical Documents